                                1 April 2014                                                                                REF: 9517



                                Noosa Shire Council
                                PO Box 141
                                Tewantin
                                Qld. 4565
Robin                           Attention: Subdivisions Engineer
Russell
& ASSOCIATES PlY. LID.
  ABN 78010589661               Dear Sir,

                                                      GATEWAY RISE - NOOSAVILLE                - STAGE 1

                                We have been engaged as Consulting Electrical Engineer for the design of
                                electricity reticulation and street lighting on the above subdivision. Details of the
                                subdivision are contained on the Subdivision Details Sheet enclosed.

                                A copy of our final Works Plan is enclosed herewith for your approval, subject to
                                Energex's approval also. We would appreciate it if you would advise us as follows:

                                  i.    Approval of alignments specified on the enclosed plan, for poles, street lighting
                                        columns and underground cables:
                                  ii.   approval to use "as constructed" levels as permanent levels;
                                 iii.   formal approval of the works proposed on Council-controlled road, as required by the
                                        Electricity Act 1994, 5.102;
                                 iv.    formal approval of the street lighting design;
                                  v.    confirmation that the electricity reticulation and street lighting, as designed, satisfies
                                        the requirements of Council's development approval for this subdivision.

                                Our cheque for Council's lodgement fee is enclosed.            Please send your tax invoice
                                within 28 days.

                                Thank you for this assistance.




     {O rZL:. ~
      CERTIFIED
      QUALITY
                                Yours faithfully,
                                ROBIN RUSSELL & ASSOCIATES PTY. LTO.




     _
      1II~ItAaHIE"'T
             "OJOU-
                       SUTEIf
                                Robin Russell
                                (RPEQ 1546)

     RobinRussell
    BE. BCom. FlU-I. CPEng
           RPEO 1S4e
                                Encl:   Works Plan
     Consulting                         Subdivision Detaifs Sheet
 ElectricalEngineers                    IDAS form 1 & 6
       Subdivision                      Cheque $693
    Electrical Services
 204/6 Babarra SI. Stafford
 Queensland 4053 Australia
        Head Office
    Ph (07)3872 5555
    Fax (07) 3872 5566
      Sunshine Coast
     Ph (07) 5442 1758
              Email
     rrOrobrus.com.au
    www.robrus.com.au
                                                                                                         33.Certified Sl Design for Approval.docx
Full text of the other 3 pages

Page 2

 

 

 

  
 
 
 
 

Lot 10

 

 

 

 

ey,
Lot 8
wy, %,
ey
(o)*
Lot7 ®

Lot 6

 

 

AT SC1389563 - LIVE 11kV/LV
AND SERVICES. FAND EXCAVATE.

RESTORE SITE WFEN COMPLETED.

DANGER

 

ONLY AT THIS LOCATION.

 

USE BARRIER AND SIGNS.

 

  

 
  

 

 

 

 

 
 

 

DEVELOPERS SURVEYOR

1.

- NOTES

PROPOSED LOT 17 - S.E. CORNER NEXT TO

THE DRAINAGE RESERVE IS TO HAVE A MINIMIUM
2m x 2m TRUNCATION TO ALLOW FOR THE
INSTALLATION OF ELECTRICAL SERVICE PILLAR
CLEAR OF SWWATER AND S/WATER PITS.

THE TRUNCATED PROPERTY BOUNDARY LINE
OF VENTURE DRIVE AND PROJECT AVENUE IS
TO BE STAKED FOR NEW ELECTRICAL WORKS

 

INSTALLATION OF BORED CONDUITS

TO COMPLY WITH THE ELECTRICAL SAFETY ACT, BORED
CONDUITS SHALL BE INSTALLED AT A MINIMUM DEPTH

OF 900mm. AT EACH END, WHERE THE CONDUIT RISES
TOA DEPTH OF LESS THAN 900mm, A TRENCH SHALL

BE EXCAVATED AND PROTECTIVE COVERS AND MARKER
TAPE SHALL BE LAID ABOVE THE CONDUIT.

TO BE INSTALLED.

 

 
 

 

TUNNEL BORING SHALL BE REQUIRED AT
STN'S 248-28.

 

 

 

 

 

 

 

 

 

 

 

TELSTRA - NOTE

RELOCATION WORKS REQUIRED.
PROPOSED TO MOVE SMALL PIT TO
ALLOW FOR ELECTRICAL WORKS IN
FRONT OF PADMOUNT SC21257

 

 
 
 

    

 
    
    

 

 

 

 

DANGER

IN VENTURE DRIVE, EXISTING
MAJOR SERVICES IN ALL LOCATIONS.
CONFIRM AND POT HOLE BEFORE EXCAVATING.

 

  

DETAIL 'A'- SH

 
 
  

  

 

 

 

DRAINAGE
RESERVE

  

REINSTATE VERGE &
LANDSCAPE AS REQUIRED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
  
 
  

 

   

 

 
 
 

ELECTRICAL CONTRACTOR

The works detailed on this drawing shall be constructed in accordance with Robin Russell & Associates’
General Specification for Installation of Electricity Reticulation and Street Lighting - Issue ‘Y’.

CIVIL CONTRACTOR

The installation of all electrical conduits shall be supervised by the holder of an electrical work licence
- Electrical Safety Act 2002.
Energex conduits and transformer site retaining walls shalt be installed strictly in accordance with
Energex's specifications (see below). They will be inspected for compliance upon completion.
The civil contractor shail install enveloping conduits under retaining walls behind pillars - two 100mm
Conduits into each lot (one for Electricity, one for Tetstra), 600mm deep behind the pillar, near ground
level inside the lot
Relevant specifications in Energex's Underground Distribution Construction Manual are found at -
Section C1: Conduits
Section C2: Excavation
Section C3: Transformer Sites
These sections of the manual can be downloaded from the following Energex web site:
hitp:/Awww.energex.com.au/about_energex/asp/echnical_documents. asp
Civil engineers who have registered for access to the following RRA website may download extracts
from Energex's manual at
ittp-/Awww. robrus.com.au
The civil contractor shall ensure that all conduits have been installed before constructing retaining
wails, paths, driveways & water services. The civil contractor shall please inform the electrical
contractor of any ‘as constructed" departures from the civil design.

