Table 6.3 – Existing Site Peak Flow Rates (L/s)
Storm Event Q1 Q2 Q5 Q10 Q20 Q50 Q100
(1EY) (0.5EY) (0.5EY) (10%AEP) (5%AEP) (2%AEP) (1%AEP)
Existing PFR 111 160 216 251 295 352 391
(PFR – Peak Flow Rate)
6.1.2 Proposed Site
The development consists of the construction of residential townhouse/ unit development along with a
shared access driveway and ground level landscaping/ courtyards & a community pool area. The total
pervious area for the site was calculated to be approximately 1330m2 which equates to a fraction
impervious of 0.79.
The Developed site catchment is as follows.
- Area – 0.6326 Ha
- Tc – 6 mins
- Fraction Impervious (Fi) – 0.79
Peak flow rates for the median design storms for the developed site are given in Table 6.4
Table 6.4 – Developed Site Peak Flow Rates (L/s)
Storm Event Q1 Q2 Q5 Q10 Q20 Q50 Q100
(1EY) (0.5EY) (0.2EY) (10%AEP) (5%AEP) (2%AEP) (1%AEP)
Developed 184 232 286 347 399 468 523
PFR
(PFR – Peak Flow Rate)
6.1.3 Peak Flow Comparison
Table 6.5 indicates the increased peak flow rates for the developed cases.
Table 6.5 – Comparison of Existing Vs Developed Peak Flows (L/s)
AEP Q1 Q2 Q5 Q10 Q20 Q50 Q100
Storm (1EY) (0.5EY) (0.2EY) (10%AEP) (5%AEP) (2%AEP) (1%AEP)
Increase 73 72 70 96 104 116 132
PF
(PF – Peak Flow )
SCG Consulting Engineers Page 16 SCG Ref: 33132(SWMP)