Wingara Hills Pty Ltd
Permanent batters should not be steeper than 1V:2H in the natural stiff (or stiffer) clays. Batters in extremely
weathered mudstone may be constructed at 1V:1H (subject to inspection by Core).
Further positive support by engineer-designed retaining structures may also be required where space
restrictions prevent trimming of batters to safe slopes and where slopes are surcharged or near movement
sensitive structures (ref Section 7.2).
Permanent batters that are not retained should be protected from erosion (e.g. revegetation or stone
pitching).
7.1.4 Erosion Protection
Any excavations or disturbance of materials should be carefully monitored and managed during the
construction phase to minimise potential for scour/erosion and sediment run off.
Exposed soil (i.e. on batters or drains) should be protected from erosion by appropriate measures such as
re-vegetation and hydro-seeding, protective matting, geotextiles or hard facings. Temporary sediment control
should be adopted during construction where surface water will flow offsite. Concentrating surface runoff
should be avoided unless adequate erosion protection and flow dissipation is constructed.
7.2 Retaining Structures
Design for retaining structures could be carried out using a triangular pressure distribution applicable to the
wall type and based on the parameters listed in Table 4. The values in Table 4 assume that the walls are
fully drained and no allowance is included below for construction loading, up-slope footing loadings, and
backfill compaction stresses. Retaining walls should be founded as described in Section 7.3.
Positive permanent drainage (surface and subsoil) must be installed behind retaining walls to prevent the
development of hydrostatic pressures. Drainage outlets must extend beyond the ends of the walls.
Retaining wall backfill should be a loose, free draining granular material and should only be lightly
compacted as heavy compaction may raise the earth pressure to above the ‘at rest’ earth pressure.
Table 3: Retaining structure design parameters.
Lateral earth pressure coefficient
Unit Friction Non-
Cohesion, Yielding
Retained material weight angle yielding
cu (kPa)
(t/m3) (degrees)
Ka
Kp Ko
(cantilever)
Stiff clay - Residual Soil 1.8 25 50-100 0.41 2.5 0.58
Very Stiff to Hard Clay - Residual
1.9 30 100-200 0.33 3.00 0.50
Soil
Extremely Weathered
1.9 34 >1000 0.38 3.54 0.44
Material/Mudstone
Notes:
Ka - active; Ko - at rest; Kp - passive
For yielding walls active state develops when: Deflection > 0.001H to 0.004H (granular soil),
or deflection > 0.01H to 0.04H (cohesive soil)
7.3 Footings
The proposed structures could be supported on a combination of high-level strip/pad and/or piered footings
founded at least 300 mm into stiff (or stiffer) residual soils or extremely weathered material/mudstone below
depths of 1.2 m BGL. Design bearing pressures are provided in Section 7.3.2.
J002915-001-R-Rev0 9
Document Set ID: 24031832
Version: 1, Version Date: 14/08/2025