                                                             BRW Enterprises (Qld) Pty Ltd
“DA Report”, PF 80 Cooroy Care Farm Development for LCC.                           Page : 8
______________________________________________________________________________________

The design shall incorporate strategically located control valves. Each cold water riser shall be
isolated at the bottom (or top in cases of downfeeds). Branch lines shall be isolated at the riser on
each level and further, where servicing an outlet or group of outlets. Isolation valves shall be
butterfly valves where the service exceeds 80mm diameter. Ball valves shall be used on services less
than 80mm diameter. All valves shall be tagged to identify the areas serviced.

All fittings shall comply with the requirements of SAA MP52 and shall have AS markings and
manufacturer’s License N° stamped into the fitting.

Pressure reducing valves set to 500kPa (in accordance with Australian Standard, AS 3500) are to be
installed to equipment, pipework, etc requiring pressure limitations.




                                                                               Document : 14,967/da-rep/A
Log in to download the original file

Appendix K - Hydraulic and Wet Fire Services Report.pdf · 544 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.