Effluent Disposal Approval northern unit

of 16

Page text shows just the words. Original shows the document exactly as it was published.

                                                                                                                               PO Box 4291, Springfield QLD 4300
                                                                                                                               ABN 37 147 807 420
                                                                                                                               QBCC Licence Number: 15055672



                                                                                     Proudly Australian Owned




                                       Site and Soil Evaluation

                  On-Site Wastewater and Effluent Disposal
                          System Design Solution

                                                    53 Martins Road,
                                                    Cooroy QLD 4563



                                                     APPROVED
                                                                NOOSA COUNCIL
                                                          PLUMBING SERVICES
                                       PLUMBING & DRAINAGE ACT 2018
                                       PLUMBING PERMIT NO PL21/0290


                                       Date 30/8/2021                                         Officer




                                                                            Taylor Environmental No: TE211533
                                                                                           Date: 23 April 2021



Document Set ID: 21598877
                                       Taylor Environmental (Australia) Pty Ltd on behalf of Taylor Environmental Unit Trust
Version: 1, Version Date: 30/08/2021
Log in to download the original file

Effluent Disposal Approval northern unit.pdf · 1.3 MB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

Full text of the other 15 pages

Page 2

                 1 Background
                 Taylor Environmental (Australia) Pty Ltd was engaged to design an on-site wastewater
                 treatment and effluent disposal system at 53 Martins Road, Cooroy QLD 4563. This property
                 is not serviced by a municipal sewer network and requires a wastewater treatment and effluent
                 disposal system.

                 The site location is displayed in Figure 1, below.




                 Figure 1: Site Location

                 The design was completed by Chris Taylor (Director, Taylor Environmental (Australia) Pty Ltd,
                 QBCC Licence Number 150 556 72).


                 2 Legislation and Standards
                 This report has been completed in accordance with the relevant legislative requirements:

                 ●   Plumbing and Drainage Act
                 ●   Plumbing and Drainage Regulation
                 ●   Queensland Plumbing and Wastewater Code
                 ●   AS/NZS 1547:2012 On-site Domestic Wastewater Management
                 ●   Plumbing Code of Australia (PCA)


                 3 Effluent Standards
                 Table 1 below presents the effluent standards produced by approved wastewater treatment
                 systems with beds or trenches.
                 Table 1: Effluent Quality
                  Parameter                                 Secondary           Advanced Secondary
                                                            90% < 20 mg/L       90% <10 mg/L
                  Biochemical Oxygen Demand
                                                            100% < 30 mg/L      100% <20 mg/L
                                                            90% < 30 mg/L       90% < 10 mg/L
                  Total Suspended Solids
                                                            100% < 45 mg/L      100% < 20 mg/L
                 Site and Soil Evaluation                                     53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                          Page 2 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 3

                 4      Site Details
                 Details of the subject property are presented in Table 2, below.

                 Table 2: Property Details
                  Feature                               Details
                  Property Address                      53 Martins Road, Cooroy QLD 4563
                  Real Property Description             Lot 4 on RP852013
                  Local Authority                       Noosa Shire Council
                  Property size                         15.5797 ha
                  Dwellings/structures                  Primary dwelling, sheds, proposed caretakers’ cottage
                  Water Supply                          Rainwater
                  Easements                             n/a
                  Vegetation                            Pasture grasses
                  Slope                                 13%
                  Slope configuration                   Linear Divergent
                  Aspect                                East
                  Water bodies                          Dams and intermittent watercourses
                  Bores                                 n/a
                  Flood hazard                          n/a
                  Environmental Areas                   Riparian Buffer Area around watercourses


                 5 Soil Investigation
                 A geotechnical assessment of the property was undertaken by Geotechnical Soils on 2
                 November 2020. The soil profile of the proposed land application area (Borehole 3) is
                 presented in Table 3.

                 Table 3: Soil Profile
                  Depth         Texture           Colour                         Plasticity     Structure        Category
                  300           Sandy Clay        Grey yellow brown              Low            Moderate         4
                  700           Sandy Clay        Red/orange yellow brown        Medium         Strong           5
                  1400          Sandy Clay        Orange brown                   Low-medium     Strong           5
                  2000          Sandy Clay        Yellow brown                   Low            Moderate         4


                 Table 4 presents the design characteristics of the receiving soil.

                 Table 4: Design Soil
                  Feature                                     Details
                  Texture                                     Sandy Light Clay
                  Colour                                      Red/orange yellow brown
                  Structure                                   Strong
                  Category                                    5
                  Indicative Permeability (Ksat)              0.12 – 0.5m/day
                  Design Loading Rate (DLR)                   12 mm/day

                 Site and Soil Evaluation                                                 53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                                      Page 3 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 4

                 6 Wastewater System Solution Design
                 It is proposed to install and AES system for the new caretakers cottage. The septic system for
                 the primary residence is to be retained.

