                                                                                                                     MECHANICAL VENTILATION

ALTERATIONS & ADDITIONS                                                                                              IF APPLICABLE ALL BATHROOMS, LAUNDRIES, AND WC'S NOT NATURALLY VENTILATED ARE TO BE MECHANICALLY VENTILATED IN
                                                                                                                     ACCORDANCE WITH AS1668.2 AND AS/NZS 3666.1

                                                                                                                     TERMITE PROTECTION
                                                                                                                     SUPPLY & INSTALL A TERMITE BARRIER SYSTEM IN ACCORDANCE WITH AS 3660, AS 3660.1, AND THE NCC PART 3.1.3. INSTALL TO THE
SITE ADDRESS                                                                                                         MANUFACTURER'S SPECIFICATIONS AND PROVIDE WRITTEN WARRANTIES COMMENCING FROM THE DATE OF PRACTICAL COMPLETION.
24 THE PENINSULA, NOOSAVILLE, QLD, 4567
                                                                                                                     WINDOW FRAMES & GLAZING
                                                                                                                                                                                                                                                                                               M Design
RP DESCRIPTION                                                                                                       WINDOW FRAMES AND GLAZING SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS 2047, AS 1288 AND TO AS3959 PART 6.5.2                                                               PO Box 290
                                                                                                                                                                                                                                                                                               Peregian Beach QLD 4573
Lot 441 on RP856191                                                                                                  EXTERNAL DOORS                                                                                                                                                            QBCC No. 1066058
                                                                                                                     SIDE HUNG EXTERNAL DOORS SHALL BE CONSTRUCTED IN ACCORDANCE WITH AS3959 PART 6.5.3.
SITE AREA                                                                                                            EXTERNAL SLIDING DOORS SHALL COMPLY WITH AS3595 PART 6.5.4. GARAGE DOORS SHALL COMPLY WITH AS3595 PART 6.5.5                                                              Contact: Michael Broeren
                                                                                                                                                                                                                                                                                               t. 07 5471 2721
811m²                                                                                                                                                                                                                                                                                          t. 0422 969 645
                                                                                                                     SMOKE ALARMS & EMERGENCY LIGHTING
                                                                                                                                                                                                                                                                                               w. www.mdesign.com.au
LOCAL AUTHORITY                                                                                                      SUPPLY & INSTALL INTERCONNECTING HARD-WIRED SMOKE ALARMS IN ACCORDANCE WITH PART E2 OF THE NCC & AS 1670.
                                                                                                                     NEW & PROPOERTY UPGRADED SMOKE ALARMS MUST BE BE PHOTOELECTRIC AND COMPLY WITH AUSTRALIAN STANDARD 3786-2014,                                                             © COPYRIGHT 2021 - M DESIGN
NOOSA COUNCIL                                                                                                        NOT ALSO CONTAIN AN ISOLATION SENSORE, BE LESS THAN 10YRS OLD, OPERATE WHEN TESTED AND BE INTERCONNECTING WITH                                                            THE IDEAS AND CONCEPTS CONTAINED
                                                                                                                     EVERY OTHER REQUIRED SMOKE ALARM IN THE DWELLING SO ENSURING THEY ALL ACTIVATE TOGETHER                                                                                   WITHIN THIS DOCUMENT AND THE
                                                                                                                                                                                                                                                                                               DOCUMENT ITSELF REMAIN THE
CONSTRUCTION NOTES                                                                                                   WATERPROOFING - WET AREAS
                                                                                                                     WATERPROOFING OF INTERNAL WET AREAS SHALL COMPLY WITH AS3740 AND THE BCA, PART 3.8.1. PROVIDE A PROPRIETARY LIQUID OR
                                                                                                                                                                                                                                                                                               INTELLECTUAL PROPERTY OF
CONSTRUCTION NOTES TO BE READ IN CONJUNCTION WITH ALL OTHER DRAWINGS AND DOCUMENTS                                                                                                                                                                                                             M DESIGN AND MAY NOT BE COPIED OR
                                                                                                                     SHEET MEMBRANE SYSTEM AND FALL TO WASTES. ALL WATERPROOFING SHALL REMAIN THE RESPONSIBILITY OF THE BUILDER. PROVIDE                                                       REPRODUCED IN PART OR IN WHOLE
                                                                                                                     WRITTEN WARRANTIES COMMENCING FROM THE DATE OF PRACTICAL COMPLETION.                                                                                                      WITHOUT EXPRESSED WRITTEN
CONSTRUCTION REFERENCE DOCUMENTS:
                                                                                                                                                                                                                                                                                               PERMISSION FROM MICHAEL BROEREN
ALL WORK TO COMPLY WITH THE REQUIREMENTS OF THE NATIONAL CONSTRUCTION CODE OF AUSTRALIA 2016 (NCC) HOUSING           WATERPROOFING - WALL OPENINGS                                                                                                                                             OF M DESIGN.
PROVISIONS VOLUME TWO, RELEVANT AUSTRALIAN STANDARDS AND THEIR MOST CURRENT AMENDMENTS,                              INSTALL ALL NECESSARY FLASHINGS, MEMBRANES, DRIPS, STORM MOULDS, CAULKING ETC SO THAT WATER IS PREVENTED FROM
AND THE QUEENSLAND DEVELOPMENT CODE                                                                                  PENETRATING THE BUILDING BETWEEN FRAMES AND THE BUILDING STRUCTURE. PROVIDE WRITTEN WARRANTIES COMMENCING FROM THE




