RFI - S25-054 Revised Concept Issue 18.06.2025 updated

of 40

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

Very large file (34.6 MB): the original may take a few minutes to open or download. The page text below is quick to read.

Original PDF page 1, section 1. The text section number identifies this passage in the reader.

           PROPOSED RESIDENTIAL DEVELOPMENT
           3 ALLAMBI RISE - NOOSA HEADS
           CLIENT NAME
           PROJECT No. S25-054




                                                                                                                                                                                                                                                                                                   NOT FOR CONSTRUCTION
C1    ##.##.####   REVISION NAME                                                                                                                         BRISBANE
                                               DESIGNED:         APPROVED:
                                                                                                                                                    T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT             PROJECT NUMBER
                                                                                                                                                                       SHAUN LOCKYER ARCHITECTS                                                                                                                    S25-054
                                                                                                           WE S TE R A
                                                                                                                                                      GOLD COAST
                                               DRAWN:
                                                                                                                                                    T: 07 5571 1599                                                                                       LOCATION: 3 ALLAMBI RISE - NOOSA HEADS
                                                                                                                                                  SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                 SHEET NUMBER
                                               CHECKED:
                                                                                                           PART NE RS                               T: 07 5391 3777
                                                                                                                                                   NORTHERN NSW
                                                                                                                                                                      USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                      PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                          TITLE:    COVER SHEET
                                                                                                                                                                                                                                                                                                                     0.0
                                                                                                                                                                                                                                                                                                                      .
                                               DATE:                                          STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                    T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                 CENTRAL VICTORIA
                                                                                                                                                                                                                                                                    CLIENT NAME                                            ##
                                                                                                                                                                      STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                               PAGE SIZE:   A3   For and on behalf of          www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                      CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                               REVISION
No.    DATE        REVISIONS       DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                         T: 03 5441 0922
Log in to download the original file

RFI - S25-054 Revised Concept Issue 18.06.2025 updated.pdf · 34.6 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

Full text of sections 2 to 12 (of 40)

Section 2

 STANDARD SAFE DESIGN REPORT (STD SDR REPORT)                                                                                          SDR5       ALL ASPECTS DETAILED OR NOTED IN THE WESTERA CIVIL/ENVIRONMENTAL/STRUCTURAL DOCUMENTS ARE SDR18                                                                  IT IS THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR'S RESPONSIBILITY TO ENSURE
                                                                                                                                                  THOSE REQUIRED FOR THE COMPLETED PROJECT OR DEVELOPMENT ONLY. THE BUILDER, PROJECT                                                                               THAT SITE WORKERS ARE SUITABLY QUALIFIED, TRAINED AND INSURED FOR THE TASKS BEING
 IN ACCORDANCE WITH THE WORK HEALTH AND SAFETY ACT AND REGULATIONS 2011 THE FOLLOWING CHECKED
                                                                                                                                                  MANAGER OR PRINCIPAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY NECESSARY                                                                                 UNDERTAKEN ON SITE. (CCD) (CE)
 TASKS AND HAZARDS HAVE BEEN IDENTIFIED AS POTENTIAL CONSTRUCTION RELATED HAZARDS ASSOCIATED
 WITH IMPLEMENTING THE DESIGN AS DOCUMENTED.                                                                                                      TEMPORARY CONNECTIONS AS WELL AS SUPPORTS AND BRACING TO MAINTAIN THE STABILITY AND SAFETY
                                                                                                                                                  OF THE RELEVANT STRUCTURES THROUGHOUT THE CONSTRUCTION PERIOD. THIS INCLUDES ELEMENTS       SDR19                                                                IT IS THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT
        (CCD) CONSTRUCTION CONFORMANCE TO DESIGN - SDR1,2,3,4,5,6,7,11,12,13,16,18,26,28                                                          SUCH AS PREFABRICATED TIMBER AND STEEL ELEMENTS, UNRESTRAINED WALLS, CONCRETE COLUMNS,                                                                           ALL SITE PERSONNEL ARE PROVIDED ADEQUATE SPACE, VENTILATION AND APPROPRIATE PERSONAL
        RISK LEVEL = 3                                                                                                                            BEAMS AND SLABS, PRECAST PANELS, ETC WHICH REQUIRE TEMPORARY SUPPORT OR PROPPING TO                                                                              PROTECTIVE EQUIPMENT TO UNDERTAKE THE WORKS REQUIRED. ALL CONSTRUCTION EQUIPMENT IS TO
        (SA&SWP) SITE ACCESS CONTROL AND FENCING INCLUDING STAIRS, SCAFFOLD, LADDERS, RAILINGS, SAFE WORK                                         PREVENT OVER STRESS, EXCESSIVE DEFORMATION OR INSTABILITY UNTIL THE FINAL STRUCTURAL SYSTEM                                                                      BE USED IN ACCORDANCE WITH BEST INDUSTRY SAFETY PRACTICES AND REGULATIONS. (GSW) (SWD&E)
        PLATFORMS FREE FROM FALLING DEBRIS AND ADEQUATE WORKSPACE - SDR8,14,21,23,28                                                              IS COMPLETED. THE DESIGNER IS TO BE CONTACTED FOR FURTHER ADVICE IF REQUIRED. (CCD)
                                                                                                                                                                                                                                              SDR20                                                                DEMOLITION WORKS ARE REQUIRED TO BE CARRIED OUT IN A SAFE, SYSTEMATIC AND ORDERLY MANNER IN
        RISK LEVEL = 6
                                                                                                                                       SDR6       WHERE THESE DESIGN DRAWINGS ONLY DOCUMENT PART OF A PROJECT OR DEVELOPMENT, IT IS THE                                                                            ACCORDANCE WITH THE SITE SPECIFIC SAFETY PLAN AND ALL GENERAL SAFETY INDUCTION REGULATIONS.
        (GSW) GENERAL SITE WORKS - SDR2,6,9,10,11,12,14,15,17,19,25,26,28                                                                         BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR'S RESPONSIBILITY TO ENSURE ALL DESIGN                                                                           TEMPORARY PROPPING OF MEMBERS MAYBE REQUIRED IN ACCORDANCE WITH THE DIRECTION OF A
        RISK LEVEL = 6                                                                                                                            DRAWINGS ARE COORDINATED BETWEEN CONSULTANTS. FOR EXAMPLE, CO-ORDINATION TO ENSURE                                                                               SUITABLY QUALIFIED PROFESSIONAL IN ACCORDANCE WITH RELEVANT SAFETY PRACTICES AND
                                                                                                                                                  APPROPRIATE SLAB THICKENINGS AND DETAILING FOR SEWAGE/STORMWATER CONNECTIONS,                                                                                    REGULATIONS. (DEM) (SIC)
        (CE) USE OF CONSTRUCTION EQUIPMENT - SDR18,24,28
        RISK LEVEL = 6                                                                                                                            LOAD-BEARING AND BRACING WALL ELEMENTS, CAST IN FIXINGS, ETC. (CCD) (GSW)
                                                                                                                                                                                                                                              SDR21                                                                AT ALL TIMES THE BUILDER, PROJECT MANAGER, OR PRINCIPAL CONTRACTOR IS TO PROVIDE LOCAL
        (SWD&E) STORMWATER, DRAINAGE AND ELECTRICAL SERVICES WORK - SDR9,10,14,19,28                                                   SDR7       NO ALLOWANCE HAS BEEN MADE FOR CONSTRUCTION LOADS INCLUDING STACKING OF MATERIALS ON                                                                             TRAFFIC AND PEDESTRIAN MANAGEMENT PLANS AS NEEDED TO ENSURE SAFE ACCESS AROUND AND ONTO
        RISK LEVEL = 6                                                                                                                            DECKS, FLOORS OR ROOF PLATFORMS, LOADS IMPOSED DUE TO PLANT, MACHINERY, LIFTING DEVICES,                                                                         THE BUILDING SITE. CONSIDERATION MUST ALSO BE GIVEN TO SAFE WORKER ACCESS TO ALL WORK AREA
                                                                                                                                                  IMPACT/VIBRATION/CYCLIC LOADS, ETC. IT IS THE BUILDER, PROJECT MANAGER OR PRINCIPAL                                                                              INCLUDING ADEQUATE WALKWAYS AND STAIRS, SCAFFOLDING, SECURE LADDER ACCESS, SAFE WORKING
        (W@H) WORKING AT HEIGHTS - SDR21,22,23,28                                                                                                 CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE DESIGNER OF ANY LOADS, THAT ARE NOT DOCUMENTED,                                                                        PLATFORMS, ACCESS PATHS FREE FROM FALLING OBJECTS, ADEQUATE RAILINGS, FALL ARREST SYSTEMS,
        RISK LEVEL = 7                                                                                                                            THAT THE STRUCTURE MAY BE SUBJECTED TO DURING CONSTRUCTION. (SIC) (OL) (EA) (CCD)                                                                                ETC. ALL PITS, FLOOR CAVITIES AND RELATED COVERS AND GRATES MUST BE MADE SAFE. (SA&SWP)
        (DEM) DEMOLITION - SDR10,15,18,20,26,28                                                                                                                                                                                                                                                                    (W@H) (FC)
                                                                                                                                       SDR8       UNLESS NOTED ON THE DRAWINGS NO ADDITIONAL ALLOWANCE HAS BEEN MADE FOR SPECIFIC LOADS
        RISK LEVEL = 7                                                                                                                            ASSOCIATED WITH THE MAINTENANCE OF THE STRUCTURE OR DEVELOPMENT.                                                                                   SDR22         ALL FORMWORK AND SCAFFOLDING SYSTEMS ARE TO BE DESIGNED AND CERTIFIED BY A LICENSED
        (EA) ENVIRONMENTAL GROUND VIBRATIONS, NOISE AND DUST - SDR7,9,28                                                                          THE DESIGNER IS TO BE INFORMED OF ANY REQUIREMENTS NECESSARY TO EXTERNALLY SUPPORT                                                                               CONTRACTOR TO COMPLY WITH RELEVANT AUSTRALIAN STANDARDS AND KEPT AND MAINTAINED IN A
        RISK LEVEL = 6                                                                                                                            PLATFORMS, CRANES, SCAFFOLDS ETC AS REQUIRED. (SIC) (SA&SWP) (CCD) (OL)                                                                                          GOOD WORKING ORDER. REGULAR CHECKS ON ERECTED MEMBERS AND FIXINGS MUST BE CARRIED OUT
                                                                                                                                                                                                                                                                                                                   BY A QUALIFIED PROFESSIONAL TO ENSURE COMPLIANCE WITH THE DESIGN. (FC) (W@H)
        (SP&IT) SURROUNDING PROPERTY AND INFRASTRUCTURE INCLUDING TREES - SDR9,10,28                                                   SDR9       DURING CONSTRUCTION, THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR SHALL
        RISK LEVEL = 5                                                                                                                            PROTECT NEIGHBOURING PROPERTIES FROM NOISE AND DUST IN ACCORDANCE WITH LOCAL                                                                       SDR23         CLIMBING ON SCAFFOLDING OR FORMWORK AND WORKING AT HEIGHTS WITHOUT SUITABLY
                                                                                                                                                  AUTHORITY REQUIREMENTS, RADIATION, GROUND VIBRATIONS, STORMWATER FLOWS AND OTHER                                                                                 APPROVED RAILINGS, BARRIERS AND RESTRAINTS FIXED OFF TO CERTIFIED ANCHOR POINTS IS
        (EX) TRENCHING AND EXCAVATIONS >1m - SDR10,14,28                                                                                          CONSTRUCTION HAZARDS. CONDITION REPORTS ON NEIGHBOURING PROPERTIES AND STRUCTURES                                                                                STRICTLY PROHIBITED. (FC) (W@H) (SA&SWP)
        RISK LEVEL = 7                                                                                                                            ARE RECOMMENDED PRIOR TO CONSTRUCTION. (EA) (SWD&E) (U/AGS) (P&IT) (GSW)
        (CS) CONFINED SPACES - SDR10,14,16,27,28                                                                                                                                                                                                                                                     SDR24         ALL SITE MACHINERY AND ELECTRICAL EQUIPMENT IS TO BE KEPT IN GOOD WORKING ORDER WITH
        RISK LEVEL = 7                                                                                                                 SDR10      THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR IS REQUIRED TO VERIFY AND IF                                                                                CURRENT SAFETY TAGGING AND SERVICING WHERE APPLICABLE. (CE) (SWD&E)
                                                                                                                                                  NECESSARY CONDUCT FURTHER SEARCHES TO ACCURATELY LOCATE EASEMENTS, UNDER GROUND
        (U/AGS) - WORK AROUND UNDERGROUND AND ABOVE GROUND SERVICES AND OBSTRUCTIONS - SDR9,10,28                                                 AND ABOVE GROUND SERVICES, PROPERTY BOUNDARIES, TREES, EXISTING STRUCTURES AND OTHER                                                               SDR25         THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR IS TO ADEQUATELY TREAT AND DISPOSE
        RISK LEVEL = 7                                                                                                                            OBSTRUCTIONS PRIOR TO DEMOLITION AND OR CONSTRUCTION. THE DESIGNER IS TO BE IMMEDIATELY                                                                          OF DANGEROUS SITE MATERIALS INCLUDING CONTAMINATED SOILS AND ASBESTOS IN ACCORDANCE
                                                                                                                                                  NOTIFIED OF ANY ELEMENTS NOT SHOWN ON THE APPROVED DRAWINGS AS THE DESIGN AND SAFETY                                                                             WITH AUTHORITY REGULATIONS, INDUSTRY STANDARDS AND PRACTICES. (HM) (GSW)
        (HM) EXPOSING AND HANDLING HAZARDOUS MATERIALS - SDR16,25,28
        RISK LEVEL = 4                                                                                                                            DESIGN REPORT MAY REQUIRE AMENDING. (DEM) (SP&IT) (U/AGS) (GSW) (SWD&E)
                                                                                                                                                                                                                                                                                                     SDR26         THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR IS TO ENSURE THAT THE SITE IS
        (FC) FORMWORK CONSTRUCTION - SDR21,22,23,28                                                                                    SDR11      THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR MUST OBTAIN DESIGN AND INSPECTION                                                                           MAINTAINED IN A SAFE WORKING MANNER AND THAT ALL SITE PRACTICES ARE IN ACCORDANCE WITH
                                                                                                                                                  CERTIFICATES ON ALL SUNDRY ELEMENTS OF THE STRUCTURE AND DEVELOPMENT INCLUDING BUT NOT                                                                           CURRENT WORK PLACE HEALTH AND SAFETY LAWS AND REGULATIONS. (CCD) (GSW)
        RISK LEVEL = 6
                                                                                                                                                  LIMITED TO COMPACTION TESTING, PIPELINE TESTING, CLADDING DESIGN AND FIXINGS, WINDOWS,                                                             SDR27         IDENTIFIED CONFINED SPACES COMPLY WITH RELEVANT STANDARDS FOR REASONABLY SAFE ACCESS
        (LSC) LIFTING AND POSITIONING OF STRUCTURAL COMPONENTS - SDR15,18,28
                                                                                                                                                  BALUSTRADES, STAIRS, SUSPENDED CEILINGS, INTERNAL FIT-OUT ITEMS AND ALL OTHER ELEMENTS NOT                                                                       AND MINIMIZED FOR ENTRY. THE BUILDER, PROJECT MANAGER AND/OR THE PRINCIPAL CONTRACTOR
        RISK LEVEL = 6
                                                                                                                                                  DETAILED IN THE DESIGN DOCUMENTS. (GSW) (CCD)                                                                                                                    HAS RESPONSIBILITY TO CONTROL ACCESS AND MANAGE ASSOCIATED HAZARDS AND RESIDUAL RISKS
        (SIC) STRUCTURE/MEMBER INSTABILITY DURING CONSTRUCTION - SDR7,8,12,14,20,28                                                                                                                                                                                                                                WHICH MAY INCLUDE INUNDATION, BIOLOGICAL, ENGULFMENT, ASPHYXIATION, ETC. THROUGH ACCESS
        RISK LEVEL = 6                                                                                                                 SDR12      THE CONSTRUCTION IS TO BE FULLY CARRIED OUT IN ACCORDANCE WITH ALL DESIGN DRAWINGS                                                                               CONTROL, PERMITS, AND MONITORING PROCESSES. (CS)
                                                                                                                                                  AND NOTES AS DOCUMENTED. IF CONSTRUCTION CEASES AT ANY STAGE, THE DESIGNER IS TO BE
        (OL) OVER LOADING DUE TO CONSTRUCTION & MAINTENANCE LOADS - SDR7,8,15,28                                                                  NOTIFIED TO PROVIDE ADVICE ON THE SAFETY OF COMPLETED CONSTRUCTION WORK AT THAT                                                                    SDR28         REFER DRAWING SHEETS FOR ANY SPECIFIC ADDITIONAL REQUIREMENTS.
        RISK LEVEL = 5                                                                                                                            TIME. (SIC) (GSW) (CCD)
        (AMH) ADDITIONAL MATERIAL HAZARDS EXIST. REFER TO PROJECT SID HAZARD CHECKLIST (FORM WHS 006 a & b)                            SDR13      IT IS THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR'S RESPONSIBILITY
                                                                                                                                                  TO INFORM THE DESIGNER OF ANY CHANGE TO CONTRACTUAL ARRANGEMENTS
 THE ABOVE LISTED TASKS AND HAZARDS HAVE BEEN ASSESSED AND ARE TO BE FURTHER MITIGATED BY
 1) FOLLOWING RISK REDUCTION MEASURES AS INDICATED ABOVE.
                                                                                                                                                  BETWEEN THE CLIENT AND THEMSELVES WHICH MAY IMPACT ON THE DESIGN AND                                                    RISK TABLE '2' MITIGATED HAZARD RISK ASSESSMENT TOOL WITH RECOMMENDED ACTIONS BY PCBU REPRESENTATIVE
 2) COMPLY WITH RISK TABLE '2' SUGGESTED ACTIONS.                                                                                                 SAFETY OF THE DESIGN. (CCD)                                                                                                 RISK LEVEL =
                                                                                                                                                                                                                                                                                                                                                                 CONSEQUENCE IF IT DID OCCUR
 3) IMPLEMENTING AND COMPLY WITH RISK REDUCTION MEASURES INDICATED IN THE PROJECT                                                      SDR14      THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR SHALL PROVIDE                                                          CONSEQUENCE x PROBABILITY
 SID-ARAM (FORM WHS-006b) IF ABOVE (AMH) - ADDITIONAL MATERIAL HAZARD BOX IS CHECKED.                                                             SUITABLE WARNING SIGNS, BARRIERS AND ACCESS CONTROLS TO CONFINED SPACES                                                                                                  1 - INSIGNIFICANT. 2 - MINOR.            3 - CONSIDERABLE.        4 - EXTREME.           5 - CATASTROPHIC.
                                                                                                                                                                                                                                                                              PROBABILITY OF EVENT                         (NO DAMAGE ).      (SOME DAMAGE AND/OR (REPAIRABLE DAMAGE         (SERIOUS DAMAGE        (MAJOR DAMAGE
 SDR1              IT IS THE CLIENT'S RESPONSIBILITY TO PROVIDE THIS 'SAFE DESIGN REPORT' TO THE BUILDER, PROJECT                                 AND FENCING AROUND ALL EXCAVATIONS. AT NO STAGE SHOULD AN EXCAVATION BE                                                     OCCURRING                                                       FIRST AID TREATMENT). AND/OR INJURIES          AND/OR FATALITY OR     AND/OR MULTIPLE
                   MANAGER AND/OR PRINCIPAL CONTRACTOR AND THEIR MUTUAL RESPONSIBILITY TO HAVE A SAFETY                                           APPROACHED OR ENTERED INTO UNLESS AN APPROVED AND CERTIFIED SHORING                                                                                                                                               CAUSING LOST TIME).      PERMANENT DISABILITY). FATALITIES).
                   MANAGEMENT PLAN ("SMP") FOR SITE ACCESS AND SAFE WORKING. (CCD) (SA&SWP)                                                       SYSTEM HAS BEEN INSTALLED OR THE BANKS HAVE BEEN BATTERED AND/OR BENCHED                                                  1 - WILL ONLY OCCUR IN
                                                                                                                                                                                                                                                                                                                                   1                       2                      3                    4                    5
                                                                                                                                                  IN ACCORDANCE WITH THE PROJECTS GEOTECHNICAL ENGINEERING SPECIFICATION                                                    EXCEPTIONAL CIRCUMSTANCES
 SDR2              IT IS THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR'S RESPONSIBILITY TO BUILD THE WORKS                                 AND/OR WRITTEN INSTRUCTIONS BY THE INSPECTING GEOTECHNICAL ENGINEER.                                                      2 - COULD OCCUR AT SOMETIME                            2                       4                      6                    8                    10
                   STRICTLY IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AND NOT TO MAKE ANY VARIATIONS TO THE                                       (SA&SWP) (EX) (GSW) (SIC) (SWD&E)
                   CONSTRUCTION WITHOUT THE SPECIFIC WRITTEN APPROVAL OF THE DESIGNER. (CCD) (GSW)                                                                                                                                                                          3 - LIKELY TO OCCUR SOMETIME                           3                       6                      9                    12                   15
                                                                                                                                       SDR15      AT NO STAGE SHALL SITE PERSONNEL PASS UNDER MATERIALS BEING LIFTED AND
                                                                                                                                                                                                                                                                            4 - WILL PROBABLY OCCUR                                4                       8                     12                    16                   20
 SDR3              IT IS THE CLIENT'S RESPONSIBILITY, THROUGH CONSULTATION AND ENGAGEMENT OF SUITABLY QUALIFIED                                   MOVED AROUND ON SITE. IT IS THE BUILDER, PROJECT MANAGER OR PRINCIPAL
                                                                                                                                                  CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT SITE MATERIALS ARE DELIVERED,                                                  5 - EXPECTED TO OCCUR                                  5                       10                    15                    20                   25
                   PROFESSIONALS, TO MAKE THE DESIGNER AWARE OF ANY INFORMATION RELATING TO HAZARDS AND RISKS
                   WHERE CONSTRUCTION WORK IS TO BE CARRIED OUT, INCLUDING BUT NOT LIMITED TO: THE LOCATION OF                                    TRANSPORTED, STORED AND POSITIONED IN A SAFE MANNER AND IN ACCORDANCE                                                    RISK LEVEL         1 TO 3 = MINOR        4 TO 6 = LOW       7 TO 8 = MODERATE        9 TO 10 = SIGNIFICANT        11 TO 18 = MAJOR      19 TO 25 = EXTREME
                   UNDER GROUND AND ABOVE GROUND SERVICES, IDENTIFICATION OF CONTAMINATED SOILS OR UNEXPECTED                                     WITH THE PRODUCT SPECIFICATION, THE SITE SPECIFIC SAFETY PLAN AND GENERAL                                                                                                                                     BEFORE CARRYING OUT          UNACCEPTABLE RISK     UNACCEPTABLE RISK.
                                                                                                                                                                                                                                                                           SUGGESTED           BE AWARE OF          ENSURE             PREPARE WORK
                   SOILS AND OTHER MATERIALS OR THE PRESENCE OF DANGEROUS MATERIALS INCLUDING ASBESTOS. (CCD)                                     SAFETY INDUCTION REGULATIONS. (LSC) (GSW) (OL) (DEM)                                                                     ACTIONS BY          THE RISK AND         ADEQUATE           METHOD STATEMENTS,       WORKS NECESSITATING THIS     FURTHER MITIGATIONS   THE HAZARD HAS NOT
                                                                                                                                                                                                                                                                           PRINCIPAL           CONSEQUENCES.        CONTROL            ENSURE ADEQUATE          RISK, MEET WITH THE          ARE REQUIRED.         BEEN MITIGATED TO
                                                                                                                  SDR16                           BUILDERS AND CONTRACTORS ARE REQUIRED TO OBTAIN AND COMPLY WITH MATERIAL                                                 BUILDER             TAKE ADEQUATE        MEASURES.          MONITORING OF THE        DESIGNER TO DISCUSS ALL      ALTERNATIVELY,        THE "REASONABLE
 SDR4              THIS DESIGN HAS BEEN DOCUMENTED IN ACCORDANCE WITH RELEVANT AUSTRALIAN STANDARDS, LOCAL                                                                                                                                                                                                                                                      MEASURES OUTLINED IN THE     CHANGED TO THE        PRACTICABLE "RISK
                                                                                                                                                  PRODUCT SPECIFICATIONS AND RECOMMENDATIONS WHEN USING MATERIALS AND                                                      AND/OR              PRECAUTIONS.         ENSURE ALL         WORKS. ADHERE
                   AUTHORITY REGULATIONS AND STANDARD BUILDING CODES OF PRACTICE UNLESS NOTED OTHERWISE.                                                                                                                                                                   PROJECT                                  CONTRACTORS        CLOSELY TO THE           DESIGN DOCUMENTS SO THAT     DESIGN CONCEPT MAY    REDUCTION
                                                                                                                                                  ELEMENTS SPECIFIED IN THE DESIGN DOCUMENTS. (HM) (CCD)
                   EACH LEVEL OF CONSTRUCTION IS TO BE STRUCTURALLY COMPLETED AND INSPECTED TO ENSURE DESIGN                                                                                                                                                               MANAGER                                  HAVE ADEQUATE      ASSOCIATED NOTES         NO MITIGATION MEASURES       BE REQUIRED TO        STANDARD. THE
                   COMPLIANCE BY THE CERTIFYING AUTHORITY PRIOR TO ADVANCING TO THE NEXT STAGE OF WORK. IT IS THE SDR17                                                                                                                                                                                             TRAINING.          ON THE DESIGN            ARE MISSED. PREPARE          MEET WESTERA'S        DESIGN AD HAZARD
                                                                                                                                                  THE BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR MUST ELIMINATE OR                                                                                                                                        DETAILED WORK PLANS, SAFE    SAFE DESIGN           REDUCTION
                                                                                                                                                                                                                                                                                                                                       DOCUMENTS.
                   BUILDER, PROJECT MANAGER OR PRINCIPAL CONTRACTOR'S RESPONSIBILITY TO PROGRAM THE WORKS IN A                                    LIMIT (SO FAR AS REASONABLE PRACTICABLE) SLIP HAZARDS AND PROTRUDING, SHARP                                                                                                                                   WORK METHOD STATEMENTS       REQUIREMENTS.         APPROACH IS
                   SAFE MANNER AND TO HIGHLIGHT TO THE DESIGNER ANY ASPECTS OF THE WORK THAT MAY REQUIRE                                          OR ABRASIVE ELEMENTS ON SITE. HAZARDOUS ELEMENTS MUST BE CAPPED,                                                                                                                                              (SWMS), PERMIT TO START,                           INADEQUATE.
                   FURTHER CLARIFICATION OR ADVICE WITH REGARD TO THE HEALTH AND SAFETY OF THE PROJECT. (CCD)                                     ADEQUATELY SCREENED OR CLEARLY MARKED TO ENSURE SITE SAFETY. (GSW)                                                                                                                                            MONITORING, TRAINING, ETC.



