Original source · versioned page text
Appendix B - Acoustic Report
Attached to the e-mail PM Submission - Wayne Simmiss - 51995.1611.04.
Your Mates Bowlsy Pty Ltd Reference: #1859d1-B
Your Mates Bowls Pub Date: 6 March 2025
Noise Impact Assessment
2025 to determine the existing noise impacts. Noise measurements were taken using a Nor139
sound level meter at the locations illustrated in the figure below. Noise survey instrumentation
information is provided in Table 3.
A
B C
Measurement Location
Figure 5. Attended measurement locations of mechanical plant noise
Measured noise levels from the mechanical plant assessment are presented below.
Table 8. Measured mechanical plant noise levels
Meas. Description / Duration Level, dBA
Comments
No. Location (min:sec) Leq L90 Lmin
Location A –
Directly below
Plant noise clearly audible. Continuous
1 rooftop mechanical 1:00 57 57 56
noise source.
plant, 3m from the
noise source
Location B –
Plant noise clearly audible. Continuous
2 1m from Patton 1:00 68 68 68
noise source.
refrigeration unit
Location C – At the
Noise from refrigeration plant and kitchen
eastern boundary of
3 1:00 58 58 58 exhaust fan audible. Continuous noise
the site, adjacent to
source.
11 Opal Street
Live It Acoustics Page 13