                                                                                                                                                                                                                                                                                                                  09.12.21
                                                                                                                                                                                                                                                                                                                  04.02.22
                                                                                                                                                                                                                                                                                                DATE
                                                                                                                     DATE OF PRACTICAL COMPLETION.
BUILDING CLASSIFICATION = 1a & 10a
                                                                                                                     WATERPROOFING - DECKS
LOCAL AUTHORITY:                                                                                                     LAY JAMES HARDIE EXTERIOR SECURER BOARD WITH 3 COAT ROLL ON WATERPROOF SYSTEM. TILE FLOOR TO FALL TO GRATED DRAIN.
THE WORK IS TO BE CARRIED OUT IN ACCORDANCE WITH APPLICABLE LOCAL AUTHORITY REGULATIONS IN RELATION TO THE           INSTALL ALL NECESSARY FLASHINGS, MEMBRANES, DRIPS, ETC SO THAT WATER IS PREVENTED FROM PENETRATING THE BUILDING AROUND
CLASS AND TYPE OF CONSTRUCTION, INCLUDING CONDITIONS SET OUT IN RELATED DEVELOPMENT PERMITS & APPROVALS.             THE DECK. PROVIDE WRITTEN WARRANTIES COMMENCING FROM THE DATE OF PRACTICAL COMPLETION.
                                                                                                                                                                                                                         to AS4654
SETOUT, LEVELS, AND DIMENSIONS:                                                                                      FALLS IN FLOORS
BEFORE COMMENCING CONSTRUCTION ALL DIMENSIONS, EXISTING LEVELS, FINISHED LEVELS AND ALL SITE SERVICES ARE TO BE




                                                                                                                                                                                                                                                                                                DESCRIPTION
                                                                                                                     FALL WET AREA FLOORS TO FLOOR WASTES. FALL ALL EXTERNAL SURFACES AWAY FROM THE BUILDING AND/OR TO DRAINAGE OUTLETS
VERIFIED BY THE BUILDER. NOTIFY THE DESIGNER OF ANY VARIATION BETWEEN THE DOCUMENTATION AND SITE CONDITIONS.         UNLESS OTHERWISE NOTED. PROVIDE SLAB SET-DOWNS, STRUCTURAL FALLS, & BEDDINGS AS REQUIRED.

FLOOR LEVELS:                                                                                                        STAIRS, HANDRAILS & BALUSTRADES




                                                                                                                                                                                                                                                                                                                  FOR CERTIFICATION
ALL STRUCTURAL AND FINISHED FLOOR SURFACE LEVELS AND GRADES ARE TO BE CONFIRMED WITH THE DESIGNER PRIOR TO           STAIRS, HANDRAILS AND BALUSTRADES TO BE CONSTRUCTED IN ACCORDANCE WITH THE NCC, PARTS 3.9.1 & 3.9.2, INCLUDING AS1170.1 AND
THE COMMENCEMENT OF ANY WORK.                                                                                        AS1288. BALUSTRADES TO HAVE A MINIMUM HEIGHT OF 1000mm ABOVE FINISHED SURFACE LEVEL UNLESS NOTED OTHERWISE. STAIR




                                                                                                                                                                                                                                                                                                                  FOR QUOTING
                                                                                                                     BALUSTRADE TO HAVE A MINIMUM HEIGHT OF 865mm ABOVE STAIR NOSING UNLESS NOTED OTHERWISE.
DRAWINGS:
WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALING OFF DRAWINGS. DO NOT SCALE FROM DRAWINGS. NOTIFY THE                 THERMAL INSULATION
DESIGNER OF ANY VARIATIONS OR DISCREPANCIES IN THE DIMENSIONING OF THE PLANS.                                        SUPPLY & INSTALL THERMAL INSULATION (ALL WALL SARKING TO BE BRADFORDS Enviroseal™ ProctorWrap™ RW FOR RESIDENTIAL WALL OR
                                                                                                                     SIMILAR APPROVED.) IN ACCORDANCE WITH THE NCC, PART 3.12.1. ALSO REFER TO THE ENERGY EFFICIENCY REPORT, AND SCHEDULES
GEOTECHNICAL REPORT:




                                                                                                                                                                                                                                                                                                REV
                                                                                                                     FOR PRODUCT SELECTIONS.