C1    ##.##.####     REVISION NAME                                                                                                                                                                       BRISBANE
                                                                                        DESIGNED:         APPROVED:
                                                                                                                                                                                                    T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                                                   PROJECT NUMBER
                                                                                                                                                                                                                       CONSULTANTS NAME                                                                                                                                                                                    S24-###
                                                                                                                                                           WE S TE R A
                                                                                                                                                                                                      GOLD COAST
                                                                                        DRAWN:
                                                                                                                                                                                                    T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                                  SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                                                       SHEET NUMBER
                                                                                        CHECKED:
                                                                                                                                                           PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                                   NORTHERN NSW
                                                                                                                                                                                                                      USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                                      PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                          TITLE:        CONSTRUCTION NOTES - SHEET 1
                                                                                                                                                                                                                                                                                                                                                                                                                             1.0
                                                                                                                                                                                                                                                                                                                                                                                                                              .
                                                                                        DATE:                                                 STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                                    T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                                 CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                                        CLIENT NAME                                                                                                     ##
                                                                                                                                                                                                                      STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                        PAGE SIZE:   A3   For and on behalf of                 www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                                      CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                                                     REVISION
No.     DATE          REVISIONS                                             DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                                T: 03 5441 0922

Section 3

                                                                                                                              L2     THE STRUCTURAL WORK SHOWN ON THESE DRAWINGS HAVE BEEN DESIGNED USING
               GENERAL NOTES                                                                                                         THE FOLLOWING BASE WIND PARAMETERS IN ACCORDANCE WITH AS1170.2.
                                                                                                                                                                                                                                                                                                    DRAINAGE/PLUMBING/TREES
      G1       THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL AND OTHER                                        IMPORTANCE LEVEL                -    2                 WIND SPEED (m/s)                              WIND PRESSURE (kPa)
               CONSULTANTS DRAWINGS, SPECIFICATIONS AND INSTRUCTIONS. ANY DISCREPANCIES OR OMISSIONS                               REGION                         -     B1                SERVICEABILITY - 42.64                        SERVICEABILITY - 1.09                               D1 THE EXTERNAL FINISHED SURFACE SURROUNDING THE FOOTINGS AND SLAB ON GROUND IS TO BE
               SHALL BE REFERRED TO THE ENGINEER FOR CLARIFICATION BEFORE PROCEEDING WITH THE WORK.                                TERRAIN CATEGORY                -    TC1                                                                                                                    WELL DRAINED AT ALL TIMES BY SLOPING THE SOIL AWAY FROM THE BUILDING AND GRADED TO GIVE A
                                                                                                                                                                                          ULTIMATE        - 62.32                       ULTIMATE       - 2.33
                                                                                                                                                                                                                                                                                               SLOPE OF NOT LESS THAN 50mm OVER THE FIRST 1 METER FROM THE BUILDING. PONDING OF WATER
                                                                                                                                                                                                                                                                                               AROUND THE BUILDING IS TO BE PREVENTED DURING AND AFTER CONSTRUCTION. ALL WATER IS TO
      G2       PRIOR TO THE COMMENCEMENT OF CONSTRUCTION THE CONTRACTOR SHALL CHECK AND CO-ORDINATE
                                                                                                                                                                                                                                                                                               BE DRAINED TO EITHER THE STREET FRONTAGE OR TO FIELD DRAIN PITS CONNECTED TO A
               WITH THE ARCHITECT AND OTHER CONSULTANTS ALL STEPS, FALLS, REBATES, SETDOWNS, CHASES AND
                                                                                                                                                                                                                                                                                               DISCHARGE LINE. SPOON DRAINS ARE TO BE LOCATED AT THE TOP AND BOTTOM OF ALL BATTERS.
               PENETRATIONS.
                                                                                                                                                                                                                                                                                               REFER TO THE BCA CLAUSE 3.1.2 FOR FURTHER DRAINAGE REQUIREMENTS.