 

 

Care! Lighting of new or altered existing roads might not comply with specified standards
until new road lighting has been commissioned. The civil contractor shail ensure that
Necessary warming signs are installed and speed restrictions are applied if necessary.

 

 

 

 

 

 

 

 
  
  

   

 

 

 

 

 

 

 

  

 

 

 

   

 

 

 

 

  
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

ON-SITE SERVICES CHECKS

Robin Russell & Associates gives no warranty regarding the presence or location of buried services,
including newly-installed services. "As Constructed” locations may differ from what is drawn on this
works plan. Contractors shall be responsible to identify and locate all buried services. Initial
identification can be obtained from:

Dial Before You Dig Service

Telephone 1100

Fax 1300 652 077

On-line enquiries can be made at:

http:/Awww.1100.com.au.
Having determined which services may be present, on-site locations should then be arranged with
relevant service authorities.
Sewerage and water plans for the subdivision may be obtained on request from the Superintendent.

INSTALLATION OF TELECOMMUNICATIONS CONDUITS BY TELSTRA

Telstra's contractor will install telecommunications conduits in shared trenches and other excavations
provided oy the electrica: contractor. in commercial subd visions. or where more than 2xP 100 conauits
are required the conduits may not be instalied aove Energex conduits. They shall be laid in a
separate trench on the standara communications alignment specified
Contractors shail novfy Telstra's contractor

* one week before road crossing trenches will be open

* — two days before footpath trenches will be cpen
Teistra’s contractors are

south of Brisbane River Silcar Communications

 

LEGEND: ELECTRICAL

 

—-—— EXISTING UNDERGROUND CABLE
PROPOSED UNDERGROUND CABLE
PROPOSED NBN CONDUIT ON COMMS ALIGNMENT
COMMS CONDUIT IN SHARED TRENCH
BORED CONDUIT

GAS IN SHARED TRENCH

STATION NUMBER

PADMOUNT TRANSFORMER

PROPOSED POLE TRANSFORMER

METER BOX/ LV SWITCHBOARD

PROPOSED SERVICE PILLAR

EXISTING SERVICE PILLAR

FUTURE SERVICE PILLAR

EXISTING LINK PILLAR

PROPOSED C&i PILLAR

EXISTING OVERHEAD ELECTRICITY MAINS
PROPOSED OVERHEAD ELECTRICITY MAINS
HV POLE

HV +LV POLE

LV or STREET LIGHT POLE

PROPOSED STREET LIGHT

EXISTING STREET LIGHT

FUTURE UNDERGROUND STREET LIGHT
RECOVER STREET LIGHT

EARTH

EXISTING RATE 3 STREETLIGHT CABLE
PROPOSED RATE 3 STREETLIGHT CABLE
EXISTING RATE 3 STREET LIGHT
PROPOSED RATE 3 STREET LIGHT
EXISTING CONSUMERS OVERHEAD CABLE
PROPOSED CONSUMERS OVERHEAD CABLE
EXISTING CONSUMERS UNDERGROUND CABLE
PROPOSED CONSUMERS UNDERGROUND CABLE
Lg PROPOSED CONSUMERS SWITCHBOARD