                 Table 5 below presents the key features of this design solution.
                 Table 5: Design Features
                                             Feature                                   Details
                                             Treatment plant                           Advanced Enviro Septic (AES)
                   Treatment System          Treatment plant approval                  15/2019
                                             Treatment level                           Advanced secondary
                                             Water supply                              Rain Water (120 L/day)
                                             Number of bedrooms                        2 bedrooms
                     Design Volume
                                             Number of people                          4 People
                                             Total Design Volume (Q)                   480 L/day
                                             Category                                  5
                  Soil Characteristics
                                             Design Loading Rate (DLR)                 12 mm/day
                                             Application method                        Subsurface AES bed
                    Land Application
                                             Required Land Application Area            A = Q / DLR = 480 / 12 = 40 m2
                         Area
                                             Proposed Land Application Area            40 m2



                 The design of the AES system is presented in Appendix A.

                 The Advanced Enviro-Septic Approved Design Calculator is presented in Appendix B.

                 The AES Treatment Plant Approval is presented in Appendix C.



                 7 Setback Distances
                 The Queensland Plumbing and Wastewater Code V1:2019 Appendix Part 2, Table T2 and
                 Table T5, outlines minimum setback separation distances required for subsurface land
                 application areas.

                 These distances are presented in Table 6.

                 Table 6: Separation Distances
                                                                                      Separation Distance
                                           Feature
                                                                              Up Slope   Down Slope       Level
                  Property boundaries, pedestrian paths, walkways,
                                                                                2m                  4m                 2m
                  recreation areas, retaining walls, footings
                  Inground swimming pool                                        6m                  6m                 6m
                  Inground potable water tank
                                                                                6m                  6m                 6m
                  (not exposed to primary effluent)
                  Inground potable water tank
                                                                                15 m                15 m              15 m
                  (exposed to primary effluent)

                 Site and Soil Evaluation                                                  53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                                       Page 4 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 5

                                                                                Separation Distance
                                           Feature                        Adv.
                                                                                   Secondary        Primary
                                                                        Secondary
                     Top of bank of watercourse / waterbody                    10 m            30 m               50 m
                     Open stormwater drainage channel or drain                 10 m            30 m               50 m
                     Bore or dam                                               10 m            30 m               50 m
                     Permanent water table (vertical)                          0.3 m           0.6 m              1.2 m

                 This design complies with all relevant separation distances.


                 8 Maintenance
                 Homeowners have a responsibility to ensure the onsite wastewater treatment and effluent
                 disposal system is maintained and serviced.

                 The following servicing and precautions are to be undertaken:

                 •     Septic tanks to be checked annually and pumped out when 1/3 full of solids or once every
                       5 years, whichever is sooner
                 •     Read and follow the Owner's Manual that is provided with the system
                 •     Comply with local authority’s servicing requirements
                 •     Do not manipulate the system so that it no longer complies with the Council issued permit
                       or the plans located in Appendix A of this document
                 •     Maintain the land application area e.g. regularly mowed and ensure that there is no
                       ponding of effluent
                 •     Vehicles, animals and general access to the land application area is to be generally
                       restricted with warning signs erected
                 •     Use low sodium biodegradable soaps and detergents as per the label instructions and no
                       paints, solvents, chemicals, food scraps, fats, oils or any other solids to be disposed of
                       “down the drain”
                 •     It is always good practice to minimise / stagger high wastewater generating activities such
                       as laundry over a full week
                 •     On-site sewage systems are not designed to cope with the flow from garbage grinders




                 Chris Taylor MEnvMan, BAppSc(Chem), ADCivEng Cert IV DWM003
                 Director | Taylor Environmental (Australia) Pty Ltd
                 23 April 2021




                 Site and Soil Evaluation                                              53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                                   Page 5 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 6

                 Appendix A                  System Design Drawings




                 Site and Soil Evaluation                             53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                  Page 6 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 7

                                                                                                                           REVISIONS
                                                                                                           REV DATE      SUBJECT               AUTHORISED
                                                                                 PROPOSED CARETAKERS        A 23/04/2021 REVISION A            C. TAYLOR
                                                                                 COTTAGE WITH AES SYSTEM




                                                                                     20000
                                       RIPARIAN                                                                 TAYLOR ENVIRONMENTAL
                                       BUFFER AREA
                                                                                            14000

                                                                                       50
                                                                                         00
                                                                                             0
                                                              180000