      G3       ALL DIMENSIONS ARE IN MILLIMETRES UNLESS NOTED OTHERWISE. DIMENSIONS SHALL NOT BE
               OBTAINED BY SCALING OFF THE DRAWINGS.                                                                                                                                                                                                                                        D2 ENSURE PLUMBING INCLUDING STORMWATER DISCHARGE, SEWERAGE AND DRAINAGE ARE KEPT IN
                                                                                                                              L3     THE STRUCTURAL WORK SHOWN ON THESE DRAWINGS HAVE BEEN DESIGNED USING                                                                                      GOOD WORKING ORDER AND ARE NOT ALLOWED TO SATURATE THE GROUND AROUND THE BUILDING.
      G4                                                                                                                             THE FOLLOWING BASE EARTHQUAKE PARAMETERS IN ACCORDANCE WITH AS1170.4                                                                                      REPAIRS TO DAMAGE MUST BE ADDRESSED PROMPTLY
               ALL DIMENSIONS SHALL BE CHECKED BY THE CONTRACTOR PRIOR TO COMMENCEMENT OF THE WORKS.
                                                                                                                                     PROBABILITY FACTOR - 1.0
      G5       THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STRUCTURE AND ADJACENT                                        HAZARD FACTOR - 0.08                                                                                                                                   D3 TREES AND SHRUBS ARE TO BE KEPT A MINIMUM OF 2 TIMES THEIR MATURE HEIGHT AWAY FROM THE
               STRUCTURES IN A STABLE CONDITION AND ENSURING NO PART SHALL BE OVERSTRESSED DURING THE                                                                                                                                                                                          BUILDING. IN THE EVENT THIS CANNOT BE ACHIEVED A "ROOT BARRIER" SYSTEM SHALL BE INSTALLED
                                                                                                                                     DOMESTIC STRUCTURE - YES
               WORKS.                                                                                                                                                                                                                                                                          AND CERTIFIED BY A SPECIALIST CONTRACTOR TO PROTECT THE BUILDINGS FOUNDATION SYSTEM.
                                                                                                                                     SUBSOIL CLASS - Ce
      G6       ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE RELEVANT CURRENT CURRENT                                EARTHQUAKE DESIGN CATEGORY - EDC1                                                                                                                      D4 ALL PLUMBING INSTALLED ON REACTIVE CLAY SITES IS TO BE PLACED IN ACCORDANCE WITH THE BSA
               AUSTRALIAN STANDARDS, THE BCA, AND LOCAL COUNCIL REGULATIONS.                                                         WHERE THESE PARAMETERS ARE BEING CONSIDERED BY OTHERS FOR USE ON ANY                                                                                      RECOMMENDED GUIDELINES FOR SANITARY AND STORMWATER INSTALLATION ON REACTIVE CLAY
                                                                                                                                                                                                                                                                                               SITES AS A MINIMUM STANDARD.
                                                                                                                                     ELEMENTS ON THE BUILDING, THEY SHOULD BE DESIGN CHECKED BY ANOTHER
      G7       ALL NON-LOADBEARING WALLS SHALL BE KEPT 20mm CLEAR OF THE UNDERSIDE OF SLABS, BEAMS AND                               SUITABLY QUALIFIED ENGINEER WHO SHOULD ALSO PROVIDE CERTIFICATION FOR
               OTHER STRUCTURAL ELEMENTS, UNLESS NOTED OTHERWISE.                                                                    THAT ELEMENT. WESTERA PARTNERS ARE NOT RESPONSIBLE FOR EARTHQUAKE
                                                                                                                                     LOADING CALCULATIONS ON ELEMENTS PROVIDED BY OTHERS.
                                                                                                                                                                                                                                                                                                    FOUNDATIONS
      G8       THE CONTRACTOR IS TO CONFIRM THE LOCATIONS OF ALL EXISTING UNDERGROUND SERVICES AND
                                                                                                                                                                                                                                                                                             F1     REFER TO SOIL REPORT AND FOOTING PLAN FOR REFERENCE TO THE REQUIRED FOUNDING
               TAKE NECESSARY MEASURES TO AVOID CLASHES PRIOR TO COMMENCING EARTHWORKS AND/OR PILING.                                LOAD COMBINATIONS HAVE BEEN CALCULATED IN ACCORDANCE WITH AS/NZS 1170.0
                                                                                                                              L4                                                                                                                                                                    MATERIAL FOR THE FOOTINGS, THE SOIL PROFILE ACROSS THE SITE AND SPECIFIC SITE
                                                                                                                                                                                                                                                                                                    RECOMMENDATIONS.
      G9       THE STRUCTURAL ENGINEERING DESIGN DOCUMENTED FOR THIS PROJECT RELATES TO THE PROPOSED
               NEW CONSTRUCTION OF BUILDING ELEMENTS. THE CONDITION AND COMPLIANCE OF EXISTING                                       SITE PREPARATION                                                                                                                                        F2     THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY SHOULD THE FOUNDATION MATERIAL DIFFER
               STRUCTURAL COMPONENTS HAVE NOT BEEN ASSESSED NOR CERTIFIED AS PART OF WESTERA                                                                                                                                                                                                        FROM THAT STATED IN THE SOIL REPORT.
               PARTNERS COMMISSION ON THIS PROJECT UNLESS SPECIFICALLY STATED ON THE DESIGN DOCUMENTS.                        SP1 SITE EARTHWORKS SHALL BE CARRIED OUT IN ACCORDANCE WITH AS3798 - GUIDELINES ON
                                                                                                                                  EARTHWORKS FOR COMMERCIAL AND RESIDENTIAL DEVELOPMENTS.                                                                                                    F3     TOPSOIL CONTAINING PLANT ROOTS AND ANY ORGANIC MATERIAL SHALL BE REMOVED FROM
      G10 IT IS THE BUILDERS RESPONSIBILITY TO OBTAIN SUFFICIENT SURVEY & GEOTECHNICAL ADVICE AND TO                                                                                                                                                                                                THE BUILDING AREA PRIOR TO CONSTRUCTION.
          INSTALL RETENTION SYSTEMS AS NECESSARY TO FACILITATE EXCAVATIONS ADJACENT TO SITE                                   SP2 REFER TO THE GEOTECHNICAL REPORT FOR THE SOIL PROFILE ACROSS THE SITE AND SITE
          BOUNDARIES.                                                                                                             RECOMMENDATIONS.                                                                                                                                           F4     FOOTINGS SHALL BE LOCATED CENTRALLY UNDER COLUMNS AND WALLS UNLESS NOTED
                                                                                                                                                                                                                                                                                                    OTHERWISE.
      G11 WHERE PROPRIETARY ITEMS / ELEMENTS / ASPECTS FORM PART OF THE STRUCTURE, WESTERA                                    SP3 THE SITE SHALL BE STRIPPED OF ALL TOPSOIL & VEGETATION AND PROOF ROLLED TO IDENTIFY SOFT
          PARTNERS HAS RELIED UPON MANUFACTURERS SUPPLIED INFORMATION FOR THEIR SPECIFICATION AND                                 SPOTS, WHICH SHALL BE EXCAVATED AND REPLACED WITH SUITABLE FILL APPROVED BY THE                                                                            F5     ALL WATER AND LOOSE MATERIAL SHALL BE REMOVED FROM FOOTING EXCAVATIONS PRIOR TO
          DESIGN.                                                                                                                 GEOTECHNICAL ENGINEER.                                                                                                                                            CONCRETING.

      G12 UNLESS NOTED OTHERWISE WESTERA PARTNERS CERTIFICATION EXCLUDES NON-STRUCTURAL                                       SP4 IN ACCORDANCE WITH AS3798, THE COMPACTION REQUIREMENTS FOR SHALLOW FILL ARE AS                                                                             F6     UNLESS OTHERWISE NOTED ON DRAWINGS, ALL FOOTINGS SHALL BE FOUNDED INTO MATERIAL
          CLADDING ELEMENTS INCLUDING FIRE RATING AND / OR FIRE TOXICITY FOR SUCH CLADDING ELEMENTS.                              FOLLOWS:                                                                                                                                                          HAVING A SAFE BEARING CAPACITY OF NOT LESS THAN 100kPa. TO BE CONFIRMED IN WRITING
                                                                                                                                                                                                                                                                                                    BY A GEOTECHNICAL ENGINEER.
      G13 "AS CONSTRUCTED" DRAWINGS WHEN ISSUED BY WESTERA PARTNERS SHALL ONLY INCORPORATE                                                A) SAND UP TO 800mm DEEP IS TO BE COMPACTED IN 200mm LAYERS BY A VIBRATING PLATE
                                                                                                                                                                                                                                                                                             F7     IT IS THE BUILDING CONTRACTORS RESPONSIBILITY TO MAINTAIN FOOTING DIMENSIONS
          DESIGN CHANGES FORMALLY ADVISED BY CLIENT/BUILDER, AND APPROVED AND INSPECTED BY                                                OR VIBRATION ROLLER. THE FILL IS TO HAVE AN N VALUE OF 7 USING A STANDARD
                                                                                                                                                                                                                                                                                                    INDICATED ON THE DRAWINGS. THE BUILDER IS TO SEEK GEOTECHNICAL ADVICE ON THE
          WESTERA PARTNERS.                                                                                                               PENETROMETER TEST. DENSITY INDEX IS TO BE NOT LESS THAN 75% IN ACCORDANCE
                                                                                                                                                                                                                                                                                                    ABILITY TO EXCAVATE THE EXISTING GROUND IN ITS PRESENT CONDITION AND ALLOW FOR
                                                                                                                                          WITH AS1289. TESTING OF DENSITY INDEX SHALL BE DONE IN ACCORDANCE WITH AS1289.
                                                                                                                                                                                                                                                                                                    FORMWORK OR MASS CONCRETE OVER POUR.
      G14 WESTERA PARTNERS HAS LIMITED CONTROL OR INPUT TO LOCAL GOVERNMENT OR OTHER
          LEGISLATED APPROVALS UNLESS SPECIFICALLY ENGAGED BY ITS CLIENT. ANY CHANGES TO                                                  B) NON-SAND FILL UP TO 400mm DEEP SHALL BE COMPACTED IN NOT MORE THAN 150mm
          APPROVAL REQUIREMENTS (INCLUDING ORDERS FOR SUSPENSION OF WORKS ETC) SHOULD BE
          COMMUNICATED TO WESTERA PARTNERS AND ALL OTHER RELEVANT DESIGNERS TO ALLOW
                                                                                                                                          LAYERS BY A MECHANICAL ROLLER, CLAY FILL SHALL BE MOIST DURING COMPACTION.
                                                                                                                                          STANDARD COMPACTION INDEX IS NOT TO BE LESS THAN 95% FOR A RESIDENTIAL
                                                                                                                                                                                                                                                                                                    CONCRETE
          ASSESSMENT OF POTENTIAL RISKS AND ENSURE DESIGN AND SAFETY COMPLIANCE.                                                          PROJECT AND 98% FOR A COMMERCIAL DEVELOPMENT OR PAVEMENT IN ACCORDANCE                                                                            C1 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS3600 CONCRETE
                                                                                                                                          WITH AS1289. REACTIVE CLAY SHOULD BE AVOIDED AS FILL BUT IF USED SHOULD BE                                                                           STRUCTURES CODE AND THE REFERENCED STANDARDS THEREIN.
      G15 THE CONTRACTOR SHALL CONTACT THE ENGINEER AT LEAST 24 HOURS PRIOR TO                                                            PLACED AT A MOISTURE CONTENT WHICH APPROXIMATES THE FIXED EQUILIBRIUM
          ARRANGE AN INSPECTION WHEN REQUIRED.                                                                                            MOISTURE CONTENT.                                                                                                                                 C2 THE CONCRETE STRENGTH GRADE AND THE COVER TO REINFORCEMENT FOR THE VARIOUS
                                                                                                                                                                                                                                                                                               CONCRETE ELEMENTS SHALL BE AS LISTED BELOW:
               LOADINGS                                                                                                       SP5 ANY FILLED BUILDING PLATFORMS IN EXCESS OF THE FILL LEVELS DESCRIBED ABOVE SHALL BE
                                                                                                                                  CONTROLLED FILL IN ACCORDANCE WITH AS3798 - GUIDELINES ON EARTHWORKS FOR COMMERCIAL
      L1                                                                                                                                                                                                                                                                                                                SURFACES IN CONTACT      INTERIOR                 EXTERIOR
               THE STRUCTURAL WORK SHOWN ON THESE DRAWINGS HAS BEEN DESIGNED FOR THE                                              AND RESIDENTIAL DEVELOPMENTS OR THE GEOTECHNICAL REPORT. THE TESTING AND CERTIFICATION
               FOLLOWING LIVE LOADS:                                                                                              OF THE FILL PLATFORM SHALL BE CARRIED OUT BY A SUITABLY QUALIFIED TESTING BODY.                                                                                                           WITH GROUND          SURFACES                 SURFACES
                                                                                                                                                                                                                                                                                                       ELEMENT          STRENGTH    COVER   STRENGTH    COVER       STRENGTH    COVER
                          LOCATION          UNIFORM LOAD (kPa)               POINT LOAD (kN)                                  SP6 FOR SITES WHERE CUT AND FILL IS REQUIRED, THE FILL SHALL CONTINUE PAST THE EDGE OF THE
                                                                                                                                                                                                                                                                                                                          GRADE               GRADE                   GRADE
                                                                                                                                  BUILDING AT LEAST 1m AND SHALL BE RETAINED OR BATTERED BEYOND THIS POINT. REFER TO THE                                                                     FOOTINGS U.N.O                N25         50          -          -         -         -
                      GARAGE SLAB                    2.5                                  13                                      GEOTECHNICAL REPORT FOR BATTER SLOPE DETAILS. UNLESS NOTED OTHERWISE THE INTERIOR OF
                                                                                                                                                                                                                                                                                             FOOTINGS BEAMS                N32         50          -          -          -            -
                                                                                          1.8                                     THE SLAB SHALL BE FOUNDED ON COMPACTED MATERIAL AND THE EDGE BEAMS & INTERNAL LOAD-
                    GENERAL AREAS                    1.5                                                                          BEARING ELEMENTS SHALL BE FOUNDED ON NATURAL SOIL (REFER GEOTECHNICAL REPORT)                                                                              GROUND SLAB & STAIRS           N32        50         N32        30        SB40          45
                         BALCONIES                   2.0                                  1.8                                                                                                                                                                                                SUSPENDED SLABS                 -          -         N40        30        SB40          45
                               ROOF                  0.25                                 1.1                                                                                                                                                                                                CONC COLUMNS/WALLS              -          -         N40        30        SB40          45

C1     ##.##.####   REVISION NAME                                                                                                                                                         BRISBANE
                                                                             DESIGNED:           APPROVED:
                                                                                                                                                                                     T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                          PROJECT NUMBER
                                                                                                                                                                                                        CONSULTANTS NAME                                                                                                                                                         S24-###
                                                                                                                                            WE S TE R A
                                                                                                                                                                                       GOLD COAST
                                                                             DRAWN:
                                                                                                                                                                                     T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                   SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                              SHEET NUMBER
                                                                             CHECKED:
                                                                                                                                            PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                    NORTHERN NSW
                                                                                                                                                                                                       USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                       PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                           TITLE:       CONSTRUCTION NOTES - SHEET 2
                                                                                                                                                                                                                                                                                                                                                                                     1.1
                                                                                                                                                                                                                                                                                                                                                                                      .
                                                                             DATE:                                             STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                     T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                  CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                        CLIENT NAME                                                                        ##
                                                                                                                                                                                                       STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                             PAGE SIZE:     A3   For and on behalf of           www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                       CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                            REVISION
No.     DATE        REVISIONS                                    DRN   ENG                       WESTERA PARTNERS PTY. LTD.                                                          T: 03 5441 0922

Section 4

                                                                                                                                       FOR CONCRETE USING NORMAL PORTLAND CEMENT AS3972 - TYPES A OR D WITHOUT
                CONCRETE CONTINUED                                                                                            C20
                                                                                                                                       ADMIXTURES, STRIPPING STAGES SHALL CONFORM TO THE MINIMUM STRIPPING TIMES FOR THE
                                                                                                                                                                                                                                                                                                 C30     A VAPOUR BARRIER OF 0.2mm (200um) MINIMUM THICK POLYTHENE SHEETING SHALL BE
                                                                                                                                       APPROPRIATE EFFECTIVE SPANS AND TEMPERATURES GIVEN IN THE FOLLOWING TABLE:
                                                                                                                                                                                                                                                                                                         PLACED BENEATH SLABS ON GROUND UNLESS NOTED OTHERWISE.
      C3        CONCRETE TO HAVE A MAXIMUM AGGREGATE SIZE OF 20mm WITH 80mm MAXIMUM SLUMP, A
                WATER/CEMENT RATIO OF NOT GREATER THAN 0.65 AND A MAXIMUM FINAL BASIC DRYING                                                                       MEMBER
                SHRINKAGE STRAIN OF 800 x 10 , UNLESS APPROVED OTHERWISE.                                                                MEMBER                                              MEMBER                MINIMUM STRIPPING TIME (DAYS) FOR