o EXISTING CABLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lot 12 elsewhere Service Stream Commun cations PROPOSED CABLE
e
I
| ) BIKE PATH CLEARANCES o 340mm HD CONDUIT
MOLY * . . . . " . 5 woe
¢ Xs} Lot 201 Lot 16 ‘Austroads Guide to Road Design Part 6A: Pedestrian & Cyclist Paths" specifies a minimum
REINSTATE VERGE AS | | Lot 14 / . clearance of 0.5m between a bike path and any obstacle. in order to achieve specified road © 80/100mm LD CONDUIT
REQUIRED CAUTION 4 Ooo” ots \ I path lighting within the specified verge, it has nat been possible to satisfy that requirement. © 100mm WHITE ENERGEX COMMS. CONDUIT
RECOVER LIVE LV END. / ] Lot 10 @® 125mm LD CONDUIT
eee tot TREE PROTECTION ZONES TREE PROTECTION ZONE (TPZ) @ _CABLEMARKER POST
Oo I . . . .
unwed Lot 22 The Electrical Contractor must avoid any trenching, boring, p A _""ENERGEX ELECTRIC CABLE" MARKER PLATE
9 35 01004619 Lot 12 or disturbance of earth inside any area covered by a 4 2
& O0e™™ Tree Protection Zone (TPZ) within the extent of works for this foo
H T project Any exceptions ‘e ts must be approved wing by \ UNDERGROUND CABLE CERTIFICATION
R le projects’ Tree Arborist or Landscape Architect and in . i
B C Xe Conjunction with all Local Authority's development approvals. All cables detailed on this drawing have been checked using the
y FUTURE STAGE 2 Lot 10 ©; cable locator described below and are, according to measurements
R zai SNe Refer AS 4970-2009 ‘Protection of Trees on Development Sites' taken, on the correct alignment and at correct depths below the
H / Lot 24 finished level, except as marked up. Alignments are subject to the
4 / NOTES accuracy of survey pegs present at the time of measurement.
/ 4. DANGER - EXISTING MAJOR TELSTRA AND SERVICE IN ALL AREAS.
LOT1 CHECK ALL SERVICES ONSITE AND HAND LOCATE AND IDENTIFY. Make: Model:
U71345 2. EXTRA WIDTH AND DEPTH TRENCHING MAY BE REQUIRED TO ACCOMMODATE Serial No: Date Cables Checked’)
‘ TELSTRA CONDUITS - LOCATIONS SUBJECT TO CONFIRMATION BY TELSTRA. Name of Person Who Conducted Checks
3. ALTERATIONS TO EXISTING SERVICES - NOTIFY CUSTOMERS OF PROPOSED ame oF rerson Wvno Wonducte! Ss:
Lot 8 5.0m DATE/TIME OF INTERRUPTION TO SUPPLY. Certified (signature of checker):
foe 6.0m
4, NOTE - SOME NON STANDARD ALIGNMENT AND BORED CONDUIT REQUIRED Phone No. of checker:
ON VENTURE DRIVE TO AVOID EXISTING SERVICES, LV CABLES AND VEGETATION.
& e 5. TELSTRA TO BE ON A SEPARATE ALIGNMENT. ROAD LIGHTING CERTIFICATE
tk ROCK WALL ON BOUNDARY a < NO JOINT USE SERVICES TRENCH IN COMMERCIAL/INDUSTRIAL SUBDIVISIONS. Within the bounds ofthis tis ood lghting design is certied to
Oo oS estate, certified
+ 6. DEVELOPERS SURVEYOR TO STAKE LOCATIONS AS PER NOTES ON MAIN PLAN. comply generally with the nominated categories of AS1158.1-1986,
s ASINZS1158.1.1:2005 and/or AS/NZS1158.3.1:2005 for luminaires
z & 7. PROPOSED RING MAIN UNIT LOCATION. :
3 i REFER TO NOTES ON PLANS AND SCHEDULES. and lamps supplied under Energex contract C10227.
2 VENTURE DRIVE EXTENSION AND VISION COURT -
TELSTRA - NOTE nerves
L -
SEPERATE TRENCHING IS REQUIRED
FOR TELSTRA CONCUITS IN
COMMERCIAL INDUSTRIAL SUBDIVISIONS ROAD LIGHTING MAINTENANCE SCHEDULE
This design assumes maintenance factors of 0.7 for minor road
LOT 2 lighting and 0.75 for major road lighting. These maintenance factors
are based on the following nominal maintenance schedule, which
might not necessarily be adopted by Energex.
1. Lamps shail be replaced at 36-month intervals.
CONSTRUCTION CONTACTS . ep ‘ .
Transformer site to be constructed by the Electrical Contractor, for new square series. TELECOMMUNICATIONS INFRASTRUCTURE 2. Atthat fime, luminaires shall be cleaned, inspected & maintained.
ELECTRICAL ENGINEER PLAN VIEW -20m 0 20 40 60m For all construction details refer to Energex Underground Distribution Construction Manual - Section 4. 3. Vegetation shall be kept clear of streetlights 7
ROBIN RUSSELL & ASSOCIATES PTY LTD SCALE 1-100 a The Electrical Contractor shall arrange for a soil compaction (est to be cartied out on the transformer site and CONDUITS & PITS | to be designed by: Telstra's contractor 4. Inspection patrols and spot lamp replacement shall maintain
DESIGNER : 1 1000 (At - NOT REDUCED) provide Robin Russell and Associates with a written report of the results. If the result is: to be installed by: Telstra's contractor service availabilty at not less than 95%. ;
ANTHONY HOBBS ph: 0499 999515 : greater than 50 kPa then a concrete base stab shall be supplied and installed by the Electrical Contractor. to be owned by: 5. Luminaires and lamps shalt be replaced with exact equivalents.
CONSTRUCTION MANAGER . less than ‘ot kPa then the Becta Contractor shall provide a pier foundation in line with the Energex TELECOMMUNICATIONS INFRASTRUCTURE to be provided by: ¢el Ss tr a
ground Construction Manual. a LZ . y
SHANE HYDE pit 0419 021772 The Civil Engineer and Civil Contractor shall ensure the site is level & prepared with retaining walls (required) & = [fT eteesssnnsnonteet ttrranttinsettvnss teens
CIVIL ENGINEER safety fence (if required) in line with the requirements of the Energex Underground Distribution Construction Manual . Telstra AFR: - Robin Russell RPEQ 1546
TOD NOOSA CONSULTING ENGINEERS
— SOURCE DOCUMENTS SITE INFORMATION
SURVEYOR
TOTAL NUMBER OF LOTS
MURRAY & ASSOCIATES PTY LTD PROPOSED $C2069511 ( STN 2) - VISION COURT CREATOR DRAWING DWG. NO. REV. NO. | DATE o
JOHN CAMPBELL ph: 5441 2188 SCALE 1:200 (AT Al SIZE) TOD NOOSA CONSULTING ENGINEERS | PROPOSED WATER 06583/21 W 26/3/2008 ERTY DESCRIPTION
TELSTRA CONTRACTOR TOD NOOSA CONSULTING ENGINEERS | BASE ACAD..06583 EMAR T7ER2014 LOTS 1, 9-17 cancelling P/O LOT 81 ON SP211687
GM TOD NOOSA CONSULTING ENGINEERS | ROADWORKS & DRAINAGE | - 6583-54 1773/2014
BOB TANNER ph: 0477 708028
DATE | REV | REVISION APP. | DATE | REV | REVISION APP. | CURRENT REVISION CHANGES: i RC TION SWP47.1 DESIGNED D. BUCKENHAM DESCRIPTION LOCATION DRAWING No.
s SUBDIVISION ELECTRICAL SERVICES
12608 | A _| ORIGINAL ISSUE RR Robin ZAG tre et wave, [COUN | SCRE. DRAWN —_| N OWENS ELECTRICITY RETICULATION GATEWAY RISE - NOOSAVILLE STAGE 1 -
26.6.08 APPROVED RR. + 0 4058 4 ‘ ROBIN RUSSELL NOOSAVI LLE
R u Ss se | | Tet (07) 3672 5555 3 COUNCIL REF | 2007/1626 APPROVED BY | poco 1546
25.3.14 c FOR TENDER RR. Fax (07) 3672 5566 . - CUENT ENERGEX PROJECT No. SHEET No.
& ASSOCIATES PTY. LTD. Ema r@vobrus com au ceateriee UBD REF Me Gd Gye VV
CONSULTING ENGINEERS - ELECTRICAL ABN. 78.010 589 661 “ en * = GATEWAY RISE PTY LTD THIS DOCUMENT IS COPYRIGHT AND THE PROPERTY OF ROBIN RUSSELL & ASSOCIATES PTY LTD $01 04679 1 OF 3
. DWT REV V26 - 20140225 DATE 25/03/2014 AND MUST NOT BE RETAINED, COPIED OR USED WITHOUT AUTHORITY. A1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 3