                                                                                                                                                                                                                                                                                                                  D
                                                                                                                                                                                                                                                                                                                  B
ARCHITECTURAL DRAWINGS AND DOCUMENTS ARE TO BE READ IN CONJUNCTION WITH THE GEOTECHNICAL REPORT. REFER TO
THE SPECIFICATION APPENDICES.                                                                                        LIGHTING
                                                                                                                     LIGHTING SHALL BE PROVIDED ACCORDANCE WITH THE NCC PART J6 & AS1680
STRUCTURAL ENGINEERING (FOUNDATIONS):
ARCHITECTURAL DRAWINGS AND DOCUMENTS ARE TO BE READ IN CONJUNCTION WITH THE ENGINEERS DRAWINGS. REFER TO             FLASHINGS
ENGINEERING DRAWINGS FOR ALL FOOTINGS, SLABS, AND MASONRY DESIGN & DETAILS.                                          FLASHINGS SHALL GENERALLY BE CORROSION RESISTANT, COMPATIBLE WITH THE OTHER MATERIALS IN THE INSTALLATION, AND COATED




                                                                                                                                                                                                                                                                                                                                                                         24 THE PENINSULA, NOOSAVILLE,
                                                                                                                     WITH A NON-STAINING COMPOUND WHERE NECESSARY IN ACCORDANCE WITH AS/NZS 2904.
LIGHT STEEL FRAME & STRUCTURAL STEEL:
THE BUILDING FRAMES AND STRUCTURAL STEEL MEMBERS ARE TO BE DESIGNED, SUPPLIED, & INSTALLED BY A SUITABLY             ELECTRICAL SERVICES
QUALIFIED FRAMING CONTRACTOR INCLUDING BUT NOT LIMITED TO ALL ROOF, WALL, FLOOR, CEILING, POSTS, BEAMS, AND




                                                                                                                                                                                                                                                                                                ALTERATIONS & ADDITIONS
                                                                                                                     ELECTRICAL SERVICES TO BE PROVIDED IN ACCORDANCE WITH THE FOLLOWING:
BRACING MEMBERS. STEEL MEMBERS SHALL MEET THE REQUIREMENTS OF AS 4100 STEEL STRUCTURES, AS/NZS 4600 COLD-            ELECTRICAL INSTALLATION: TO AS/NZS 3008.1.1 AND SAA HB 301.
FORMED STEEL STRUCTURES, AND THE N.A.S.H. (NATIONAL ASSOCIATION OF STEEL HOUSING) STANDARD. PROVIDE STRUCTURAL       TELECOMMUNICATIONS CABLING: TO AS/ACIF S008, AS/ACIF S009, AS/NZS 3080, SAA HB 29 AND SAA HB 252.
CERTIFICATION AND WARRANTIES AS REQUIRED BY THE CERTIFIER AND PROPRIETOR RESPECTIVELY.                               DOMESTIC ELECTRICITY METER ENCLOSURES: TO AS 6002.

GALVANISING OF STRUCTURAL STEELWORK:                                                                                 EXTERIOR ROOFING & CLADDING SYSTEMS
ALL STRUCTURAL STEELWORK, FITTINGS AND FIXTURES SHALL BE HOT DIPPED GALVANISED IN ACCORDANCE WITH AS/NZS 4680        ALL EXTERIOR ROOFING & CLADDING SYSTEMS ARE TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS,




                                                                                                                                                                                                                                                   PRELIMINARY DESIGN - NOT FOR CONSTRUCTION
& AS 2309. ALL OTHER STEELWORK, FITTINGS AND FIXTURES SHALL BE PASSIVE GALVANISED UNLESS NOTED OTHERWISE IN THE      INCLUDING ALL FASTENERS, EXPANSION JOINTS, GASKETS, TRIMS, AND THE LIKE. SHEET METAL ROOFING: TO AS 1562.1. CORROSION
FINISHES SCHEDULES. AVOID ON SITE WELDING.                                                                           PROTECTION TO NCC TABLE 3.5.1.1.A. ROOF CONSTRUCTION TO COMPLY WITH AS3595 PART 6.6




                                                                                                                                                                                                                                                                                                                                      KIRSTY WILSON
                                                                                                                     FIBRE CEMENT CLADDING: TO AS/NZS 2908.2 TYPE A, AND TO AS 3959 PART 6.4.1
TEMPORARY EROSION CONTROL:
CONTRACTOR TO PROVIDE ALL NECESSARY EROSION CONTROL MEASURES, SILT BARRIERS, AND THE LIKE DURING                     INTERIOR LININGS & PLASTERBOARD
CONSTRUCTION IN ACCORDANCE WITH LOCAL AUTHORITY REQUIREMENTS AND AS APPROPRIATE TO CONTROL EROSION ON THE            ALL INTERIOR LININGS ARE TO BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS, INCLUDING ALL FASTENERS,