      C4        NO ADDITIVES SHALL BE ADDED OF APPLIED TO THE CONCRETE MIX WITHOUT THE APPROVAL OF
                                                                                                                                         TYPE                                                SPAN (m)              AVERAGE AIR
                                                                                                                                                                                                                        TEMP. DURING PERIOD PRIOR
                                                                                                                                                                                                                                                                                                         CONCRETE SHRINKAGE CRACKING
                THE ENGINEER.                                                                                                                                                                                           TO STRIPPING                                                                     TO REDUCE THE OCCURRENCE OF SHRINKAGE CRACKING IN CONCRETE SLABS, THE FOLLOWING
                                                                                                                                                                                                                        21°C+                10-21°C                 5-10°C                              GUIDELINES SHOULD BE FOLLOWED:
      C5        THE MAXIMUM PERMISSIBLE TRANSPORT TIME FOR CONCRETE BETWEEN BATCHING AND
                                        BE IN
                PLACEMENT ON SITE SHALL BE  IN ACCORDANCE
                                               ACCORDANCE WITH THE FOLLOWING TABLE.                                                                                                                                         2                     2                      5
                                                                                                                                                                   WALL                                                                                                                          CS1     SLABS ON GROUND SHOULD BE POURED ON POLYTHENE SHEETING OVER A SMOOTH SUB-BASE.
                       AMBIENT AIR                 MAX. BATCHING TO PLACEMENT TIME                                                       VERTICAL AND              COLUMN
                      TEMPERATURE                                                                                                        UNLOADED                  BEAM SIDE                                                                                                                     CS2     WATER MUST NOT BE ADDED TO THE CONCRETE MIX AFTER IT LEAVES THE BATCHING PLANT
                                                                                                                                                                                                                                                                                                         UNLESS ORDERED BY THE SUPPLIER.
                    10° - 24°C                                120 MINUTES                                                                                                                                                   5                     6                      7
                                                                                                                                                                   WALL, COLUMN OR
                    25° - 27°C                                 90 MINUTES                                                                VERTICAL                  LOAD-BEARING                                                                                                                  CS3     PLACE CONCRETE AS SOON AS POSSIBLE.
                    28° - 30°C                                 60 MINUTES                                                                AND LOADED                STRUCTURE
                                                                                                                                                                                                                                                                                                 CS4     ADEQUATELY COMPACT THE CONCRETE, PARTICULARLY AROUND CORNERS, PENETRATIONS AND
                    31° - 33°C                                 45 MINUTES                                                                                                                                                                                                                                INSERTS.
                                                                                                                                         HORIZONTAL                SLAB                      UNDER 3                       7                     10                     14
                    34° - 36°C                                 30 MINUTES
                                                                                                                                                                                             3-6                           10                    14                     21
                    37°C+                          NO PLACEMENT OF CONCRETE UNLESS                                                                                                                                                                                                               CS5     CLOSE ANY EARLY CRACKING BY RE-COMPACTING THE CONCRETE OR RE-TROWELLING THE
                                                                                                                                                                                             OVER 6                        14                    21                     28                               SURFACE.
                                                       CHILLED WATER OR ICE IN MIX
                                                                                                                                         HORIZONTAL                BEAM                      UNDER 3                       10                    14                     21
                ALL CONCRETE
                    CONCRETE SHALL
                             SHALL BE
                                   BE MECHANICALLY
                                      MECHANICALLY VIBRATED.
                                                   VIBRATED. VIBRATORS
                                                             VIBRATORS SHALL
                                                                       SHALL NOT
                                                                             NOT BE
                                                                                 BE USED
                                                                                    USED TO
                                                                                         TO SPREAD
                                                                                            SPREAD                                                                                                                                                                                               CS6     IN WINDY CONDITIONS ERECT WIND BREAKS OR WALLS.
      C6        ALL                                                                                                                                                                          3-6                           14                    21                     28
                CONCRETE.
                                                                                                                                                                                             OVER 6                        21                    28                     28                       CS7     APPLY ALIPHATIC ALCOHOL IMMEDIATELY AFTER SCREEDING AND BULL FLOATING.
      C7        ALL CONCRETE SHALL BE SAMPLED AND TESTED IN ACCORDANCE WITH AS1379 ADOPTING THE                                        NOTE: THIS
                                                                                                                                       NOTE: THIS TABLE
                                                                                                                                                  TABLE IS BASED ON
                                                                                                                                                        IS BASED
                                                                                                                                                           BASED ON SUPERIMPOSED
                                                                                                                                                                 ON SUPERIMPOSED CONSTRUCTION
                                                                                                                                                                    SUPERIMPOSED CONSTRUCTION LOADS
                                                                                                                                                                                 CONSTRUCTION LOADS NOT
                                                                                                                                                                                                    NOT EXCEEDING
                                                                                                                                                                                                        EXCEEDING 1.0kPa.
                                                                                                                                                                                                                  1.0kPa.
                                                                                                                                                                                                                                                                                                 CS8     RE-APPLY ALIPHATIC ALCOHOL TO SURFACES AFTER EACH FINISHING OPERATION.
                PROJECT ASSESSMENT METHOD FOR COMPRESSIVE STRENGTH AND SLUMP COMPLIANCE. THE
                RESULTS OF ALL TESTS SHALL BE PROMPTLY SUBMITTED TO THE ENGINEER FOR REVIEW.                                  C21      REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT NECESSARILY SHOWN IN TRUE                                                                           CS9     ONCE THE SLAB IS FINISHED, CONTINUOUSLY CURE FOR 7 DAYS VIA WATER PONDING,
                                                                                                                                       PROJECTION OR SCALE.                                                                                                                                              IMPERVIOUS SHEETS OVER THE SLAB OR MEMBRANE FORMING CURING COMPOUNDS APPLIED IN
      C8        WHEN THE AIR TEMPERATURE EXCEEDS 30°C, ALIPHATIC ALCOHOL SHALL BE APPLIED TO THE
                                                                                                                                                                                                                                                                                                         ACCORDANCE WITH THE MANUFACTURERS SPECIFICATION.
                CONCRETE SURFACE OF SLABS IMMEDIATELY AFTER THE INITIAL SCREED AND AGAIN AFTER BULL                           C22      ALL REINFORCEMENT SHALL BE SECURELY SUPPORTED IN ITS CORRECT POSITION ON PLASTIC BAR
                FLOATING.                                                                                                              CHAIRS, GENERALLY AT NOT GREATER THAN 800mm CENTRES IN BOTH DIRECTIONS.                                                                                  CS10 STRUCTURAL ENGINEER IS TO BE NOTIFIED BY THE CLIENT, ARCHITECT OR BUILDER, OF ANY
                                                                                                                                                                                                                                                                                                     SPECIAL SHRINKAGE REQUIREMENTS FOR EXPOSED CONCRETE ELEMENTS PRIOR TO
      C9        CURING OF ALL CONCRETE SURFACES SHALL COMMENCE IMMEDIATELY AFTER COMPLETING                                   C23      WELDING AND HEATING OF REINFORCEMENT SHALL NOT BE PERMITTED WITHOUT APPROVAL OF THE                                                                           CONSTRUCTION.
                CONCRETE FINISHING AND SHALL CONTINUE FOR 7 DAYS. CONTRACTOR TO CONFIRM METHOD OF                                      ENGINEER.
                CURING WITH ENGINEER PRIOR TO USE.
                                                                                                                                                                                                                                                                                                CS11 WHERE BRITTLE FLOOR COVERINGS SUCH AS CERAMIC TILES ARE BEING USED, ADDITIONAL SLAB
                                                                                                                              C24      ALL STEEL REINFORCEMENT IN CONCRETE ELEMENTS SHALL BE INSPECTED BY THE ENGINEER AND                                                                           REINFORCEMENT SHOULD BE ADDED TO THE SPECIFIED MINIMUM REINFORCEMENT. IF NO EXTRA
      C10       SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE THICKNESS OF APPLIED FINISHES.                                               PASSED PRIOR TO POURING OF ANY CONCRETE.                                                                                                                      REINFORCEMENT IS ADDED, COVERING SHOULD BE DELAYED UNTIL 90 DAYS AFTER THE SLAB HAS
                                                                                                                                                                                                                                                                                                     BEEN PLACED.
      C11       BEAM DEPTHS ARE WRITTEN FIRST AND INCLUDE SLAB THICKNESS, IF ANY.                                             C25      LAP REINFORCEMENT ONLY AT LOCATIONS SHOWN ON THE DRAWINGS OR AS APPROVED BY THE
                                                                                                                                       ENGINEER.                                                                                                                                                CS12 ALL SHRINKAGE CRACKS ARE TO BE TREATED WITH A LOW VISCOSITY ACRYLIC POLYMER
      C12       CONSTRUCTION JOINTS SHALL BE PROPERLY FORMED AND USED ONLY WHERE SHOWN OR
                                                                                                                                                                                                                                                                                                     SPECIFICALLY DESIGNED TO PENETRATE, REPAIR AND SEAL MOVING CRACKS SUCH AS 3M
                APPROVED BY THE ENGINEER.                                                                                     C26      SLAB FABRIC SHALL BE LAPPED ONE FULL PANEL OF FABRIC PLUS 50mm SO THAT THE TWO                                                                                CP&R 5742 OR APPROVED EQUIVALENT.
                                                                                                                                       OUTERMOST TRANSVERSE WIRES OF ONE SHEET OVERLAP THE TWO OUTERMOST TRANSVERSE
      C13       NO HOLES, CHASES OR EMBEDDED ITEMS OTHER THAN THOSE SHOWN ON THE STRUCTURAL                                            WIRES OF THE SHEET BEING LAPPED BY 50mm.
                DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT PRIOR APPROVAL OF THE
                ENGINEER. CONDUITS, PIPES ETC. SHALL NOT BE PLACED IN THE COVER THICKNESS OF THE
                CONCRETE.                                                                                                              BAR REINFORCEMENT SHALL BE LAPPED IN ACCORDANCE WITH THE FOLLOWING TABLE.
                                                                                                                                                                                                                                                                                                 PC1     POLISHED/HONED CONCRETE SLABS
                                                                                                                              C27
                                                                                                                                                                                                                                                                                                         WHERE POLISHED/HONED CONCRETE SLABS ARE REQUIRED, THE SLAB SHALL COMPLY WITH THE
      C14       WHERE SERVICE PIPES PENETRATE CONCRETE ELEMENTS, PROVISION SHOULD BE MADE TO                                                                                      TYPICAL BAR REINFORCEMENT LAP LENGTHS
                                                                                                                                                                                                                                                                                                 PC2     FOLLOWING:
                ALLOW FOR MOVEMENT OF THE ELEMENT.
                                                                                                                                                  BAR                      LAP LENGTH UNO                      HORIZONTAL BARS WITH GREATER
                                                                                                                                                                                                           THAN 300mm OF CONCRETE CAST BELOW THEM                                                        CONCRETE TO HAVE A MINIMUM STRENGTH GRADE OF S32 WITH A MAX SHRINKAGE STRAIN OF
      C15       FORMWORK SHALL BE DESIGNED, CONSTRUCTED AND STRIPPED IN ACCORDANCE WITH AS3610
                                                                                                                                                                                                                                                                                                 PC3     650 x10 AND A MAX WATER/CEMENT RATIO OF 0.45, UNO
                FORMWORK CODE, UNLESS NOTED OTHERWISE ON THE DRAWINGS.                                                                       N12                   550                              750
                                                                                                                                             N16                   800                             1100                                                                                                  SLABS ON GROUND TO BE A MINIMUM OF 130mm THICK, REINFORCED WITH SL81 FABRIC WITH 30mm
      C16       STRIPPING OF FORMWORK AND REPROPPING OF SUSPENDED SLABS AND BEAMS SHALL BE
                                                                                                                                             N20                  1100                             1400                                                                                                  TOP COVER, UNO.
                CARRIED OUT PROGRESSIVELY SO THAT AT NO STAGE IS THE SLAB OR BEAM UNSUPPORTED
                UNTIL IT IS PERMITTED TO FULLY REMOVE ALL PROPPING.                                                                          N24                  1250                             1600                                                                                                  FOLLOW CCAA GUIDELINES FOR CONCRETE SHRINKAGE CRACKING AND POLISHED CONCRETE
                                                                                                                                             N28                  1400                             1800                                                                                                  FLOORS
      C17       IN MULTISTORY CONSTRUCTION, PROPS SHALL BE LOCATED IN THE SAME POSITION ON EACH
                                                                                                                                             N32                  1600                             2100
                FLOOR SO THAT THEY WILL BE CONTINUOUS IN THEIR SUPPORT FROM FLOOR TO FLOOR. WHERE
                THE NUMBER OF PROPS ON A FLOOR IS REDUCED, THE REMAINING PROPS SHALL BE LOCATED                                              N36                  2000                             2500
                DIRECTLY UNDER PROPS ON THE FLOOR ABOVE.                                                                               WHERE LAPS ARE SHOWN ON THE DRAWINGS THE ABOVE LAP LENGTHS SHALL BE ADOPTED
                                                                                                                                       WHERE LAPS ARE SHOWN ON THE DRAWINGS THE ABOVE LAP LENGTHS SHALL BE ADOPTED UNLESS
                                                                                                                                                                                                                   UNLESS
                                                                                                                                       NOTED OTHERWISE. WHERE BARS OF DIFFERENT DIAMETER ARE SHOWN LAPPED, ADOPT THE LAP
      C18       PROPPING TO SUSPENDED SLABS AND BEAMS SHALL NOT BE REMOVED UNTIL THE CONCRETE                                          LENGTH APPROPRIATE TO THE SMALLER DIAMETER BAR.
                HAS ACQUIRED SUFFICIENT STRENGTH TO SUPPORT SAFELY ITS OWN WEIGHT AND ANY
                SUPERIMPOSED LOAD WITHOUT DAMAGE OR UNACCEPTABLE DEFLECTION.                                                  C28      A LEVELING SAND LAYER (50mm MINIMUM IN THICKNESS) SHALL BE PLACED UNDER SLABS ON
                                                                                                                                       GROUND UNO. THE SAND SHALL BE SALT FREE AND COMPACTED TO 65% DENSITY INDEX.
      C19       NO MASONRY WALLS OR SIMILAR PERMANENT LOADINGS SHALL BE ERECTED ON ANY PART OF
                THE STRUCTURE WHILE THE PART IS STILL SUPPORTED BY PROPS.                                                     C29      A VAPOUR BARRIER OF 0.2mm (200um) MINIMUM THICK POLYTHENE SHEETING SHALL BE PLACED
                                                                                                                                       BENEATH SLABS ON GROUND UNLESS NOTED OTHERWISE.
C1     ##.##.####   REVISION NAME                                                                                                                                                             BRISBANE
                                                                               DESIGNED:         APPROVED:
                                                                                                                                                                                         T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                          PROJECT NUMBER
                                                                                                                                                                                                            CONSULTANTS NAME                                                                                                                                                         S24-###
                                                                                                                                                WE S TE R A
                                                                                                                                                                                           GOLD COAST
                                                                               DRAWN:
                                                                                                                                                                                         T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                       SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                  SHEET NUMBER
                                                                               CHECKED:
                                                                                                                                                PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                        NORTHERN NSW
                                                                                                                                                                                                           USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                           PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                               TITLE:      CONSTRUCTION NOTES - SHEET 3
                                                                                                                                                                                                                                                                                                                                                                                       1.2
                                                                                                                                                                                                                                                                                                                                                                                        .
                                                                               DATE:                                            STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                   DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                         T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                      CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                           CLIENT NAME                                                                       ##
                                                                                                                                                                                                           STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                               PAGE SIZE:   A3   For and on behalf of               www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                           CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                            REVISION
No.        DATE     REVISIONS                                      DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                              T: 03 5441 0922