 

 

 

 

DANGER - STN 29

REFER TO PREVIOUS PROJECT No. C0054045.
HAND EXCAVATE EXISTING EARTH PIT LOCATION
TO LOCATE AND IDENTIFY ALL CONDUITS, CABLES
AND EXISTING SERVICES. SAW CUT EXISTING
DRIVEWAY IF REQUIRED AFTER LOCATION OF SERVICES.
INSTALL 71kV CABLE IN SPARE CONDUIT.
RESTORE THIS SITE TO EXISTING CONDITION
ON COMPLETION CF ALL WORKS.
USE BARRIERS AND SIGNS AT ALL TIMES

 

 

 

 

DANGER

AT $C21257 AND PROPOSED R.M.U. HAND
EXCAVATE AND LOCATE ALL CONDUITS AND CABLES.
LOCATE AND INSTALL THE R.M.U. TO SUIT ALL
EXISTING SERVICES.

PREVIOUS XVISION COURTIiKV CONDUITS ETC
INSTALLED ON PROJECT No. C0054045.

 

 

 

 

 

 

 

 

 

 
  
 
 
 
 
 
   
 
 
  

240 LV

© ‘ ee Bout)

    
   
  

 

 

 

 

/ Bett)
] Uo im GOS wou
e DRNE / O* \
yen™ 1S. @ Ze \
/ a gh ur1336
/ a”
/ oe O L TN
eed —\O p> -=See we Qon
a _ ~ ~ Om”
_ “2 _ 7 ~~ ~ SN of Rey,
a-7 _ SS
_ Fae” REINSTATE VERGE & a \
@™y LANDSCAPING AS REQUIRED \ \
~ SS
‘“ N
“ X
N
N
\
N
SC754851
J
DETAIL ‘A’
(SCALE 1:500)

DATE | REV | REVISION APP. | DATE | REV | REVISION APP. | CURRENT REVISION CHANGES:
12608 | A _| ORIGINAL ISSUE RR
26.6.08 APPROVED RR
25.3.14 FOR TENDER RR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
    