                                                                                                           QBCC LICENCE NUMBER 150 556 72
                                                                                                           ABN NUMBER 95268308955

                                                                                                           Phone: +61 400 301 364
                                                                                                           Email: [email protected]
                                                                                                           Web: www.taylorenviro.com.au
                                                               PRIMARY
                                                               DWELLING

                                                                                                            WASTE WATER TREATMENT &
                                                                                                            EFFLUENT DISPOSAL SYSTEM

                                                                                                           AUTHORISED FOR ISSUE                  DATE

                                                                                                                                              23/04/2021


                                                                       APPROVED                            STREET ADDRESS
                                                                                                           53 MARTINS ROAD, COOROY 4563
                                                                                                           LOT & PLAN 4 RP852013
                                                                                                           NAME OF CLIENT
                                                                          NOOSA COUNCIL                    ECO COTTAGES
                                                                                                           COUNCIL
                                                                                                           NOOSA SHIRE
                                                                       PLUMBING SERVICES                   DESIGNER
                                                                                                           C. TAYLOR
                                                                                                                                                  DATE
                                                                                                                                                23/04/2021
                                                                                                           DRAWN                                  DATE
                                                            PLUMBING & DRAINAGE ACT 2018                   M. MAHONY
                                                                                                           DRAWING DETAILS
                                                                                                                                                23/04/2021

                                                                                                           Site Layout
                                           MARTINS          PLUMBING PERMIT NO PL21/0290                   SCALE
                                                     ROAD
                                                                                                           1:2000
                                                                                                           CLIENT REFERENCE #


                                                                                                           JOB NUMBER              REVISION      DWG #

                                                            Date 30/8/2021          Officer                TE211533                    A           SL1


Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 8

    GENERAL NOTES:
     - LOCATION OF HSTP, ORG, VENT PIPE AND OTHER                   135m                                                                                                                                                        REVISIONS
        WASTE PIPES TO BE DETERMINED BY PLUMBER                                                                                                                                                                 REV DATE      SUBJECT               AUTHORISED
     - REFER TO COMPLIANCE PERMIT FOR CONDITIONS OF                                                                                                                                                              A 23/04/2021 REVISION A            C. TAYLOR
        COUNCIL APPROVAL

    REDUCED LEVELS:                                                                                                                       135m
     - AES FSL = 135.1
     - MIN INVERT OF SEPTIC TANK OUTLET = 135.175
     - MIN INVERT OF SEPTIC TANK INLET = 135.225                                                                                                                                                  134m
     - MIN TOP OF SEPTIC TANK = 135.65
     - DWELLING FFL = 137.00                                                                                                                                                                             133m

    AES SYSTEM:                                                                                                                                                                                                      TAYLOR ENVIRONMENTAL
     - EXCAVATE BED WITH LASER LEVEL
     - RIP LEVEL OF BASE ≈300 to 400mm
     - RE-EXCAVATE BED BACK TO CORRECT LEVEL USING
        A LASER LEVEL                                                                                                        POOL




                                                                                                                                                                        12200
     - GYPSUM BASE AT 1kg/m2
     - PLACE AES APPROVED SAND
     - USE JIG TO ENSURE THAT AES PIPES ARE STRAIGHT
        AND LEVEL
                                                                       136m
     - PLACE AES APPROVED SAND OVER PIPES TO THE




                                                                                                                                                         20000
        CORRECT DEPTH
     - REPLACE EXCAVATED SOIL IN BED                                                                                                                                            100% RESERVE AREA
     - TOP SOIL AND GRASS
     - NO TREES WITHIN 2m OF BED

    SEPTIC TANK:
                                                                               PROPOSED




                                                                                                                                        930
     - TO BE INSTALLED AS PER MANUFACTURERS
         SPECIFICATION                                                        CARETAKERS




                                                                                                                                         0
     - SWIVEL KNUCKLE AND EXPANSION JOINTS TO BE                                                                               950
                                                                                COTTAGE                   BH2                       0
         INSTALLED ON INLET AND OUTLET PIPES
     - 75mm MIN DIFFERENCE IN LEVEL BETWEEN BOTTOM
         OF SEPTIC TANK OUTLET AND FINAL SURFACE AREA                                                                                                                                                           QBCC LICENCE NUMBER 150 556 72
         OF AES BED                                                                                                                                              TE2                                            ABN NUMBER 95268308955
                                                                                                                                                                                                  9400
    DRAINAGE:                                                                                                                                                                                                   Phone: +61 400 301 364
     - ∅100 uPVC DWV (MIN GRADE 1:60) UNLESS                                                3000L (min) ALL-WASTE                                                                                               Email: [email protected]
                                                                                                                                                  TE1                                                           Web: www.taylorenviro.com.au
         OTHERWISE NOTED                                                                               SEPTIC TANK
                                                                                       24000
                                                                 CARPORT      BH1
                                                                                                                                                                                                                 WASTE WATER TREATMENT &
                                                RAINWATER TANK
                                                                                                                                                                                                                 EFFLUENT DISPOSAL SYSTEM
                                                                                                                                          BH3                                     14300
                                                                                                                                                                 Ensure AES bed is installed                    AUTHORISED FOR ISSUE                  DATE
                                                                                                                                                                 outside of the Riparian Buffer
                                                                                                                                                                 Zone                                                                              23/04/2021