Section 5

                STRUCTURAL STEEL
                                                                                                                                S12       CONCRETE ENCASED STEELWORK SHALL HAVE A MINIMUM OF 50mm OF COVER CONCRETE                                                                               M7       GROUT FOR CORE FILLING SHALL BE STRENGTH GRADE S20. THE GROUT SHALL HAVE A MAXIMUM
                THE CONSTRUCTION CATEGORY HAS BEEN DETERMINED IN ACCORDANCE WITH AS 5131 AND THE
                                                                                                                                          REINFORCED WITH W5 WIRE AT 150 CRS. OR FGW41 FABRIC UNLESS NOTED OTHERWISE.                                                                                      AGGREGATE SIZE OF 10mm, A MAXIMUM SLUMP OF 230mm +/-25mm AND A MINIMUM CEMENT
                FOLLOWING PARAMETERS:
                                                                                                                                                                                                                                                                                                           CONTENT OF 300kg/m³.
                    IMPORTANCE LEVEL          - 2
                    SERVICE CATEGORY          - SC1                                                                             S14       THE POSITION AND DETAIL OF ANY SPLICES REQUIRED OTHER THAN THOSE SHOWN ON THE
                                                                                                                                          DRAWINGS SHALL BE APPROVED BY THE ENGINEER.                                                                                                             M8       ADDITIVES SHALL NOT BE ADDED TO THE GROUT OR MORTAR WITHOUT THE SPECIFIC PERMISSION
                    FABRICATION CATEGORY      - FC1
                                                                                                                                                                                                                                                                                                           OF THE ENGINEER.
                    CONSTRUCTION CATEGORY     - CC2
                                                                                                                                S15       FULL CONTACT BEARING SURFACES, WHERE SPECIFIED, SHALL COMPLY WITH CLAUSE 14.4.4.2 OF
                                                                                                                                          AS4100.                                                                                                                                                 M9       PROVIDE CLEANOUT BLOCKS AT THE BASE OF ALL REINFORCED CORES.
     S1         ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS4100 STEEL STRUCTURES
                CODE AND THE REFERENCED STANDARDS THEREIN.
                                                                                                                                S16       THE ENDS OF ALL TUBULAR MEMBERS SHALL BE SEALED WITH 5mm MINIMUM PLATES AND                                                                             M10      ALL MORTAR DAGS AND PROTRUSIONS INTO THE BLOCK OR BRICK CORES SHALL BE REMOVED
                                                                                                                                          CONTINUOUS FILLET WELDS UNLESS NOTED OTHERWISE.                                                                                                                  PRIOR TO THE PLACEMENT OF ANY CONCRETE. LOOSE MATERIAL AND DEBRIS SHALL ALSO BE
     S2         THE CONTRACTOR SHALL SUBMIT STRUCTURAL STEEL SHOP DRAWINGS FOR REVIEW BY THE
                                                                                                                                                                                                                                                                                                           REMOVED FROM THE MASONRY CORES.
                ENGINEER AND ARCHITECT, BEFORE FABRICATION COMMENCES.
                                                                                                                                S17       CLADDING TRIMMING MEMBERS FOR VALLEYS, EDGES, MECHANICAL AND HYDRAULIC
                                                                                                                                          PENETRATIONS ARE NOT NECESSARILY SHOWN. REFER PURLIN MANUFACTURER FOR DETAILS.                                                                          M11      FULLY BED SOLID UNITS, FACE BED HOLLOW UNITS AND FULLY FILL VERTICAL JOINTS. NO RAKING
     S3         THE STEEL MEMBERS SHOWN ON THE STRUCTURAL DRAWINGS ARE THOSE REQUIRED FOR THE
                                                                                                                                                                                                                                                                                                           OF MORTAR JOINTS IS PERMITTED.
                COMPLETED STRUCTURE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY
                NECESSARY TEMPORARY CONNECTIONS, SUPPORTS AND BRACING TO MAINTAIN THE STABILITY AND                             S18       SUPPORT RODS FOR CEILINGS, SERVICES, ETC, WHICH ARE SUSPENDED FROM PURLINS SHALL BE
                                                                                                                                          CONNECTED TO PURLIN WEBS ONLY. NO HOLES SHALL BE DRILLED THROUGH PURLIN FLANGES.                                                                        M12      GROUTING SHALL NOT COMMENCE UNTIL THE MORTAR JOINTS HAVE GAINED SUFFICIENT STRENGTH
                SAFETY OF THE STEELWORK THROUGHOUT THE CONSTRUCTION PERIOD.
                                                                                                                                                                                                                                                                                                           TO RESIST BLOWOUT AND CORES HAVE BEEN CLEANED OUT.
     S4         THE CONTRACTOR SHALL REFER TO THE ARCHITECTURAL DRAWINGS AND SPECIFICATION FOR                                  S19       UNLESS NOTED OTHERWISE ALL STEELWORK (INCLUDING FIXINGS) SHALL BE HOT DIP
                                                                                                                                          GALVANISED OR PAINTED (INCLUDING CLEANING & PREPARATION) BASED ON THEIR LEVEL OF                                                                        M13      GROUT SHALL BE COMPACTED BY VIBRATOR OR BY RODDING WITH A ROD NOT LESS THAN 24mm
                ADDITIONAL STEELWORK, CLEATS AND BOLTS NOT SHOWN ON THE STRUCTURAL DRAWINGS.
                                                                                                                                          EXPOSURE (ATMOSPHERIC CORROSIVITY CATERGORY) IN ACCORDANCE WITH AS/NZS 2312 AND                                                                                  DIAMETER.
     S5         UNLESS NOTED OTHERWISE, ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING:                                              THE REFERENCED STANDARDS THERE IN.
                                                                                                                                                                                                                                                                                                  M14      ALL CORES SHALL BE FILLED WITH GROUT, UNLESS NOTED OTHERWISE.
                                          ELEMENT                               STEEL GRADE                                     S20       REGARDLESS OF THE PROTECTIVE COATING SYSTEM ADOPTED, SOME ONGOING MAINTENANCE IS
                                                                                                                                          TO BE EXPECTED THROUGHOUT THE DESIGN LIFE OF EXPOSED STEELWORK, PARTICULARLY IN                                                                         M15      REINFORCEMENT SHALL BE PLACED ACCURATELY AND TIED SECURELY BEFORE PLACEMENT OF
                       HOT ROLLED SECTIONS                                       300 PLUS                                                 COASTAL ENVIRONMENTS.                                                                                                                                            GROUT.
                       WELDED SECTIONS (WB, WC)                                  300 PLUS                                       S21                                                                                                                                                               M16      UNLESS NOTED OTHERWISE VERTICAL CONTROL JOINTS SHALL BE PROVIDED IN BLOCKWORK AT
                                                                                                                                          NON-DESTRUCTIVE WELD TESTING, WHERE SPECIFIED, SHALL BE CARRIED OUT BY SUITABLY
                       CHS UP TO AND INCLUDING 168 DIA.                             C250                                                  QUALIFIED PERSONNEL IN ACCORDANCE WITH CLAUSE 7.4 OF AS1554.1 USING APPROPRIATE                                                                                  8.0m CRS. AND AT 4.0m FROM CORNERS, AND IN BRICKWORK AT 5.0m CRS. AND AT 2m TO 4.5m FROM
                                                                                                                                          RADIOGRAPHIC, ULTRASONIC, MAGNETIC PARTICLE OR DYE PENETRATION TECHNIQUES. THE                                                                                   CORNERS. CONTRACTOR TO CO-ORDINATE LOCATIONS WITH ARCHITECT. JOINTS TO BE 10mm WIDE.
                       CHS GREATER THAN 168 DIA, SHS AND RHS                        C350                                                  RESULTS SHALL BE PROMPTLY FORWARDED TO THE ENGINEER FOR REVIEW PRIOR TO ERECTION                                                                                 JOINTS TO BE CONSTRUCTED IN ACCORDANCE WITH CEMENT CONCRETE & AGGREGATES AUSTRALIA
                                                                                                                                          OF THE STEELWORK.                                                                                                                                                TECHNICAL NOTE TN61.
                       FLOOR PLATES                                                   250
                       MERCHANT BAR - ROUNDS, SQUARES                            300 PLUS                                       S22       ALL COATED SURFACES DAMAGED BY SITE WELDS OR CUTTING SHALL BE THOROUGHLY CLEANED,                                                                       M17      NO HOLES OR CHASES SHALL BE CUT INTO BLOCKWORK/BRICKWORK WITHOUT PRIOR APPROVAL OF
                       AND FLATS                                                                                                          PREPARED AND PAINTED IN ACCORDANCE WITH AS2312.                                                                                                                  THE ENGINEER.

                                                                                                                                                                                                                                                                                                  M18      ALL WALL INTERSECTIONS SHALL BE OF BONDED CONSTRUCTION OR TIED WITH MEDIUM DUTY TIES
                                                                                                                                                                                                                                                                                                           AT 400mm MAXIMUM CRS.
     S6         UNLESS NOTED OTHERWISE, ALL WELDS SHALL BE 6mm CONTINUOUS FILLET WHERE POSSIBLE,
                OTHERWISE ADOPT CPBW. ALL WELDS SHALL BE CATERGORY GP U.N.O. ALL WELDS SHALL BE FROM
                                                                                                                                                                                                                                                                                                  M19      IN CAVITY/BRICK VENEER WALLS PROVIDE MEDIUM DUTY GALVANISED WALL TIES AT 600 CENTRES
                E43XX/W40X ELECTRODES OR ALTERNATIVES GIVING A NOMINAL TENSILE STRENGTH OF WELD
                METAL fuw OF 430MPa OR GREATER.                                                                                           MASONRY BLOCK & BRICKWORK                                                                                                                                        VERTICALLY AND HORIZONTALLY AND AT 300 AVERAGE CENTRES ADJACENT TO OPENINGS. TIES TO
                                                                                                                                                                                                                                                                                                           BE EMBEDDED A MINIMUM OF 50mm INTO THE MORTAR JOINTS. STAINLESS STEEL TIES SHALL BE
                                                                                                                                M1        ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS3700 MASONRY CODE AND                                                                                USED IN LOCATIONS LESS THAN 1km FROM THE COAST.
     S7         ALL CLEATS AND GUSSET PLATES SHALL BE 10mm THICK, UNLESS NOTED OTHERWISE.
                                                                                                                                          THE REFERENCED STANDARDS THEREIN.
     S8         ALL BOLTS SHALL BE M20 8.8/S UNLESS NOTED OTHERWISE. BOLT HOLES SHALL BE 2mm GREATER
                THAN SPECIFIED BOLT SIZE UNLESS NOTED OTHERWISE.                                                                M2       MINIMUMDURABILITY
                                                                                                                                        MINIMUM  DURABILITYREQUIREMENTS.
                                                                                                                                                            REQUIREMENTS.
                                                                                                                                          LOCATION                                       SALT ATTACK                        MORTAR               DURABILITY CLASS OF
     S9         BOLT DESIGNATIONS SHALL CONFORM TO THE FOLLOWING:                                                                                                                        RESISTANCE GRADE                   CLASS                WALL TIES AND BUILT
                                                                                                                                                                                         OF MASONRY UNITS                                        IN COMPONENTS
                       DESIGNATION           AUST. STANDARD     INSTALLATION METHOD
                                                                                                                                          INTERIOR MASONRY                               GENERAL PURPOSE                           M3                             R3

                           4.6/S             AS 1111           SNUG TIGHT                                                                 EXTERIOR MASONRY                                     GENERAL                             M3                             R3
                                                                                                                                          GREATER THAN 1 km FROM COAST                         PURPOSE
                           8.8/S             AS/NZS 1252       SNUG TIGHT
                                                                                                                                          EXTERIOR MASONRY                                     EXPOSURE                            M4                             R4
                           8.8/TB            AS/NZS 1252       FULLY TENSIONED (SOME SLIP ALLOWED)                                        UP TO 1 km FROM COAST

                           8.8/TF            AS/NZS 1252       FULLY TENSIONED WITH NO SLIP.                                    M3        ALL MASONRY BLOCKS SHALL HAVE A MINIMUM UNCONFINED COMPRESSIVE STRENGTH OF 15MPa.
                                                               CONTACT SURFACES TO BE FREE FROM
                                                               APPLIED FINISHES                                                 M4        ALL LOAD-BEARING BRICKS SHALL HAVE A MINIMUM UNCONFINED COMPRESSIVE STRENGTH OF
                                                                                                                                          20MPa.
 S10            LOAD INDICATING WASHERS SHALL BE USED TO VERIFY TIGHTENING OF BOLTS IN TF AND TB
                CONNECTIONS.                                                                                                    M5        CLAY BRICKS SHALL EXHIBIT A MAXIMUM 5 YEAR EXPANSION OF 1.0mm/m. THE BRICK SUPPLIER
                                                                                                                                          SHALL PROVIDE A RECENT TEST CERTIFICATE CONFIRMING THE EXPANSION.
 S11            WASHERS SHALL BE INSTALLED UNDER BOTH BOLT HEAD AND NUT AT ALL SLOTTED BOLT HOLE
                LOCATIONS.                                                                                                      M6        MORTAR SHALL BE CLASS M3 OR M4 IN ACCORDANCE WITH NOTE M2 ABOVE. REFER TO AS3700 FOR
                                                                                                                                          COMPLYING MIX PROPORTIONS. SAND SHALL BE CLEAN WELL GRADED AND FREE OF SILT AND CLAY.
 S12            CONCRETE ENCASED AND FIRE SPRAYED STEELWORK SHALL NOT BE PAINTED.                                                         NO "BRICKIES LOAM" ALLOWED.




C1        ##.##.####    REVISION NAME                                                                                                                                                            BRISBANE
                                                                                 DESIGNED:         APPROVED:
                                                                                                                                                                                            T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                          PROJECT NUMBER
                                                                                                                                                                                                               CONSULTANTS NAME                                                                                                                                                          S24-###
                                                                                                                                                   WE S TE R A
                                                                                                                                                                                              GOLD COAST
                                                                                 DRAWN:
                                                                                                                                                                                            T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                          SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                      SHEET NUMBER
                                                                                 CHECKED:
                                                                                                                                                   PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                           NORTHERN NSW
                                                                                                                                                                                                              USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                              PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                  TITLE:       CONSTRUCTION NOTES - SHEET 4
                                                                                                                                                                                                                                                                                                                                                                                           1.3
                                                                                                                                                                                                                                                                                                                                                                                            .
                                                                                 DATE:                                                STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                            T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                         CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                               CLIENT NAME                                                                          ##
                                                                                                                                                                                                              STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                 PAGE SIZE:   A3   For and on behalf of                www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                              CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                            REVISION
No.        DATE         REVISIONS                                   DRN   ENG                      WESTERA PARTNERS PTY. LTD.                                                               T: 03 5441 0922

Section 6

              TIMBER FRAMING                                                                                                     T12               UNLESS NOTED OTHERWISE, NAILS AND SCREWS TO BE DETAILED IN ACCORDANCE                                                                               TIEDOWN DETAILS (N4 EQUIVALENT)
                                                                                                                                                   WITH THE FOLLOWING TABLE:
      T1      ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS1720 - TIMBER STRUCTURES                                                                                                                                                                                                      BATTENS TO TRUSSES/RAFTERS
              CODE, AS1684 - RESIDENTIAL TIMBER FRAMED CONSTRUCTION STANDARD AND THE REFERENCED                                                                                   MINIMUM SPACING, EDGE & END DISTANCES                                                                                 ADOPT 1/75mm No.14 TYPE 17 SCREW TO ALL AREAS.
              STANDARDS THEREIN.                                                                                                                                                           FOR NAILS & SCREWS                                                                                           OR FOR PROPRIETARY BATTENS FIX TO MANUFACTURERS SPECIFICATIONS.
                                                                                                                                                                                                             MINIMUM DISTANCE
      T2      ALL FRAMING, BRACING AND TIEDOWN INFORMATION SPECIFIED FORM THE BASIS FOR THE DESIGN OF
                                                                                                                                                                                             HOLES FOR NAILS HOLES FOR NAIL                                 FOR SCREWS
                                                                                                                                                                                                                                                                                                        RAFTER TO TOP PLATE
              THE STRUCTURAL SUPPORT ELEMENTS DOWN TO THE FOUNDATIONS. ALTERNATIVE SOLUTIONS WILL                                      SPACING TYPE                                                                                                                                                     1/30x0.8 GI LOOPED STRAP WITH 5/2.8Ø NAILS EACH END
              ONLY BE PERMITTED UPON WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER.                                                                                                             NOT PREBORED PREBORED TO 80%
                                                                                                                                                                                                             OF NAIL DIAMETER
                                                                                                                                                                                                                                                                                                        RAFTER TO BEAM (FACE MOUNTED)
      T3      PREFABRICATED TIMBER ROOF TRUSSES, PROPRIETARY FLOOR JOIST SYSTEMS AND ALTERNATIVE                                  END DISTANCE                                                      20 D                             10 D                        10 D                                   1/LVSIA ANGLE BRACKET WITH 6/PRYDA WTF12-35 SCREWS EACH LEG
              TIMBER ELEMENTS TO THOSE SHOWN ON THE ENGINEERING DRAWINGS ARE TO BE DESIGNED AND                                                                                                                                                                                                         FIX EACH RAFTER TO BEAM WITH 2/No.14 TYPE 17 SCREWS WITH 35mm EMBEDMENT
              CERTIFIED BY THE SUPPLIER'S STRUCTURAL ENGINEER. DESIGN AND INSPECTION CERTIFICATES FOR                             EDGE DISTANCE                                                     5D                               5D                          5D
                                                                                                                                                                                                                                                                                                        TO END GRAIN
              THESE ELEMENTS ARE TO BE ISSUED TO THE BUILDER FOR LODGMENT WITH THE LOCAL AUTHORITY.                               BETWEEN NAILS OR SCREWS
                                                                                                                                                                                                    20 D                             10 D                        10 D
                                                                                                                                  - ALONG GRAIN
      T4      ALL TIMBER MEMBERS USED ARE TO HAVE A MINIMUM LEVEL OF DURABILITY AS SPECIFIED IN                                                                                                                                                                                                         RIBBON TOP PLATES
                                                                                                                                  - ACROSS GRAIN                                                    10 D                             3D                          3D                                     JOINTS IN PLATES SHALL BE OVER STUDS AND BE NOT LESS THAN 1200mm
              AS1684.2 - APPENDIX B
                                                                                                                                  D = SHANK DIAMETER OF NAIL                                                                                                                                            APART IN ADJOINING PLATES. A MINIMUM OF 2/75 x 3.05mm NAILS SHALL BE
      T5      ALL TIMBER SHALL BE SEASONED UNLESS NOTED OTHERWISE.                                                                                                                                                                                                                                      USED TO CONNECT THE DOUBLE PLATES TOGETHER AT EACH END .

      T6      ALL TIMBER SHALL BE FREE OF GUM VEINS, KNOTS AND ANY OTHER IMPERFECTIONS WITHIN                                   TIMBER SCHEUDLE                                                                                                                                                         TOP PLATES TO FRAME/SLAB BELOW
              CONNECTION ZONES.                                                                                                                                                                                                                                                                         M12 TIEDOWN RODS AS SHOWN ON ROOF & FLOOR FRAMING PLANS. RODS TO BE
                                                                                                                                 ROOF LEVEL                                                                                                                                                             FIXED TO SLAB VIA RAMSET CHEMSET INJECTION 800 SERIES OR EQUIVALENT.
      T7      UNLESS NOTED ON THE STRUCTURAL DRAWINGS, THE TIMBER ELEMENTS SPECIFIED HAVE NOT BEEN                               LOAD BEARING FRAME (3000 MAX HIGH)                                                                                                                                     FIXINGS HOLE DEPTH TO BE 125mm WITH 50mm SLAB EDGE CLEARANCE.
              DESIGNED TO SUPPORT HANGING DOORS, AIR CONDITIONING UNITS, WATER TANKS, ETC. THE                                   STUD AT 450crs               -       90 x 35 MGP12
              CONTRACTOR IS TO SUPPLY THE STRUCTURAL ENGINEER WITH THE NECESSARY INFORMATION TO                                  TOP PLATE                    -       3/35 x 90 MGP12                                                                                                                   PLATES TO STUDS
              DESIGN CHECK THE FRAMING ELEMENTS AND MAKE CHANGES ACCORDINGLY IF REQUIRED.                                        BOTTOM PLATE                 -       35 x 90 MGP12 (WHEN CONTINUOUSLY SUPPORTED)                                                                                       2/75mm NAILS SKEWED THROUGH STUD INTO THE PLATE.
                                                                                                                                 NOGGINGS                     -       90 x 35 MGP10 (AT 1350 crs)
      T8      WASHERS SHALL BE PROVIDED UNDER ALL NUTS AND BOLT HEADS BEARING AGAINST TIMBER IN
                                                                                                                                                                                                                                                                                                        MULTIPLE STUDS
              ACCORDANCE WITH THE FOLLOWING TABLE:                                                                               NON LOAD BEARING FRAME U.N.O.                                                                                                                                          1/75mm NAIL AT 600 MAX. CRS.
                                                                                                                                 STUDS AT 600 CENTRES, PLATES AND NOGGINGS - 90 x 35 MGP12
                                        BOLT SIZE                        WASHER                                                                                                                                                                                                                         NOGGING TO STUDS
                                                                                                                                 NON LOAD BEARING FRAME - BRACING PLY WALL                                                                                                                              2/75mm NAILS SKEWED OR THROUGH NAILED INTO STUDS
                                        UP TO M12                50 x 50 x 3.0mm THICK                                           STUDS AT 450 CENTRES, PLATES AND NOGGINGS - 90 x 35 MGP12
                                            M16                  57 x 57 x 4.0mm THICK                                                                                                                                                                                                                  BOTTOM PLATE TO BLOCK WALL COREFILL
                                                                                                                                                                                                                                                                                                        PROVIDE M10 RAMSET 801 CHEMSET, 120 MIN. EMBED. (50 EDGE DISTANCE)
                                            M20                  65 x 65 x 5.0mm THICK                                           SILL & HEAD TRIMMERS AT OPENINGS
                                        OVER M20                 75 x 75 x 6.0mm THICK                                           OPENING SPAN     0mm - 2400mm 35 x 90 MGP12
                                                                                                                                 OPENING SPAN 2401mm - 3000mm 2/35 x 90 MGP12                                                                                                                           BOTTOM PLATE TO CONCRETE SLAB
      T9      ALL BOLTS, WASHERS AND DRILLED IN ANCHORS SPECIFIED IN EXTERNAL AREAS ARE TO BE HOT DIP                            OPENING SPAN 3001mm - 3600mm 3/35 x 90 MGP12                                                                                                                           PROVIDE M10 BOLT, 75mm MASONRY NAIL(HAND DRIVEN AT SLAB EDGE)
              GALVANISED IN ACCORDANCE WITH AS1214.                                                                              OPENING SPAN >3600mm - REFER SPECIFIC DETAILS                                                                                                                          OR SCREW @ 1200mm max crs.