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

LABELS NOTE AT SC1389563 (STN 1) - GATEWAY DRIVE
CONTRACTOR TO SUPPLY ALL LABELS TO ENERGEX SPECIFICATION ALL EXISTING LABEL INFORMATION & CABLE DESTINATIONS AT $C21257 ORT “ en eee LABEL INFORMATION
& SC741343 TO BE CONFIRMED PRIOR TO ORDERING NEW LABELS.
mar | nas | we | 6 TRANSFORMER
AT SC1389563 (STN 1) - GATEWAY DRIVE AT X2069512 (STN 30) - VENTURE DRIVE 'SOLATOR ISOLATOR
LABEL LABEL LETTER] LABEL LABEL LABEL LABEL LETTER: LABEL LABEL
sie _| covour | sve LABEL INFORMATION lLocaTion| DESCRIPTION size __{cotour} size LABEL INFORMATION LOCATION] DESCRIPTION + | ees} wel s EXISTING
NEAR ISOLATOR:
15040 WB 20 FRONT IDENTCATION 100x40 | WB} 15 1S70 IS71 IS72 1S73 ISOLATOR IDENTIFICATION
DESIGN ‘OR
5020 |BLUEW) 10 FRONT | IDENTIFICATION 150x40 | wB | 20 FRONT DEnTInCenON 2 wel s EXISTING
EAR iSOLATOR
tooo | we | 15 1S15 SF17 1S16 a To i TOOFF
eee 150x50 | ew} 10 | VISIONCOURT | VENTUREDRIVE | VENTURE DRIVE SPARE oa fee
15040 | Bw | 20 FRONT | pernrigarion 02069511 S60} SC21257 1825 SC754851 1S30 BOK | DESTIN 3 feos | wel s EXISTING
70 TO TO TO OFF woe [oa
VISION COURT CABLE CABLE 150x50 | Bw | 10 VISION COURT VENTURE DRIVE VENTURE DRIVE SPARE SIDE
wes | ow | 02060511 Is61_| 80% | DESTINATION $C2069511 1860 $C21257 1825 $C754851 1S30 way | DESTINATION TO GATEWAY DRIVE
TO Si FIT NEW FIT NEW FIT NEW 4 | 835 | WB | 8 ear eT (FT NEW)
INSIDE
150x50 | BW | 10 WSION COURT Sie | eon AND SERVICES LVTIE
$C2069511 S61. | WALL MATERIAL: GRAVOPLY II (1.5mm) or similar
EXISTING EXISTING FIT NEW
AT LP2171827 (STN 21)
AT SC2069511 (STN 2) - VISION COURT oo Lamel ea LABEL INFORMATION
GT ee OTL AT SC21257 (STN 31) - VENTURE DRIVE
size__| cocour | swe LABEL_INFORMATION LOCATION] DESCRIPTION GIRCUIT | LABEL] LABEL [LETTER LABEL INFORMATION TO GATEWAY DRIVE
PMO No. | size_{coLouR Sze 150x50| we | 5 $C1389563 FIT NEW
150x40 | WB 20 FRONT | iewriFicATION! AND SERVICES
7 DESIGN TNR | g0x35 | WB 6 TRANSFORMER
50x20 |BLUEW| 10 : FRONT | soeNTirIGATION ISOLATOR ISOLATOR TO VISION COURT
NEAR ISOLATOR 150x50 | WB 5 $C2069511 FIT NEW
100x40 | WB 15 IS60 SF62 $61 ISOLATOR | AND SERVICES
FEEDER 1 80x35 | WB] 5 EXISTING
me ew | a =z FO | geri AT LP2071830 (STN 25)
TO CABLE CABLE TO VENTURE ORIVE LP2071830/ TABEL | LABEL [LETTER
15050 | BW | 10 Oueere TFMR aeeend ee cox | DestIATION 2 | 0035 | we] 5 PROJECT AVENUE LP1004619 FIT NEW 2x LABELS REQD Sze _{COLOUR| Si LABEL INFORMATION
5 5 AND SERVICES TO VENTURE DRIVE $C21257 /
wwsibe 150x50} WB} 5 PROJECT AVENUE LP1004619 FIT NEW
15050 | Bw | 40 | VENTURE DRIVE THR GATEWAY DRIVE | soe | SABE AND SERVICES
X2069512 IS70 $C1389563 IS16 Ff WAL 3 | 80x35 | WB] 5 EXISTING
TO VISION COURT
FIT NEW FIT NEW FIT NEW t50x50| we | 5 $C2069511 FIT NEW
AND SERVICES
4 | 80x35 | we} 5 EXISTING
AT SC21257 (STN 31) - VENTURE DRIVE AT LP1004619 PROJECT AVENUE
eet ern we LABEL INFORMATION Location pescrpmion MATERIAL: GRAVOPLY 1l (1.5mm) or simitar EET OBER
NEAR | ISOLATOR size koLourl Sze LABEL INFORMATION
100x40 | WB | 15 IS25 SF26 1824 SOLATOR} IDENTIFICATION
Sao TO VENTURE DRIVE $C21257 /
150x40 | we | 20 FRONT | spenmiricaniON AT SC2069511 (STN 2} - VISION COURT 150x50| WB] 5 LP2071830 FIT NEW
AND SERVICES
TO CIRCUIT | LABEL [LABEL ]LETTER Fi
15050 | BW | 10 | VENTURE DRIVE TFMR ee | pesearon a ee oe LABEL INFORMATION TO PROJECT AVENUE
2069512 IS71 FMR TRANSFORMER 150x50 | WB 5 $C741343 FIT NEW