                                                                                                                                                                                                                                                                                                                                                      Project Address:



                                                                                                                                                                                                                                                                                                                                                                         QLD, 4567
SITE.                                                                                                                EXPANSION JOINTS, TRIMS, AND THE LIKE. PLASTERBOARD SHALL BE INSTALLED IN ACCORDANCE WITH AS 2589 GENERALLY, WET AREA'S
                                                                                                                     TO AS 3740. LININGS TO EXTERNAL BLOCK WALLS SHALL BE INSTALLED ON A PROPRIETARY STEEL FURRING CHANNEL SYSTEM - REFER TO
POWER CONNECTION                                                                                                     DRAWINGS FOR WALL DETAILS AND SCHEDULES FOR FINISHES.
BEFORE CONSTRUCTION COMMENCES THE CLIENT WILL PROVIDE A TEMPORARY POWER BOARD ADJACENT TO THE BUILDING
PLATFORM. CONTRACTOR TO CO-ORDINATE CONNECTION OF POWER TO THE BUILDING, AND COMMISSIONING.                          LANDSCAPING




                                                                                                                                                                                                                                                                                                                          For:
                                                                                                                     CONTRACTOR TO PROVIDE ALL EXTERNAL PAVING SLABS, DECKS AND ROCK RETAINING WALLS AS IDENTIFIED ON THE DRAWINGS.
PLUMBING, DRAINAGE & GAS
DESIGN, SUPPLY, & INSTALL ALL PLUMBING & DRAINAGE IN ACCORDANCE WITH AS3500 AND THE NCC, PART 3.1.2. AND TO AS3595   CONCRETE
PART 6.8. GAS INSTALLATIONS TO BE IN ACCORDANCE WITH AS 5601.                                                        ALL CONCRETE FLOORS AND PAVING SLABS SHALL BE REINFORCED CONCRETE IN ACCORDANCE WITH STRUCTURAL ENGINEER'S                                                                sheet title:
                                                                                                                     DRAWINGS. REFER TO SCHEDULES FOR THE REQUIRED FINISH.
VENT & WASTE PIPES
CONCEAL ALL VENT PIPES AND WASTE PIPES WITHIN WALL FRAMING UNLESS OTHERWISE NOTED, IE RETURN WASTES TO WALLS
                                                                                                                                                                                                                                                                                               GENERAL
                                                                                                                     TILING
UNDER SINKS. PROVIDE MINIMUM Rw45 SOUND ATTENUATION GENERALLY BETWEEN PLUMBING DUCTS AND INTERNAL SPACES.            TILES TO BE INSTALLED TO MANUFACTURERS SPECIFICATION & SHALL BE INSTALLED BY AN APPROVED APPLICATOR.                                                                      NOTES
CEILING ACCESS                                                                                                       SLIP RESISTANCE                                                                                                                                                            job no:                                               drawn by:
CEILING ACCESS MANHOLES ARE TO LOCATED TO SUIT ROOF FRAMING. POSITION FRAMES SO AS TO PROVIDE A CLEAR 600mm x        ALL INTERIOR & EXTERIOR FLOOR FINISHES TO COMPLY WITH AS 4586 FOR SLIP RESISTANCE INCLUDING STAIRS. PROVIDE WRITTEN                                                       2119                                                   JM
600mm OPENING.                                                                                                       EVIDENCE OF RATING UPON PRACTICAL COMPLETION.

PAINTING                                                                                                                                                                                                                                                                                        date: 04.02.22
                                                                                                                     TIMBER
COMPLY WITH THE RECOMMENDATIONS OF AS/NZS 2311.                                                                      TIMBER CONSTRUCTION TO BE IN ACCORDANCE WITH AS 1684 AND THE NCC. PARTICLEBOARD FLOORING MATERIAL TO AS/NZS 1860.1. FIBRE
AIR CONDITIONING SYSTEMS - BY OTHERS                                                                                 CEMENT FLOORING COMPRESSED SHEETS TO AS/NZS 2908.2 TYPE A, CATEGORY 5. PLYWOOD FLOORING STANDARD TO AS/NZS 2269.0,
AIR CONDITIONING SYSTEMS TO BE PROVIDED IN ACCORDANCE WITH AS/NZS 1668.1 AND AS 1668.2 AS REQUIRED BY THE NCC.                                                                                                                                                                                 scale (A3):                                                       drawing no:
                                                                                                                     BOND TYPE A, TONGUE AND GROOVED.
                                                                                                                                                                                                                                                                                                1 : 100                                                                     00
Log in to download the original file

Archs - 2022-02-09T100137.799.pdf · 2.1 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.