      T10 THE TIMBER MEMBERS SHOWN ON THE STRUCTURAL DRAWINGS ARE THOSE REQUIRED FOR THE
          COMPLETE STRUCTURE ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY                                         STUDS AT SIDE OF OPENINGS
          NECESSARY TEMPORARY CONNECTIONS, SUPPORTS AND BRACING TO MAINTAIN THE STABILITY AND                                    OPENING SPAN                  0mm - 900mm 1 STUD
          SAFETY OF THE TIMBERWORK THROUGHOUT THE CONSTRUCTION PERIOD.                                                           OPENING SPAN               1200mm - 2100mm 2 STUDS
          `                                                                                                                      OPENING SPAN               2400mm - 3000mm 3 STUDS
      T11 ALL BOLTS TO BE IN ACCORDANCE WITH THE FOLLOWING DETAIL:                                                               OPENING SPAN               3300mm - 3600mm 4 STUDS

                                                                 5D
                                         TIMBER MEMBER                                                                           ROOF FRAMING
                                                                MIN.
                                                                                                                                 RAFTERS AT 600 MAX. crs
                                                                                                                                 35 x 70 MGP12 BATTENS OR METAL ROOF BATTENS TO
                                                                                                                                 MANUFACTURERS SPECIFICATIONS AT 900 MAX. crs
                                                                                MIN.
                                                                                 4D
                             13D MIN.




                                                    LOAD                                    D = BOLT DIAMETER
                                                                                MIN.
                                                                                 5D




                                                    DIRECTION
                                                                                MIN.
                                                                                 4D




                                                                               STEEL CLEAT PLATE
                                                                               OR ANGLE BRACKET




C1     ##.##.####   REVISION NAME                                                                                                                                                            BRISBANE
                                                                               DESIGNED:         APPROVED:
                                                                                                                                                                                        T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                        PROJECT NUMBER
                                                                                                                                                                                                           CONSULTANTS NAME                                                                                                                                                         S24-###
                                                                                                                                           WE S TE R A
                                                                                                                                                                                          GOLD COAST
                                                                               DRAWN:
                                                                                                                                                                                        T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                      SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                  SHEET NUMBER
                                                                               CHECKED:
                                                                                                                                           PART NE RS                                   T: 07 5391 3777
                                                                                                                                                                                       NORTHERN NSW
                                                                                                                                                                                                          USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                          PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                              TITLE:       CONSTRUCTION NOTES - SHEET 5
                                                                                                                                                                                                                                                                                                                                                                                      1.4
                                                                                                                                                                                                                                                                                                                                                                                       .
                                                                               DATE:                                          STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                    DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                        T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                     CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                           CLIENT NAME                                                                      ##
                                                                                                                                                                                                          STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                               PAGE SIZE:   A3   For and on behalf of          www.westerapartners.com.au    ABN 52 097 417 975
                                                                                                                                                                                                          CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                          REVISION
No.        DATE     REVISIONS                                      DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                             T: 03 5441 0922

Section 7

                                                                                                                                                                 ROOF TRUSSES (OR SIMILAR)
                                                                                                   G.I. STRAP (TYPICAL)                                          WHERE APPLICABLE.
                                                                                                   REFER TIE-DOWN DETAILS                                                            TOP PLATE. REFER
                                    HEADER STUDS TO MATCH                                                                                                                            TIMBER SCHEDULE.                                                          COLUMN DEFINITON DIAGRAM
                                    WALL STUDS




                                                                                                   LINTEL.
                                                                                                   REFER
                                                                                                   PLAN.

                                                                                                                                                                                                                                                                         COLUMN TO ABOVE (AB)
                                                                                                                                                                                                                                                                COLUMN CONTINUOUS THROUGH FLOOR ABOVE



                                                                                                        LINTEL TRIMMER
 M12 TIE-DOWN ROD                                                                                       REFER TIMBER
 REFER PLAN FOR                                                                                         SCHEDULE.
 LOCATIONS                               100                                                                                                                                       100
                                         MAX.                                                     OP                                                                               MAX.
                                                                                                       EN                                                                                                     NOGGING.
                                                             90x35 MGP12                                 ING                                90x35 MGP12                                                       TYPICAL.
                                                             STUDS AT SIDES                                                                 STUDS AT SIDES                                                                                                                     COLUMN OVER (CO)
                                                             OF OPENING. REFER                                                              OF OPENING. REFER                                                                                                             COLUMN STARTS AT FLOOR ABOVE
                                                             TIMBER SCHEDULE.                                                               TIMBER SCHEDULE.

                                                                                 SILL TRIMMER
                                                                                 REFER TIMBER
                                                                                 SCHEDULE.




                                                                                                                                                                                                                                                                        COLUMN DROPPER (CD)
                                                                                                                                                                                                                                                              COLUMN DROPS FROM FLOOR (OR ROOF) ABOVE




        COUPLER AS                                                                                                                                                                                              BOTTOM PLATE.
        REQUIRED.                                                                                                                                                                                               REFER TIMBER
        TYPICAL.                                                                                                                                                                                                SCHEDULE.


                                                                                                                                                                                                    TIE-DOWN ROD CONNECTION
                                                                                                                                             SILL STUDS TO MATCH                                    TO SLAB/FOOTING OR TO
                                                                                                                                             WALL STUDS                                             UNDERSIDE OF LOWER
                                   SLAB (OR BEAM)                                                                                                                                                   FLOOR TOP PLATE
                                                              TYPICAL FRAMING ELEVATION
                                                                                                                                                         2/75x3.05mm NAILS
                                                2/75x3.05mm NAILS                    2/90x35 MGP12
                                                                                                                                                         AT EACH STUD
                                                AT EACH STUD                         TOP PLATE
                                                                                                                                                         (TYPICAL)
                                                (TYPICAL)




                                                                                                                                                                  STUD
                                                                                                                                                                  (TYPICAL)



                                        TYPICAL DOUBLE TOP PLATE CONNECTION DETAIL
C1    ##.##.####   REVISION NAME                                                                                                                                                                               BRISBANE
                                                                                      DESIGNED:                APPROVED:
                                                                                                                                                                                                          T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT   PROJECT NUMBER
                                                                                                                                                                                                                             CONSULTANTS NAME                                                                                                                  S24-###
                                                                                                                                                              WE S TE R A
                                                                                                                                                                                                            GOLD COAST
                                                                                      DRAWN:
                                                                                                                                                                                                          T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                                        SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                            SHEET NUMBER
                                                                                      CHECKED:
                                                                                                                                                              PART NE RS                                  T: 07 5391 3777
                                                                                                                                                                                                         NORTHERN NSW
                                                                                                                                                                                                                            USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                                            PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                                TITLE:    CONSTRUCTION NOTES - SHEET 6
                                                                                                                                                                                                                                                                                                                                                                 1.5
                                                                                                                                                                                                                                                                                                                                                                  .
                                                                                      DATE:                                                      STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                   DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                                          T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                                       CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                                          CLIENT NAME                                  ##
                                                                                                                                                                                                                            STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                      PAGE SIZE:        A3     For and on behalf of               www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                                            CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                     REVISION
No.    DATE        REVISIONS                                             DRN   ENG                             WESTERA PARTNERS PTY. LTD.                                                                 T: 03 5441 0922

Section 8

                     POOL                                                                                                              PILING
        NP1          ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS2783 - USE OF                                P1       ALL PILES SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH AS2159 PILING CODE AND
                     REINFORCED CONCRETE FOR SWIMMING POOLS AND REFERENCED STANDARDS THERE IN.                                         THE REFERENCED STANDARDS THEREIN.

        NP2          ALL TOPSOIL AND ORGANIC MATTER UNDER POOL FLOOR IS TO BE REMOVED. THE DESIGN                             P2       REFER TO GEOTECHNICAL REPORT FOR SOIL PROFILE ACROSS SITE AND FOUNDING
                     REQUIRES THAT THE POOL BE CONSTRUCTED ON UNDISTURBED SOUND NATURAL GROUND                                         RECOMMENDATIONS.
                     HAVING A SAFE ALLOWABLE BEARING PRESSURE OF NOT LESS THAN 75 KPa UNLESS
                     APPROVED BY THE ENGINEER.                                                                                P3       REFER TO FOOTING PLAN FOR REQUIRED ALLOWABLE PILE LOADS.

        NP3          WHERE THE POOL WALLS ARE NOT POURED AGAINST SOUND NATURAL GROUND TO LEVELS                               P4       THE PILE LOADS NOMINATED ON THE DRAWINGS DO NOT MAKE ALLOWANCE FOR NEGATIVE SKIN
                     SHOWN ON THE DRAWINGS, THE DESIGN OF THE WALLS MAY REQUIRE MODIFICATION. REFER                                    FRICTION OR OTHER SOIL LOADS. THE PILING CONTRACTOR SHALL MAKE SUITABLE ALLOWANCE
                     TO ENGINEER.                                                                                                      IN THE PILE DESIGN FOR SUCH SOIL LOADS WHERE SPECIFIED ON THE GEOTECHNICAL REPORT
                                                                                                                                       OR DEEMED APPROPRIATE.
        NP4          IF OVER EXCAVATION IS REQUIRED TO ACHIEVE UNDISTURBED SOUND NATURAL GROUND TO
                     THE UNDERSIDE OF THE POOL BASE, SEAT AND BENCH AREAS, THE OVER EXCAVATION SHALL                          P5       PILES SHALL ALSO BE DESIGNED FOR THE MINIMUM BENDING MOMENTS
                     BE BACKFILLED WITH 15MPa CONCRETE PRIOR TO FORMING AND CASTING THE POOL.                                          INDUCED BY ANY LOAD ECCENTRICITY DUE TO PILE POSSITIONAL DEVIATION
                                                                                                                                       IN ACCORDANCE WITH AS2159.
        NP5          WHERE THERE ARE VARYING FOUNDATION CONDITIONS OVER THE POOL AREA OR WHERE
                     UNDISTURBED SOUND NATURAL GROUND IS NOT ENCOUNTERED REFER TO ENGINEER FOR                                P6       PILES SHALL BE DESIGNED FOR DURABILITY IN ACCORDANCE WITH AS2159, TAKING INTO
                     FOUNDATION DESIGN.                                                                                                ACCOUNT THE AGGRESSIVENESS OF THE GROUND AND THE ENVIRONMENTAL CONDITIONS.

        NP6          A 100mm LAYER OF 20mm DIAMETER (MAXIMUM) GRAVEL IS TO BE SPREAD UNDER THE POOL
                     SLAB WHERE IT IS NOT FOUNDED ON FREE DRAINING MATERIAL.                                                  P7       A PILE SETOUT PLAN AND FULL DETAILS OF THE PROPOSED PILE TYPE, MATERIAL AND
                                                                                                                                       INSTALLATION METHOD SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW PRIOR TO
        NP7          THE DESIGN REQUIRES THAT GROUND WATER PRESSURE TO POOL WALLS AND FLOOR SLAB BE                                    COMMENCING WORKS ON SITE.
                     RELIEVED BY INSTALLATION OF A HYDROSTATIC RELIEF VALVE WITH MAIN DRAIN DETAIL.
                                                                                                                              P8       WHERE PILE SPLICES ARE REQUIRED, FULL DETAILS SHALL BE SUBMITTED TO THE ENGINEER
        NP8          THE VERTICAL WALL REINFORCEMENT SHOWN ON SECTIONS SHOULD BE NOMINALLY ON THE                                      FOR REVIEW PRIOR TO INSTALLATION.
                     CENTRE LINE OF THE WALL UNLESS NOTED OTHERWISE, AND SHOULD BE ACCURATELY BENT
                     TO REMAIN CENTRAL AROUND THE CURVATURE AND INTO THE BASE.                                                P9       THE PILING CONTRACTOR SHALL TRIM ALL PILES TO THE CUT OFF LEVELS INDICATED ON THE
                                                                                                                                       FOOTING DETAILS.
        NP9          THE MINIMUM CONCRETE COVER TO REINFORCEMENT SHALL COMPLY WITH THE FOLLOWING
                     UNLESS NOTED OTHERWISE:                                                                                  P10      ALL PILES SHALL BE ANCHORED INTO THE FOOTING SO THAT THE DESIGN LOADS
                     FORMED FACES - 40mm                                                                                               AND BENDING MOMENTS (AS PER NOTE 5) CAN BE SAFELY TRANSFERRED INTO
                     INTERNAL FACES - 50mm                                                                                             THE PILES. FULL DETAILS SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW
                     FACES CAST AGAINST GROUND - 60mm                                                                                  PRIOR TO INSTALLATION. DOWEL BARS FOR SCREW PILES SHALL BE DESIGNED
                     BAR CHAIRS SHALL BE USED TO ENSURE THE REQUIRED COVER IS MAINTAINED.                                              AND PROVIDED BY THE PILING CONTRACTOR.

       NP10          CONCRETING SHALL BE CARRIED OUT IN ONE CONTINUOUS OPERATION AND SHALL BE APPLIED                         P11      THE PILING CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL OBSTRUCTIONS
                     BY THE PNEUMATIC SPRAYED PROCESS BY EXPERIENCED OPERATORS. CONCRETE SHALL                                         THAT IMPEDE THE INSTALLATION OF PILES.
                     HAVE A MINIMUM ULTIMATE COMPRESSIVE STRENGTH (f'c) OF 40MPa AT 28 DAYS MINIMUM
                     CEMENT CONTENT OF 280 kg/m3 AND MAXIMUM 10mm AGGREGATE.                                                  P12      THE PILING CONTRACTOR SHALL SUBMIT TO THE ENGINEER FOR REVIEW PRIOR TO COMMENCING
                                                                                                                                       WORKS, EITHER GEOTECHNICAL CALCULATIONS BASED UPON THE SOIL PARAMETERS IN THE
       NP11          IMMEDIATELY AFTER PNEUMATIC CONCRETE HAS BEEN PLACED, IT SHOULD BE PROTECTED                                      SOIL REPORT, PILE LOAD TEST RESULTS OR TRIAL PILE DATA TO VERIFY THE PROPOSED
                     FROM PREMATURE DRYING BY SHADING FROM DIRECT SUNLIGHT AND SHIELDING FROM WIND.                                    FOUNDING DEPTHS OF THE PILES, ALONG WITH FACTOR OF SAFETY ADOPTED IN THE DESIGN.
                     AS SOON AS CONCRETE HAS HARDENED SUFFICIENTLY IT SHOULD BE THOROUGHLY WETTED
                     AND THEREAFTER KEPT WET CONTINUOUSLY FOR AT LEAST 7 DAYS.                                                P13      THE PILING CONTRACTOR SHALL SUBMIT TO THE ENGINEER FOR REVIEW PRIOR TO COMMENCING
                                                                                                                                       WORKS, THE PROPOSED SCREW PILE TORQUE OR PILE DRIVING SET TO ACHIEVE THE REQUIRED
       NP12          IF SALT CHLORINATOR IS USED, CONCENTRATION OF SODIUM CHLORIDE TO BE KEPT BELOW                                    SAFE ALLOWABLE LOAD CAPACITIES FOR THE PILES, ALONG WITH EITHER GEOTECHNICAL
                     10000 P.P.M.                                                                                                      CALCULATIONS BASED UPON THE SOIL PARAMETERS IN THE SOIL REPORT, PILE LOAD TESTS
                                                                                                                                       RESULTS OR TRIAL PILE DATA TO VERIFY THE PILE TORQUE OR DRIVING SET ADOPTED.
       NP13          SURFACE WATER FROM SURROUNDING AREAS SHOULD BE DIRECTED AWAY FROM THE POOL.
                                                                                                                              P14      THE PILING CONTRACTOR SHALL PROVIDE ALL DESIGN, CHECKING AND INSPECTION
       NP14          POOL PLUMBING, ETC TO BE BY OTHERS.                                                                               CERTIFICATION FOR THE PILING WORKS REQUIRED BY THE STATUTORY AUTHORITY, DULY
                                                                                                                                       SIGNED BY AN APPROPRIATELY REGISTERED PROFESSIONAL ENGINEER FOR THE STATE IN
       NP15          POOL FENCING BY OTHERS IN ACCORDANCE WITH AS1926 PART 1 & 2 AND LOCAL COUNCIL                                     WHICH THE PROJECT IS LOCATED.
                     REQUIREMENTS.
                                                                                                                              P15      THE PILING CONTRACTOR SHALL ENGAGE A LICENSED SURVEYOR TO UNDERTAKE AN AS
                                                                                                                                       CONSTRUCTED SURVEY OF THE PILE LOCATIONS AND PROVIDE THE RESULTS TO THE ENGINEER
                                                                                                                                       PRIOR TO THE CONSTRUCTION OF FOOTINGS OVER THE PILES.