TO INSIDE ssouaTor | 80x35 | WB | 6 ISOLATOR AND SERVICES
VENTURE DRIVE TFMR CABLE
‘060 | BW | 10 X2069512 1S71 va DESTINATION TO VENTURE DRIVE
1 (eos | we | 5 LP 2071830 / U2071832 FIT NEW 2x LABELS REQD LV BOARD AT $C2069511 - STN 2
(FIT NEW) EXISTING AND SERVICES TT
TO GATEWAY DRIVE VISION COURT
2 | 90x35 | we} 5 LP2071827 / U2071825 FIT NEW 2 x LABELS REG'D
AT SC754851 - OFF VENTURE DRIVE AND SERVICES cent core cers cers
LABEL LABEL ]LETTER LABEL LABEL TO VISION COURT
SzE__oLouR| size LABEL INFORMATION LocAnon) oESRTION 3 | sos | we | s 2060513 FIT NEW 2x LABELS REQD
100x40 | WB | 15 1S30 SF32 1S31 ISOLATOR! IDENTIFICATION DIRECT 12508 3158 3158 3158
ISOLATOR
150x40 | WB | 20 FRONT | iDENTIFICATION| 4 |soa5|] wel 5
TO Wy
150x50 | Bw | 10 | VENTURE DRIVE TFMR or | DES maTON
2069512 IS72 ~ MATERIAL: GRAVOPLY Il (1.5mm) or similar seen
FIT NEW EXISTING :
$C21257 X2069512 wn ©
EX SOKA A IN.4 WAY \ $C21257
sm (C) S is RING MANN UNIT | 2071825 Y) \
W oO fh) is7 | ©) was tes
1s72 (19) 27 vy,
sn ! i ul
INSTALL 240(11) GaSe | /! 1
STRAIGHT JOINT Ra 1° ¥ om “a1 u
& w il | ou se Zee
oS > | | aX) (18) 2/6 en _f* |
= | ow gS PO DISTING
7, a7 mt) usc \s SJ £7 yatg9328 t
s VENTURE DRIVE cr
t | 1 1* 5 i) « i‘ _ I~, i $C754851
| N | I TT @ ae oT x .e) » 240LV | se 1
240AL
| mL dice TORMY. 7 1 N. (16) (sy {n \ /
Asis ~ STN 30 80754851 8 W | i / )
a*O" - rien to ne (ws -——"-’
rss (TEMPORARY GENERATOR) Te \ -—
L = LP2071827 « 2
(OP eo 3 OMe) MO ® st
f $C 1389563 z  SC2069511 ~S #
/ EX SOWA 3 _ iN. SOOKVAGCF N % SC2069511 =/|
/
! z @ NS f |
2 $C1389563 : crs a
2
{ = 3 a 8 LP 1004619
\ : w/ 8 gy Eau}
\ ca. 3 an / 15508
\ > 200A. /
\ /
TWT 134 \ /
PROPOSED COMMISSIONING PLAN
N\ CONSTRUCTION PROPOSAL REO ER UUMEROIUNING PLAN FUTURE STAGE 2
AT STN 30, CONFIRM ONSITE LOCATION CONCEPT ONLY AND SUBJECT TO CHANGE BY ~ :
FOR THE R.M.UNIT AFTER ALL SERVICES THE ENERGEX SWITCHING COORDINATOR. NN. a
HAVE BEEN LOCATED AND IDENTIFIED. OPEN 1S30 SC754851 \ FuT
5 ou INSTALL AS CLOSE AS POSSIBLE TO $C21287. & IS 25 STN 31 & INSTALL TEMPORARY GENERATOR. \ 2oAL
| INSTALL EXISTING 95(11} TO $C754851 TO THE NOTIFY CUSTOMERS OF PROPOSED SUPPLY INTERRUPTIONS. N
NEWRMU. HVILV SWITCHING AND GENERATORS REQUIRED. \ .
INSTALL 240(11) FROM $C21257 TO THE R.M.U.
| 8 INSTALL 240(11) FROM NEW P) NT STN? ENERGEX TO CONFIRM THE 11kV OPEN POINT \
| 5 hee R.M.U. FOR REQUESTED ENERGEX Nel WORKS, BETWEEN ‘ NOTE
=x .
1s 1s AT SC1369563 / CCT4 - NO CURRENT CUSTOMERS.
! 3 INSTALL 24011) FROM SC1389563 TO STN 2. | 5 INSTALL NEW 3WAY PILLAR AND LV TIE TO
| = NEW SC2069511.
| =
! 1 &
| L?
|
4 S12 Y
#0 Dou? 11kV SCHEMATIC “7
$C732430 eo LV SCHEMATIC
FERVA RRIAD SCALE 1:2500) | ene
FRA BRAD so | ( 2500) (SCALE 1:2000)
| :
\
Shecrcation | SWWP47.1 DESIGNED D.BUCKENHAM | DESCRIPTION LOCATION DRAWING No.
. SUBDIVISION ELECTRICAL SERVICES
Robin mienaminn aaa, © [COUNCL | SCRE. DRAWN __[N.OWENS ELECTRICAL SCHEMATICS GATEWAY. RISE - NOOSAVILLE STAGE1 | 9547-02C
R usse | | Tet (07 3672 665 3 COUNCIL REF | 2007/1626 APPROVED BY | ROBIN RUSSELL 00
& ASSOCIATES PTY. LTD oo noon een : Map Gad LL 2 CUENT ENERGEX PROJECT Wo. SHEET No.
covSUL Ts EMGNEERS.LECTACAL ~ 78.010 il a se = * = = GATEWAY RISE PTY LTD THIS DOCUMENT IS COPYRIGHT AND THE PROPERTY OF ROBIN RUSSELL & ASSOCIATES PTY LTD S01 04679 2 OF 3
, DWT REV V26 - 20140225 DATE 25/03/2014 AND MUST NOT BE RETAINED, COPIED OR USED WITHOUT AUTHORITY. A1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 4

