For the Jellyfish® system a major service is a reactionary
process based on the outcomes from the minor service.

Rinsing does not remove accumulated Replace Jellyfish®
sediment from the tentacles tentacles!

io h®

Jellyfish® tentacles are damaged Bees E ey

tentacles!

Jellyfish® cartridges have been in
operation for 5 years

Replace Jellyfish®
tentacles!

 

i Replacement filter tentacles and components are available for
purchase from Ocean Protect

This service is designed to return the Jellyfish® device
back to optimal operating performance.

Establish a safe working area around the access point
Remove access covers

Using a vacuum unit or net remove any floatable
gross pollutants contained behind the maintenance
access wall

Using a vacuum unit decant the water until the level
drops below the base of the cartridges

S oo8

Remove Jellyfish® cartridges*

o

a. Remove cartridge lid
b. Remove cartridges vertically from chamber,
lifting from eye nut lifting points only

c. Replace and secure cartridge lid back into deck
to reduce trip hazards during maintenance

Unscrew all 11 tentacles from the cartridge head
plate for disposal, keep all components for fixing of
new tentacles to existing head plate*

Wash down deck level to remove any built up
sediment (if required)

o oo

Use vacuum unit to remove accumulated sediment
and pollutants in the chamber

Install replacement tentacles into each head plate*

8G 8

Install Jellyfish® cartridges
a. Remove cartridge lid

b. Lower cartridge into chamber, lifting from eye
nut lifting points only

c. Insert cartridge vertically into cartridge
receptacle, and secure cartridge lid back in place

a Replace access covers

© OCEAN

PROTECT

The standard maintenance approach is designed to
work towards keeping the Jellyfish® system operational
during normal conditions. From time to time, events

on site can make it necessary to perform additional
maintenance to ensure the continuing performance of
the device.

Hazardous Material Spill

If there is a spill event on site, the Jellyfish® unit should
be inspected and serviced accordingly. Specifically,

all captured pollutants and liquids from within the unit
should be removed and disposed in accordance with any
additional requirements that may relate to the type of spill
event. Additionally, it will be necessary to inspect the filter
cartridges and assess their contamination, depending on
the type of spill event it may be necessary to replace the
filtration cartridges.

Blockages

The Jellyfish® treatment system is designed to operate
in an offline arrangement, where an upstream high
flow bypass structure is in used. In the unlikely event
that flooding occurs upstream of the Jellyfish® system,
the following steps should be undertaken to assist in
diagnosing the issue and determining the appropriate
response.

a Inspect the upstream diversion structure to ensure
that it is free of debris and pollutants

Inspect the Jellyfish® unit checking both the inlet
and outlet pipes for obstructions (e.g. pollutant
build-up, blockage), which if present, should be
removed

Major Storms and Flooding

In addition to the scheduled activities, it is important to
inspect the condition of the Jellyfish® after a major storm
event. The focus is to inspect for damage and higher
than normal sediment accumulation that may result
from localised erosion. Where necessary, damaged
components should be replaced and accumulated
pollutants should be removed and disposed.

“Refer Appendix 1 for Jellyfish® Cartridge Schematic

~“

93

Used in these records

About this file

File size
21.6 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Judgment - Stockwell v Noosa Council - PEC Appeal 1998 of 2024 - 26.06.25.pdf · 21.6 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.