                                                                                                                              P16      THE PILING CONTRACTOR SHALL SUBMIT TO THE ENGINEER ALL PILING RECORDS REQUIRED BY
                                                                                                                                       SECTION 7 OF AS2159 PILING CODE, INCLUDING PILE TORQUE OR DRIVING SET RESULTS FOR
                                                                                                                                       EACH PILE.

                                                                                                                              P17      ALL EXISTING SERVICES ARE TO BE LOCATED BY THE PILING CONTRACTOR PRIOR TO
                                                                                                                                       COMMENCING WORKS. MINIMUM CLEARANCES TO SERVICES ARE TO BE MET IN
                                                                                                                                       ACCORDANCE WITH RELEVANT AUTHORITY REQUIREMENTS.




C1    ##.##.####   REVISION NAME                                                                                                                                                             BRISBANE
                                                                               DESIGNED:         APPROVED:
                                                                                                                                                                                        T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT   PROJECT NUMBER
                                                                                                                                                                                                           CONSULTANTS NAME                                                                                                                  S24-###
                                                                                                                                               WE S TE R A
                                                                                                                                                                                          GOLD COAST
                                                                               DRAWN:
                                                                                                                                                                                        T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                      SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                          SHEET NUMBER
                                                                               CHECKED:
                                                                                                                                               PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                       NORTHERN NSW
                                                                                                                                                                                                          USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                          PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                              TITLE:    CONSTRUCTION NOTES - SHEET 7
                                                                                                                                                                                                                                                                                                                                               1.6
                                                                                                                                                                                                                                                                                                                                                .
                                                                               DATE:                                           STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                   DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                        T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                     CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                        CLIENT NAME                                  ##
                                                                                                                                                                                                          STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                               PAGE SIZE:   A3   For and on behalf of              www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                          CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                     REVISION
No.    DATE        REVISIONS                                       DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                             T: 03 5441 0922

Section 9

                                                  STANDARD COG
                                                  (TYP.)
             SUSPENDED SLAB


                                                                                                                                                   REFER BLOCK WALL                                                 CORNER BARS TO MATCH
                                                                                                                                                   SCHEDULE FOR BLOCK                                               HORIZONTAL REINFORCEMENT
                                                                                                                                                   TYPE, COREFILL AND
                                                                                                                                                   REINFORCEMENT DETAILS                                                                                                                                                                                  INTERSECTION BARS TO MATCH
                                                                                                                                                                                                                    VERTICAL BARS TO BE LOCATED                                                    LAP                                     LAP            HORIZONTAL REINFORCEMENT
                                                                                                                                                                                                                    AT ALL WALL END CORES
                                                                                                                                                   NOTE:                                                            (TYP.)
                                                                                                                                                   REFER APPLICABLE PLAN
                                                                                                                                                   AND LEGEND FOR WALL TYPE
                                                      NOTE:




                                                                                                                LAP LENGTH
                                                      REFER APPLICABLE PLAN
                                                      AND LEGEND FOR WALL TYPE
                                                                                                                                                   DENOTES CLEAN OUT
                                                                                                                                                   COURSE (TYP).




                                                                                                                                                                                                                                                                                                                                           LAP
                                                                                                                                                                                                                                                        LAP
                                                      REFER BLOCK WALL
                                                      SCHEDULE FOR BLOCK
                                                                                                                                          SUSPENDED SLAB                                                                                                                                                                                                  REFER BLOCK WALL
                                                      TYPE, COREFILL AND
                                                                                                                                                                                                                                                                                                    REFER BLOCK WALL                                      SCHEDULE FOR BLOCK
                                                      REINFORCEMENT DETAILS
                                                                                                                                                                                                                                                                                                    SCHEDULE FOR BLOCK                                    TYPE, COREFILL AND
                                                                                                                                                                                                                                                                                                    TYPE, COREFILL AND                                    REINFORCEMENT DETAILS
                                                                                                                                                                                                                                                                                                    REINFORCEMENT DETAILS



                                                                                                                                                    REFER BLOCK WALL                                                                                                  BLOCK INTERSECTION PLAN DETAILS
                    LAP LENGTH




                                                                                                                                                                                                                                                                    BLOCK INTERSECTION PLAN DETAILS
                                                                                                                                                    SCHEDULE FOR BLOCK                                                                                                       SCALE 1 : 20
                                                                                                                                                    TYPE, COREFILL AND
                                                      DENOTES CLEAN OUT                                                                             REINFORCEMENT DETAILS
                                                      COURSE (TYP).

                                                      SLAB/FOOTING




                                                                                                                                                                                                                                                                                  LAP                                                LAP         INTERSECTION BARS TO MATCH
                                                  STARTER BARS WITH                                                                                                                             VERTICAL BARS TO BE LOCATED                                                                                                                      HORIZONTAL REINFORCEMENT
                                                  STANDARD COGS(TYP.)                                                                                                                           AT ALL WALL END CORES (TYP.)



               TYPICAL LOAD BEARING BLOCK WALL (BW#) DETAILS
               SCALE 1 : 20
                                                                                                                                                                                                                                                                                     CORNER BARS TO MATCH
                                                                                                                                                                                                                                                                                     HORIZONTAL REINFORCEMENT
                                                     BLOCK WALL SCHEDULE




                                                                                                                                                                                                                                                                                                                               LAP
                                                                                                                                                                                                                                      LAP
             WALL TYPE               BLOCK TYPE         VERTICAL & STARTER      HORIZONTAL & CORNER          S20 COREFILL            S40 COREFILL                                                                                                                                                                                                REFER BLOCK WALL
                                     (STRENGTH)         BAR REINFORCEMENT       BAR REINFORCEMENT               EXTENT                  EXTENT                                                                                                                                       REFER BLOCK WALL                                            SCHEDULE FOR BLOCK
                                                                                                                                                                                                                                                                                     SCHEDULE FOR BLOCK                                          TYPE, COREFILL AND
                                     200 SERIES
                   BW1                                 N12 TO END CORES &                                                                                                                                                                                                            TYPE, COREFILL AND                                          REINFORCEMENT DETAILS
                                       BLOCKS                                           N12-400                          100%             -
                                                      400 MAX. CRS. CENTRAL                                                                                                                                                                                                          REINFORCEMENT DETAILS
                                        (MPa)
                                     200 SERIES
                                                              TBC
                   BW1-R               BLOCKS
                                        (MPa)
                                                                                        N12-400                          100%             -
                                                                                                                                                                                                                                            BLOCK INTERSECTION PLAN DETAILS 300 SERIES
                                                                                                                                                                                                                                            SCALE 1 : 20
                                          -
                                     300 SERIES
                    -
                   BW2                                         -
                                                              TBC
                                       BLOCKS                                              -
                                                                                       2/N12-400                           -
                                                                                                                         100%             -
                                        (MPa)

            NOTE:
            • 'H' BLOCKS TO BE ADOPTED TYPICALLY WHERE DETAILING PERMITS                                                                                    TYPICAL BLOCK REINFORCEMENT LAP LENGTHS
            • REFER MASONRY BLOCKWORK & BRICKWORK NOTES ON SHEET 1.1 FOR ADDITIONAL REQUIREMENTS
                                                                                                                                                                    BAR                         LAP LENGTH UNO
               INCLUDING NOTE M2 FOR DURABILITY REQUIREMENTS
                                                                                                                                                                    N12                                  500
                                                                                                                                                                    N16                                  700
                                                                                                                                                                    N20                                  1200
C1    ##.##.####     REVISION NAME                                                                                                                                                               BRISBANE
                                                                                      DESIGNED:         APPROVED:
                                                                                                                                                                                            T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                         PROJECT NUMBER
                                                                                                                                                                                                               CONSULTANTS NAME                                                                                                                                          S24-###
                                                                                                                                                   WE S TE R A
                                                                                                                                                                                              GOLD COAST
                                                                                      DRAWN:
                                                                                                                                                                                            T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                          SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                     SHEET NUMBER
                                                                                      CHECKED:
                                                                                                                                                   PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                           NORTHERN NSW
                                                                                                                                                                                                              USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                              PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                  TITLE:    BLOCK WALL DETAILS
                                                                                                                                                                                                                                                                                                                                                                          2.0
                                                                                                                                                                                                                                                                                                                                                                           .
                                                                                      DATE:                                           STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                            T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                         CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                            CLIENT NAME                                                           ##
                                                                                                                                                                                                              STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                      PAGE SIZE:   A3   For and on behalf of           www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                              CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                           REVISION
No.    DATE           REVISIONS                                           DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                          T: 03 5441 0922

Section 10

                                                                                                                                                                                                          R16 DOWEL (GALV.) 600 LONG                                                             N16 DOWEL BARS
                                                                                                                                             B.C.J.                                                       GREASE & TAPE ONE END                                                                  LAPPED WITH
R16 CORNER DOWEL (GALV.)                                                                                                                                                                                                                                                                         HORIZONTAL BLOCK
                                                                                                                                                                               300                        AS SHOWN. PROVIDE AT EACH
GREASE & TAPE ONE END                                            LAP                                                                                                                                                                                                                             REINFORCEMENT
                                                                                                                                                                                                          HORIZONTAL BAR LOCATION
AS SHOWN. PROVIDE AT EACH                                                                                                                                                                                                                                                                        DRILL & EPOXY




                                                                                                                                                                                                                                                                                                                                                                      LAP LENGTH
HORIZONTAL BAR LOCATION                                                                                                                                                                                                                                                                          INTO CONCRETE
                                                                                                                                                                                                                                                                                                 (125 MIN. EMBED.)
                                      B.C.J.
                                             300




                                                                      10mm COMPRESSIBLE JOINT                                                                                   10mm COMPRESSIBLE JOINT
                                                                      FILLER WITH APPROVED FIRE                                                                                 FILLER WITH APPROVED FIRE
                                                                      RATED/WATERPROOF FLEXIBLE                                                                                 RATED/WATERPROOF FLEXIBLE
                                                                                                                                                                                                                                                                                                                                                               100
                                                                      SEALANT.                                                                                                  SEALANT.                                                                                                         REINFORCED CONCRETE
                                                                                                                                                                                                                                                                                                                                                               MIN.
                                                                                                                                                                                                                                                                                                 WALL / COLUMN
                                                                      REFER BLOCK WALL
                                                                                                                                                  NOTE:
                                                                      SCHEDULE FOR BLOCK
                                                                                                                                                  WHERE REQUIRED ADOPT SIMILAR DETAIL                                                                                                                                                         PLAN VIEW
                                                                      TYPE, COREFILL AND
                                                                                                                                                  AT CONCRETE WALLS / COLUMNS EXCEPT
                                                                      REINFORCEMENT DETAILS
                                                                                                                                                  DRILL AND EPOXY DOWEL BARS (125 MIN. EMBED.)
                                                   BCJ: DENOTES BLOCKWORK CONTROL JOINT:
                                                   BCJ LOCATIONS ARE TO COMPLY WITH NOTE M16
                                                                                                                                                                                                                                                                                      TYPICAL BLOCK WALL TO CONCRETE
                                                   ON SHEET 1.3
                                                                                                                                                  BCJ: DENOTES BLOCKWORK CONTROL JOINT:
                                                                                                                                                  BCJ LOCATIONS ARE TO COMPLY WITH NOTE M16                                                                                           WALL / COLUMN CONNECTION
                                                                                                                                                  ON SHEET 1.3
                                                       BLOCK CONTROL JOINT (BCJ) PLAN DETAILS                                                                                                                                                                                         SCALE 1 : 20

                                                       SCALE 1 : 20




                                                        1/N16 IN KNOCKOUT                                                                                                                                                                                   150 OR 200 SERIES
                                                        TOP COURSE                                                                                                                                                                                          BLOCK WALL                                                                                                                          WALL BEYOND
                                                        (700 MIN. LAPS)                                                                                                                                                                                     (REFER ARCH.)
                                                                                                                                                                                                                                                            ALL CORES FILLED
                                                                                                                                                                                 150 OR 200 SERIES BLOCK
                                                        200 SERIES BLOCK                                                                                                         (REFER ARCH.)
                                                        ALL CORES FILLED                                                                                                                                                                                    1/N16 IN KNOCKOUT                                                       PLANTER
                                                                                                                                                                                 ALL CORES FILLED                                                                                                                                                                                                                    1/N12 IN KNOCK OUT COURSE, REFER
                                                                                                                                                                                                                                                            TOP COURSE
                                                                                                                                                                                                                                                                                                                                                                                                                     TYPICAL MASONRY LINTEL ELEVATION
                                                                                                                                                                                                                                                            (700 MIN. LAPS)
                                                                                                                                                                                                                                                                                                                                                                                                                     FOR TERMINATION DETAILS INTO
                                                                                                                                                                                 1/N16 IN KNOCKOUT                                                                                                                                                                                                                   ADJACENT BLOCK WALL.
       1800 MAX HEIGHT




                                                                                                                                                                                 TOP COURSE                                                                                                                                         WATERPROOFING/TANKING.
                                                        N12-400 VERTICALS                                                                                                                                                                                   N12-400 HORIZ.
                                                                                                                                                                                                                                                                                                                                    REFER ARCHITECTS DETAILS.




                                                                                                                                                                                                                                          1200 MAX HEIGHT
                                                                                                              1200 MAX HEIGHT




                                                        (CENTRAL)                                                                                                                                                                                           (500 MIN LAPS)
                                                                                                                                     LAP LENGTH




                                                                                                                                                                                                                                                                                                                                                                                                   1600 MAX.
                                                        N12-400 HORIZ.                                                                                                           N12-400 HORIZ.                                                                                                                     55
                                                        (500 MIN LAPS.)                                                                                                          (500 MIN. LAPS)                                                                                                                  COVER                                                                                              N12-400 HORIZONTAL
                                                                                                                                                                                                                                                                                                                                                                                                                     BARS, 500 MIN LAPS.