 

 

 

URD CONDUIT SCHEDULE - ROADWAYS - BY CIVIL CONTRACTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EQUIPMENT SCHEDULE - TFMR , RMU & 11kV JOINT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

‘YY _X-SECTION (m) STN COMP
CONDUIT LENGTH (m) LOCATION No, | SMELD. | EX | REC] IN SIZE & DESCRIPTION iD cusc | aTy REMARKS
STATIONS PVC CABLE praw | KERB TRENCH —
LOCATION POM TO PROTECTION | EXCAV/ | TRENCH ROPE MARK REMARKS BY CIVIL GATEWAY DRIVE 1 $C1389663 | EX IN |240{11) TEMR TERMINATION 1CFCO524XLG | 1 [TO SPARE IS16
° 40mm 100mm 125mm ENERGEX (m) TAPE | DETAIL e IN |240(LV) TEMR TERMINATION LVPT4C240 1 |REFIT TOCCT4 & STN 22
Hp |N°} ip JNO} yp |No oD VENTURE DRIVE Ey] $C21257_ | Ex IN [240(11) TEMA TERMINATION 1iscTi24oT [1 [REFIT TO1S25 & NEW RMU UNIT
VISION COURT 2 | sc2060511 IN. [UNICULVERT FOUNDATION 1 |BASE SLAB REQUIRED
CRETE CAP CONDUITS IN {S00KVA TFMR CCF $21660 1
VISION COURT PMT 2) 14 2a |2|/ 24 | 2 2x24 24 N 104 OVER SW DUE TO 24.
INSUFFICIENT COVER IN’ HV. FUSE DSHVFSSLK | 1
IN |LVFUSE DSLVF31 3
VENTURE DRIVE 17 | 168A 5 1| 2 [2] 2 [eo 2x24 24 NZ 110 24 in. [11k TFMA ‘TERMINATION sorstazan | 2
24 26 29 2 29 2 2x29 116 29 iN ]LV TFMR TERMINATION LVPT 4G240 3
IN. |EARTHING COMMON pssGPoMeG | 1
TOTAL 5 154 154 154 nN 330 7 IN |EARTHING MIXTURE $ 17322 4
IN |SIGN DSRMSIGN 1
NOTES iN [CABLE PROTECTION STRIPS CIVBF 10A 6 |INSTALL OVER CABLES AT FRONT OF PMT
1. ROAD CROSSING CONDUITS SHALL BE INSTALLED STRICTLY IN ACCORDANCE WITH THE ENERGEX UNDERGROUND DISTRIBUTION CONSTRUCTION (UDC) MANUAL. VENTURE DRIVE 2a | 2069510 IN. [240(11) STRAIGHT JOINT 118T24/24% | 1 |RECORD LOCATION
2. ROAD CROSSING CONDUITS SHALL HAVE A MINIMUM COVER OF 800mm AT ALL PLACES UNDER THE ROAD, EXCEPT UNDER STATE-CONTROLLED “MAIN" ROADS, IN {CONCRETE PROTECTION SLAB 1352 1
WHERE CONDUITS SHALL HAVE A MINIMUM COVER OF 1200mm. IN| {CABLE PROTECTION STRIPS CVBF-A0A | 2
3. CONDUITS SHALL EXTEND TO WITHIN 900mm OF PROPERTY ALIGNMENT: PVC PROTECTIVE COVER STRIPS SHALL BE LAID ABOVE ALL ROAD-CROSSING CONDUITS IN_ {CABLE MARKER PLATE 1350-2 4
FOR THEIR FULL LENGTH. 30 X2069512 IN |UNICULVERT FOUNDATION 1 |REFER TO ENERGEX DRAWINGS LOST-D-CV009-05.
4. REFER ENERGEX UDC MANUAL V.5 SECT. C2 FOR CROSS-SECTION DETAILS. iN oq) rerwinaron “ ue 1CCF9524XLG REIT To: 95(11) roscreest sans
5. BRASS "E* MARKERS SHALL BE INSTALLED IN KERBS DIRECTLY ABOVE ELECTRICITY CONDUITS. in [240(11) TERMINATION iscrpmosoaxe| 2
6, CAUTION: DO NOT CONSTRUCT RETAINING WALLS, CONCRETE PATHS OR WATER SERVICES UNTIL FOOTPATH CONDUITS HAVE BEEN INSTALLED. in. [EAATHING psardcas | 4
IN [EARTHING DSRME GT 1
URD CONDUIT SCHEDULE - BORE & FOOTPATHS - BY ELECTRICAL CONTRACTOR IN |SUPPORT CHANNELS S18434 3
IN| {BOLTS $00184 6
X-SECTION (m) | IN_ [NUTS $10885 6
CONDUIT LENGTH (m) NOTE
STATIONS PVG CABLE KERB TUNNEL 4 PR
LOCATION Fi TO ENERGEX] PROTECTION | EXcAW/ | TRENCH | MARK REMARKS Bone. | TRENCH 1. PROPOSED RMU SITE ON VERGE ADJACENT TO EXISTING PADMOUNT SC21257 IS TO BE CONFIRMED ONSITE AFTER ALL SERVICES HAVE BEEN LOCATED AND HAND POT HOLED TO IDENTIFY.
10M - 40mm No 100mm No 125mm No} 100mm (m) TAPE | DETAIL | ©
i a ee ee Co EQUIPMENT SCHEDULE - SERVICE PILLARS
Ms
VISION COURT PaT2| 3A we J2| w |e 18 N 18 Q
‘“ 6 so fe) so 42 * x JOINTOXRD » LOCATION SIN | sitet EX | REC | IN SIZE AND DESCRIPTION comp cusc | ary REMARKS
15 15L 4 1 4 2 4 2 4 zZ 4 NO. ~~ 1.0.
PéT2| 24 es |2|/ 6 | 2 66 N 66 VISION COURT 3 2068513 in [2WAY, Si & MEN LVSP176 | 1 |CCT4LOT2
PILLAR TRENCH 1037-1 1 |(SA_FUSE 1043-1)
-gf position| | 1 10 10 ° 3L, 18 10 15 | 2071820 in. [2 WAY, St & MEN ivsPa6 | 1 |ccT2
1011-2 1
CONCRETE CAP CONDUITS 23 | _u2071621 IN |2WaY Lvsp176 | 1 {COT1.LOT 1
OVER SW CROSSING VERGE
VENTURE DRIVE 1SL 7 2,2) 7 2 7 N CNR OF LOT 9. APPROX. 1000mm 72 VENTURE DRIVE 16 | Up07ie22 In. 2 WAY, Si @ SL FUSE LvsP176 | 1
COVER, 1043-1 1
16 TEL 4 7 a a 5 4 17 | 2071823 IN [SWAY LVSP9-6 1
GATEWAY DRIVE i8A 18 3 7 a tole le 3 7 JOINTO.X/RD 3 GATEWAY DRIVE 18 | Us07tee4 in [2 WAY, S1 & S/L FUSE LvsPi76 ' LOT 14
18 | 19A we j2)| 7% 12 #6 N 76 79 | U2071625 iy | WAY & MEN LvsPi76 | 1 [Lot 12/13
17 | PMT 1 6 |2{ 6 | 2 60 N DANGER AT STN 1 60 1037-1 1
VENTURE DRIVE 26 26L 2a «| 1 | 28 | 2| 28 | 2 28 Z 28 20 | 2071826 IN. |2WAY LvsPi76 | 1 LOT!
26L 27 30 |2| 30 | 2 30 N 30 21 | LP2071827 In. [2 WAY LINK & MEN LVSP14-6SL | 1 |(OPEN LINKS)
BOY | 26 4 ; 4 4 ° 4 22 | 2071828 3 WAY ivaees ; AT SC1389563 CCT4 AND
DANGER LIVE LV END CAP IN IN
24 24h 1w |2| w |2 16 N VICINITY OF STN 24 16 LY TIE
NON STANDARD ON 3.0m POLE VENTURE DRIVE 24 U2071829 IN |3 WAY LVSP946 1 TOTALS
24A 25L 12 1 12 12 F ALIGNMENT. JOIN TO BORE 12 25 LP2071830 IN 2 WAY LINK & MEN LVSP14-6SL 1 (OPEN LINKS) LVSP4-6x 1
CONDUIT. 1037-1 1 jLV TIE TO SC21257 LVSP9-6x 3
25 L 4 1 a a D HAND INSTALL SA. CONDUIT a 26 | 2071831 IN. |2WAY LVSP176 | 1 |(SA FUSE 1043-1)LOT 17 Lysptaes x 2
BORE CONDUIT ON 3.an POLE 27 | 2071832 in. [tT WAY & MEN tvsPi76 | 1 Lvsei76x 8
a | 28 50 | 1 20 20 ALIGNMENT. BORE ROADWAY & | 30 20 1037-4 1 4040-1x 6
TRENCH FOOTPATHS. 24A | Uaeseez9 | EX | REC LIVE LV END CAP RECOVER CABLE BACK TO
HAND LOCATE EXISTING NEW PILLAR STN 26 fonex 4
28 28A 5 1 5 5 F CONDUIT - DANGER LIVE LV 5 1097-1x 5
JOINT AND CABLES PROTECTION BOLLARDS 1350-1 2 |ATSTN 26 1950-1x 2
VARIOS STREETS CABLE MARKER PLATES 1350-2 12 [AS SHOWN 4350-2x 12
28
ALL STREETS ul pore. PVC COVER STRIP AT PILLARS te5mm LV LUGS $06266 8 _JATSIN 17 & 20 Soeee6 x 8
TOTAL 62 816 883 87 467 30 467 UNDERGROUND CABLE SCHEDULE
1 CABLE SIZE / TYPE
ENERGEX TOTAL LOCATION Sew ry [VOLTS] Ex | REC | IN vkV LV REMARKS
NOTES 11AT240XSH] 11CT 185XSH]LVA4240XPV) LVC470XH |LVC416xPV] LVC24PVPV ] $0718!
1. CONDUITS SHALL BE INSTALLED WITHIN A CORRIDOR 300-900mm FROM PROPERTY ALIGNMENT, IN ACCORDANCE WITH ENERGEX UNDERGROUND DISTRIBUTION GATEWAY DRIVE - VISION COURT | PMT1 | PMT2 | 11kV IN 210
CONSTRUCTION (UDC) MANUAL. VISION COURT - VENTURE DRIVE | PMT 2] JT 2A | 11kV IN 90
2. FOOTPATH CONDUITS SHALL HAVE MINIMUM 750mm COVER, , REGARDLESS OF ENERGEX'S REQUIREMENTS. VENTURE DRIVE aT 2a] 30 | 11kV IN 216
3. CONNECT EXISTING CONDUITS, INCLUDING ROAD CROSSING CONDUITS, TO NEW FOOTPATH CONDUITS 30 31 | HkV IN 20
4. TELECOMMUNICATION CONDUITS SHALL BE INSTALLED IN A SEPARATE TRENCH. JOINT USE NOT PERMITTED BY ENERGEX IN A C &1 DEVELOPMENT. VISION COURT PmT2| 3 LV IN 6 CCT 3
5. DIRECTIONAL BORING FOR ELECTRICAL CONDUIT SHALL COMPLY WITH WITH ENERGEX SWP 61.1 - TRENCHLESS TECHNOLOGY. MINIMUM COVER SHALL BE 900mm. PMT 2| 15 LV IN 62 CCT 2
OTHERWISE INSTALL PVC COVER STRIP ABOVE CONDUIT. PMT 2 24 LV IN 79 CCT 1
VENTURE DRIVE 15 17 Lv IN 84
STREET LIGHT SCHEDULE - RATE 2 17 20 LV IN 16 185mm SINGLE STRAND
N POLE OR COMPONENTS OUTREACH BRACKET MOUNT 24 25 wv IN 30
s 24 27 U IN 4
LOCATION SITE 1.D. COMP |EXIST} REC ;ERECT| POLE COMP RECOVER ERECT EXIST] REC | ERECT REMARKS
No.
io. | am | am | om | type | CSC | ALIGN [TR | EXIST TO tcusthantemn Vous) CYSS Pom | om | am | CSC | Tim GATEWAY DRIVE 17 19 LV IN 89
VISION COURT a P2071893 P01 55 BPM {SLM872-4 0.7 su s7ae SUNC | SLM817-3 1.5  |StLM815-1 7.5 MINOR FOUNDATION 20 22 Lv IN 76 LV TIE
+5L P2071838 POT 55 BPM {SLM872-4 0.7 SL1 s70Le SUNC | SLM817-3 15 |SLM815-1 7.5 MINOR FOUNDATION PMT 1 22 LV IN 6 LV TIE
VENTURE DRIVE 16L P2071839 POT 55 BPM 'SLM872-4 0.7 Sui S702 SUNC | SLM8173 15 {StMg15-1 7.5 MINOR FOUNDATION
tea. | Pao7ied0 | P01 55 | BPM [SLM872-4 07 | Sut s7o.e | suNc | SLM817-3 1.5 _|SLM815-1 7.5 [MINOR FOUNDATION TOTALS ALL STREETS AT PILLARS Ly > 2
25L P2071841 POo1 55 BPM |SLM872-4 0.7 SLi S70L2 SUNC | SLM817-3 1.5 |SLM81S-1 7.5 MINOR FOUNDATION —— STREETLIGHTS SL > 99
SLM872-4 x 6
26L P207 1842 Pol §5 BPM 'SiM872-4 0.7 SLi s7a2 SUNC | SLM817-3 15 |SLM81S-1 7.5 MINOR FOUNDATION
NOTES SLM817-3 x 6 SUB-TOTAL 536 526 22 99 16
1, CHECK CLEAR WITH ALL SERVICE S BEFORE EXCAVATING. SLMB15-1 x 6
2. HAND POT HOLE AND LOCATE SERVICES AS REQUIRED. $04434 x 6 VARIANCE 4% 22 22 1 4 1
3. STANDARD STREET LIGHT POLES TO MATCH THE EXISTING IN GATEWAY DRIVE - 5.5m POLES AND 1.5m OUTREACH. § 15505 x t
TOTAL 558 548 23 103 7 OOTRENCH 544m
NOTES:
1. THE CONTRACTOR SHALL MEASURE ACTUAL CABLE LENGTHS REQUIRED, AFTER INSTALLATION OF CONDUITS, THEN ORDER CABLE ACCORDINGLY.
2. ELECTRICAL CONTRACTOR TO IDENTIFY AND SPIKE CABLES.
DATE | REV | REVISION APP. DATE | REV | REVISION APP. | CURRENT REVISION CHANGES: Seen ATION SWP47.1 DESIGNED D. BUCKENHAM DESCRIPTION LOCATION DRAWING No.
s SUBDIVISION ELECTRICAL SERVICES
126.08 | A | ORIGINAL ISSUE RR. Ro bi n 2046 Bebara Sree, suuties COUNCIL S.CRC. DRAWN N. OWENS ELECTRICAL SCHEDULES GATEWAY RISE a NOOSAVILLE STAGE 1
266.08 APPROVED RR. ne nae Ye ROBIN RUSSELL NOOSAVILLE "
R u Ss se | | Tek (07) 3872 5555 3 COUNCIL REF | 2007/1626 APPROVED BY | porg 4
253.14 | C | FORTENDER RR. Faxc (07) 3872 5566 . 546 CLIENT ENERGEX PROJECT No. SHEET No.
& ASSOCIATES PTY. LTD. Emait mérotrus.comau centifies UBD REF Map Gad SIGNED AQ Z . p
oe reenn ome Severe “it GATEWAY RISE PTY LTD $0104679 304 3
- ee THIS DOCUMENT IS COPYRIGHT AND THE PROPERTY OF ROBIN RUSSELL & ASSOCIATES PTY LTD
CONSULTING ENGINEERS ELECTRICAL =A. 78010 588661 DWT REV v26- 20140225 ‘| DATE 25103/2014 AND MUST NOT BE RETAINED, COPIED OR USED WITHOUT AUTHORITY. Al

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used in these records

About this file

File size
981 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

OPW14_0178 - Application for Operational Works - Electrical Reticulation & Street lighting (covering letter & plans) - 50 Gateway Dr, Noosaville- Stage 1.pdf · 981 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.