                                                                                                                                                                                                                                                                                                                             LAP LENGTH
                                                                                                                                                                                                                                                            N12-400 VERTICALS
                                                                                                                                                                                 N12-400 VERTICALS                                                          & STARTERS                                                                                                                                               N12-400 VERTICAL AND STARTER




                                                                                                                                                                                                                                                                                                                                                                                                               LAP
                                                        N16-400 & STARTERS
                                                                                                                                                                                 & STARTERS (CENTRAL)                                                                                                                                                                                                                BARS EACH FACE (CENTRAL).
                                                        (CENTRAL)
                         LAP LENGTH




                                                                                          SLAB / FOOTING                                                                                                                                                                                                                                                                                                             NOTE: FOR HEIGHTS 600 OR LESS
                                                                                                                                                                                                                                                                                                                    55
                                                                                                                                                                                                                                                                                                                  COVER                                                                                              STARTERS ONLY REQUIRED
                                                                                                                                                                                                                                                                                                                                                                                      SLAB/FOOTING                                                    SLAB/
                                                                                                                                                                                                                                                                SLAB / FOOTING

                                                                                                             NOTE:
                                                    SLAB / FOOTING                                           WHERE UPSTAND IS 800 OR LESS IN HEIGHT
                                                                                                             ONLY STARTERS ARE REQUIRED

                                                                                                                                                                                                                                                                                                                                                                                   TYPICAL 150/200 SERIES BLOCK
                                                                                      BLOCK UPSTAND (BU) DETAIL                                                                                                                        BLOCK PLANTER WALL (PW) DETAIL                                                                                                              SILL (BS) DETAIL
 BLOCK FENCE (BF) DETAIL                                                              SCALE 1 : 20
                                                                                                                                                                                                                                       SCALE 1 : 20                                                                                                                                SCALE 1:20
 SCALE 1 : 20


C1    ##.##.####                 REVISION NAME                                                                                                                                                                                                    BRISBANE
                                                                                                 DESIGNED:                                        APPROVED:
                                                                                                                                                                                                                                             T: 07 3852 4333      CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                             PROJECT NUMBER
                                                                                                                                                                                                                                                                  CONSULTANTS NAME                                                                                                                                                            S24-###
                                                                                                                                                                                                 WE S TE R A
                                                                                                                                                                                                                                               GOLD COAST
                                                                                                 DRAWN:
                                                                                                                                                                                                                                             T: 07 5571 1599                                                                                         LOCATION: PROJECT LOCATION
                                                                                                                                                                                                                                           SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                                                                           SHEET NUMBER
                                                                                                 CHECKED:
                                                                                                                                                                                                 PART NE RS                                  T: 07 5391 3777
                                                                                                                                                                                                                                            NORTHERN NSW
                                                                                                                                                                                                                                                                 USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                                                                                 PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                                                                     TITLE:    BLOCK WALL DETAILS
                                                                                                                                                                                                                                                                                                                                                                                                                                                2.1
                                                                                                                                                                                                                                                                                                                                                                                                                                                 .
                                                                                                 DATE:                                                                           STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                        DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                                                                             T: 02 6674 8047     THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                                                                          CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                                                                               CLIENT NAME                                                                            ##
                                                                                                                                                                                                                                                                 STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                                 PAGE SIZE:                     A3                For and on behalf of               www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                                                                                 CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                               REVISION
No.    DATE                       REVISIONS                                         DRN    ENG                                                    WESTERA PARTNERS PTY. LTD.                                                                 T: 03 5441 0922

Section 11

                                                                             NAILING PLATE (IF REQUIRED)                                                                            LIGS                                                     BLOCK LINTEL SCHEDULE (UNO)
                                                                             REFER PLAN FOR DETAILS                                                                                 REFER SCHEDULE
                                                                                                                                                                                                                                             TYPE                                 SPAN                     BOTTOM REO.         TOP REO.         HORIZ. REO.             LIGS
                                      LAP LENGTH                                          TOP REO.
                                                                                          REFER SCHEDULE                                                                              LAP LENGTH                                                                              1200 MAX.                          1/N12           1/N12            N12-400           R10-200




                                                                                                                                           60
                                                                                                                                                                                                                                                   BL                         2400 MAX.                          1/N16           1/N16            N12-400           R10-200
                                                                                                                                                                                                                                              (200 SERIES
                                                                                                                                                                                                                                                BLOCK)                        3000 MAX.                          2/N16           2/N16            N12-400           R10-200

                                                                                                                                                                                                                                                                              4500 MAX.                          2/N16           2/N16            N16-400           R10-200


                                                                                                                                                                                                                                                                                                                                          TOP REINFORCEMENT IN SLAB.
                                                                                                                                                                                                                                                                                                                                          REFER BLOCK LINTEL SCHEDULE
                                                                                                                                                                                                                                                                                                                                          AND ELEVATION FOR DETAILS.
                                                                                                                                                                                                                                                                                                                                                                                                       SUSPENDED SLAB
                                                                                                                                                                                                                                                                                                                    INDICATIVE ROOF TIE                                                                REFER SLAB PLAN
                                                                                          BOTTOM REO.                                            LINTEL BLOCKS                                                                              TOP REO IN KNOCKOUT TOP                                                 DOWN OR FIXING
                                                                                          REFER SCHEDULE                                                                                                                                    COURSE REFER BLOCK                                                      WHERE APPLICABLE.
                                                                                                                                                 COG BAR 300 MIN.                                                                           LINTEL SCHEDULE AND
                                                                    KNOCK OUT BLOCKS                                    OPENING                  WHERE INSUFFICIENT                                                                         ELEVATION FOR DETAILS.
                                                                    TYPICAL                                                                      WALL LENGTH AVAILABLE                                                                                                                                                                                                         TOP REO IN KNOCKOUT TOP COURSE
                                                                                                                                                                                                                                                                                                                                                                               REFER BLOCK LINTEL SCHEDULE
                                                                                                                                                                                                                                                                                                                    HORIZONTAL REO (REFER                                      AND ELEVATION FOR DETAILS.
                                                                    NOTE:                                                                                                                                                                                                                                           BLOCK LINTEL SCHEDULE)
                                                                    WALL REINFORCMENT NOT SHOWN FOR                                                                                                                                                                                                                                                                            HORIZONTAL REO (REFER
                                                                                                                                                                                                                                                                                                                                                                                                                ENGINEER




                                                                                                                                                                                                                                                                                  'D'




                                                                                                                                                                                                                                                                                                                                                              'D'
                                                                    CLARITY. REFER BLOCK WALL SCHEDULE                                                                                                                                                                                                                                                                         BLOCK LINTEL SCHEDULE)
                                                                                                                                                                                                                                                                                                                    LIGS OVER OPENING                                                                           ALL LINTEL
                                                                    AND DETAILS AS APPLICABLE                                                                                                                                                                                                                       (REFER BLOCK LINTEL                                        LIGS OVER OPENING                DEPTHS TO
                                                                                                                                                                                                                                                                                                                    SCHEDULE)                                                  (REFER BLOCK LINTEL
                                                                                                                                                                                                                                                                                                                                                                                                                A PER PROJ
                                                                                                                                                                                                                                                                                                                                                                               SCHEDULE)
                                                                                                                                                                                                                                                                                                                                                                                                                REINFORCE
                                                                                                                                                                                                                                                                                                                    BOTTOM REO, REFER                                                                           REQUIRED.
                                               TYPICAL BLOCK LINTEL ELEVATION                                                                                                                                                                                            75 TO BTM
                                                                                                                                                                                                                                                                         OF BAR
                                                                                                                                                                                                                                                                                                                    BLOCK LINTEL SCHEDULE
                                                                                                                                                                                                                                                                                                                    AND ELEVATION FOR DETAILS
                                                                                                                                                                                                                                                                                                                                                      75 TO BTM
                                                                                                                                                                                                                                                                                                                                                      OF BAR
                                                                                                                                                                                                                                                                                                                                                                               BOTTOM REO, REFER
                                                                                                                                                                                                                                                                                                                                                                               BLOCK LINTEL SCHEDULE
                                                   SCALE   1 : 20                                                                                                                                                                                                                                                                                                              AND ELEVATION FOR DETAILS
                                                                                                                                                                                                                                                                         WALL BEYOND                                                                  WALL BEYOND
                                                     N16 DOWEL BARS TOP AND BOTTOM                                                                                                 1/N16 IN CONTINUOUS LNOCKOUT
                                                     AT 400 MAX. CRS. CENTRAL                                                                                                      TOP COURSE COGGED DOWN 300 INTO
                                                     DRILL & EPOXY INTO CONCRETE WALL
                                                     (150 MIN. EMBED.)
                                                                                                                                                                                   CORES EACH SIDE OF OPENING OR
                                                                                                                                                                                   EXTEND 600 MIN. BEYOND
                                                                                                                                                                                                                                                 BLOCK LINTEL WITHOUT SLAB                                                                       BLOCK LINTEL WITH SLAB
                                                                                                                                                                                                                                                                 TYPICAL 150/200 SERIES BLOCK LINTEL (BL) DETAILS
                                                                                               SLAB




                                                                                                                                                                                                                                                                 SCALE 1:20
                                                                                                                                                                                   N12-400 'J' BARS VERT.
                                                                                               BLOCK LINTEL




                                                                                                                                                                                   CONTINUATION OF BLOCK WALL
                    REINFORCED                     500                                                                                                                             BEYOND REINFORCEMENT
                     CONCRETE
                                                                                                                                            900 LAP




                       WALL

                                                                                                                                                                                   N12-400 'J' BARS VERT.


                                    50               BLOCK LINTEL BOTTOM BAR
                                   MIN.
                                                                                                                                                                                   1/N16 COGGED DOWN 300                     WALL BE
                                                     PROVIDE 50 MIN. REBATE IN
                                                     CONCRETE WALL LOCAL TO                                                                                                        INTO CORES EACH SIDE
                                                     BLOCK LINTEL                                                                                                                  OF OPENING OR EXTEND
                                                                                                                                                                                   600 MIN. BEYOND
                                                                                                                     WALL BEYOND




      TYPICAL BLOCK LINTEL (BL) TO    TYPICAL BLOCK LINTEL (BL)
      CONCRETE WALL CONNECTION DETAIL GREATER THAN 1200 DEEP
      SCALE 1 : 20
                                                                                                                     SCALE 1 : 20


C1    ##.##.####   REVISION NAME                                                                                                                                                                                BRISBANE
                                                                                  DESIGNED:                   APPROVED:
                                                                                                                                                                                                           T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                           PROJECT NUMBER
                                                                                                                                                                                                                              CONSULTANTS NAME                                                                                                                                                          S24-###
                                                                                                                                                                  WE S TE R A
                                                                                                                                                                                                             GOLD COAST
                                                                                  DRAWN:
                                                                                                                                                                                                           T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                                         SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                                     SHEET NUMBER
                                                                                  CHECKED:
                                                                                                                                                                  PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                                          NORTHERN NSW
                                                                                                                                                                                                                             USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                                             PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                                 TITLE:    BLOCK WALL DETAILS
                                                                                                                                                                                                                                                                                                                                                                                                          2.2
                                                                                                                                                                                                                                                                                                                                                                                                           .
                                                                                  DATE:                                                           STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                   DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                                           T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                                        CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                                           CLIENT NAME                                                                           ##
                                                                                                                                                                                                                             STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                  PAGE SIZE:            A3    For and on behalf of                    www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                                             CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                             REVISION
No.    DATE        REVISIONS                                          DRN   ENG                               WESTERA PARTNERS PTY. LTD.                                                                   T: 03 5441 0922

Section 12

                                                                                                                                                                           TOP REINFORCEMENT IN SLAB.
                                                                                                                                                                           REFER BLOCK LINTEL SCHEDULE                                                                                                                              R16 DOWELS x600 LONG (GALV.)            BLOCK LIN
                                                                                            SUSPENDED SLAB                                                                 AND ELEVATION FOR DETAILS.                                                                                                                               GREASED & TAPE ONE END AS               SCALE 1 : 20
                                                                                            REFER SLAB PLAN                                                                                                                                                                                                                         SHOWN. PROVIDE AT EACH
   TOP REO IN KNOCKOUT TOP COURSE                               INDICATIVE ROOF TIE                                                                                                                                                                                                                                                 HORIZONTAL BAR LOCATION
   REFER BLOCK LINTEL SCHEDULE                                  DOWN OR FIXING                                                                                                                                                                                                                                                      AND LAP AT TOP OR WALL (LAP 500)
   AND ELEVATION FOR DETAILS.                                   WHERE APPLICABLE.
                                                                                                                                                                               TOP REO IN KNOCKOUT TOP COURSE
                                                                                                                                                                               REFER BLOCK LINTEL SCHEDULE
                                                                                                                                                                               AND ELEVATION FOR DETAILS.
                                                                                                                                                                                                                                                                                                                                                                                LIGS
                                                                 HORIZONTAL REO (REFER                                                                                                                                                                                                                                                                                          REFER SCHEDULE
                                                                                                                                                                               HORIZONTAL REO (REFER
OTE:                                                             BLOCK LINTEL SCHEDULE)
                                          'D'




                                                                                                                                        'D'
                                                                                                                                                                               BLOCK LINTEL SCHEDULE)
NING WIDTHS AND
OORDINATED ON                                                    LIGS OVER OPENING                                                                                                                                                                                                                                 300 MIN COG
                                                                                                                                                                               LIGS OVER OPENING (REFER                                                                                                                                                                       HORIZ. REO
BASIS AND                                                        (REFER BLOCK LINTEL
                                                                                                                                                                               BLOCK LINTEL SCHEDULE).                                                                                                                                                                        REFER SCHEDULE
                                                                 SCHEDULE)
T ADJUSTED AS
                                                                 BOTTOM REO, REFER
                                     75 TO BTM                                                                                   75 TO BTM                                      BOTTOM REO, REFER BLOCK
                                                                 BLOCK LINTEL SCHEDULE
                                     OF BAR                                                                                      OF BAR                                         LINTEL SCHEDULE AND                                                                                                                                      10mm COMPRESSIBLE JOINT       BOTTOM REO.
                                                                 AND ELEVATION FOR DETAILS
                                                                                                                                      WALL BEYOND                               ELEVATION FOR DETAILS                                                                                                                                    FILLER WITH APPROVED FIRE     REFER SCHEDULE
                                     WALL BEYOND
                                                                                                                                                                                                                                                                                                                                         RATED/WATERPROOF FLEXIBLE
                                                                                                                                                                                                                                                                                                                                         SEALANT.

                                     BLOCK LINTEL WITHOUT SLAB                                                               BLOCK LINTEL WITH SLAB                                                                                                                                                                                                 OPENING


                                                   TYPICAL 300 SERIES BLOCK LINTEL (BL) DETAILS                                                                                                                                                                                                                                        NOTE:
                                                                                                                                                                                                                                                                                                                                       WALL REINFORCMENT NOT SHOWN FOR
                                                   SCALE 1:20                                                                                                                                                                                                                                                                          CLARITY. REFER BLOCK WALL SCHEDULE
                                                                                                                                                                                                                                                                                                                                       AND DETAILS AS APPLICABLE
                                       300 SERIES BLOCK LINTEL SCHEDULE                                                 (UNLESS DETAILED OTHERWISE)

                                           'D'      SPAN             BOTTOM REO              TOP REO
                                                                                        (WHERE APPLICABLE)
                                                                                                                     HORIZONTAL REO                           LIGS
                                                                                                                                                                                                                                                                                         TYPICAL BLOCK LINTEL CONTROL JOINT
                                                                                                                                                                                                                                                                                           SCALE         1 : 20
                                        290 MIN    1200 MAX.             2/N16                  2/N16                          N12-400              R10-400 EACH FACE

                                        390 MIN    2400 MAX.             2/N16                  2/N16                          N12-400              R10-400 EACH FACE

                                        490 MIN    3500 MAX.             2/N16                  2/N16                       2/N12-400               R10-200 EACH FACE

                                        790 MIN    4500 MAX.             2/N20                  2/N20                       2/N12-400               N12-200 EACH FACE




  C1    ##.##.####   REVISION NAME                                                                                                                                                                      BRISBANE
                                                                                       DESIGNED:         APPROVED:
                                                                                                                                                                                                   T: 07 3852 4333    CONSULTANTS:                                                                       PROJECT: PROPOSED RESIDENTIAL DEVELOPMENT                                         PROJECT NUMBER
                                                                                                                                                                                                                      CONSULTANTS NAME                                                                                                                                                        S24-###
                                                                                                                                                          WE S TE R A
                                                                                                                                                                                                     GOLD COAST
                                                                                       DRAWN:
                                                                                                                                                                                                   T: 07 5571 1599                                                                                       LOCATION: PROJECT LOCATION
                                                                                                                                                                                                 SUNSHINE COAST
                                                                                                                                                                                                                                                                                                                                                                                           SHEET NUMBER
                                                                                       CHECKED:
                                                                                                                                                          PART NE RS                               T: 07 5391 3777
                                                                                                                                                                                                  NORTHERN NSW
                                                                                                                                                                                                                     USE FIGURED DIMENSIONS ONLY. DO NOT SCALE, IF A DISCREPANCY ARISES CHECK WITH THE
                                                                                                                                                                                                                     PROJECT ENGINEER AND/OR SUPERVISING AUTHORITY. DO NOT WORK FROM REDUCED SCALE
                                                                                                                                                                                                                                                                                                         TITLE:       BLOCK WALL DETAILS
                                                                                                                                                                                                                                                                                                                                                                                                2.3
                                                                                                                                                                                                                                                                                                                                                                                                 .
                                                                                       DATE:                                              STRUCTURAL+CIVIL+ENVIRONMENTAL ENGINEERS                                   DRAWINGS (A1-A3 SIZE PAPER). COPYRIGHT OF ALL DRAWINGS & WORKS EXECUTED FROM
                                                                                                                                                                                                   T: 02 6674 8047   THEM IS VESTED IN WESTERA PARTNERS AND USE OF THERE FORE WITHOUT PERMISSION IS
                                                                                                                                                                                                CENTRAL VICTORIA
                                                                                                                                                                                                                                                                                                                      CLIENT NAME                                                                     ##
                                                                                                                                                                                                                     STRICTLY PROHIBITED! IT IS THE BUILDERS RESPONSIBILITY TO ENSURE ALL WORKS ARE
                                                                                       PAGE SIZE:   A3   For and on behalf of                 www.westerapartners.com.au   ABN 52 097 417 975
                                                                                                                                                                                                                     CARRIED OUT WITHCARE AND DUE DILIGENCE TO COMPLY WITH THE CONTRACT DOCUMENTS.       CLIENT:                                                                           REVISION
  No.    DATE        REVISIONS                                             DRN   ENG                     WESTERA PARTNERS PTY. LTD.                                                                T: 03 5441 0922

The text continues on section 13.