                 APPROVED
                                                                                                                                                                                 SLO
                                                                                                                                                                                    PE
                                                                                                                                                                                         13%
                                                                                                                                                                                                                STREET ADDRESS
                                                                                                                         0
                                                                                                                     780                                                                                        53 MARTINS ROAD, COOROY 4563
                                                                                                                                                                                                                LOT & PLAN 4 RP852013
                                                                                                                                                                                                                NAME OF CLIENT
                          NOOSA COUNCIL                                                                                                           AES BED
                                                                                                                                                                                                                ECO COTTAGES
                                                                                                                                                                                                                COUNCIL
                                                                                            GRAVEL                                                [9.6m x 4.17m] = 40m²
                                                                                                                                                                                                                NOOSA SHIRE
                     PLUMBING SERVICES                                                     DRIVEWAY                                                                                                             DESIGNER                               DATE
                                                                                                                                                                                                                C. TAYLOR                            23/04/2021
                                                                                                                                                                                                                DRAWN                                  DATE
    PLUMBING & DRAINAGE ACT 2018                                                                                                                                                                                M. MAHONY                            23/04/2021
                                                                                                                                                                                                                DRAWING DETAILS
                                                                                                                       BH4
                                                                                                                                                                                                                PART SITE PLAN
    PLUMBING PERMIT NO PL21/0290                                                                                                              RIPARIAN BUFFER AREA                                              SCALE
                                                                                                                                                                                                                1:200
                                                                                                                                                                                                                CLIENT REFERENCE #


                                                                                                                                                                                                                JOB NUMBER              REVISION      DWG #

     Date 30/8/2021                            Officer                                                                                                                                                          TE211533                    A           SL2


Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 9

                                                                                                                                                                                                  REVISIONS
                                                                                                                                                                                  REV DATE      SUBJECT               AUTHORISED
                                          RAISED CONNECTOR                              INSPECTION POINT                     COUPLINGS                 OFFSET ADAPTER              A 23/04/2021 REVISION A            C. TAYLOR




                                                                                                                                                                    1350
                                                                                                                                           LOW VENT                                    TAYLOR ENVIRONMENTAL




                                                                                                                                                                           4170
                                                                                                                                                                    2820
                                                              INSPECTION POINT




                                                     300                                                   9000                                           300

                                                                                                           9600


                                                                                                                                                                                  QBCC LICENCE NUMBER 150 556 72
                                                                                                                                                                                  ABN NUMBER 95268308955

                                                                                                                                                                                  Phone: +61 400 301 364
                                                                                                                                                                                  Email: [email protected]
     AES BED PLAN VIEW                                                                                                                                                            Web: www.taylorenviro.com.au




                                                                                                                                                                                   WASTE WATER TREATMENT &
                                                                                                                                                                                   EFFLUENT DISPOSAL SYSTEM
                                                                     INSPECTION POINT            LOW VENT
                                                                                                                         TOP SOIL/GRASS

               APPROVED
                                                             APPROVED SAND                                                                                                        AUTHORISED FOR ISSUE                  DATE
                                                                                                                                                      INSPECTION POINT
                                                                                                   150                                                                                                               23/04/2021
                                                                                                                               BACK FILL
                                                                                                                                                                                  STREET ADDRESS
                                                                                                                                                                                  53 MARTINS ROAD, COOROY 4563
                        NOOSA COUNCIL                                                                                                                   13% SLOPE
                                                                                                                                                                                  LOT & PLAN 4 RP852013
                                                                     300
                                                               750




                                                                                                                                                                                  NAME OF CLIENT
                                                                                                                                                          150                     ECO COTTAGES
                                                                     300




                  PLUMBING SERVICES                                                                                                                                               COUNCIL
                                                                                                                                                                                  NOOSA SHIRE
                                                                                                                                                                                  DESIGNER                               DATE
  PLUMBING & DRAINAGE ACT 2018                                                                                                                                                    C. TAYLOR                            23/04/2021
                                                                                                                                                         RIP & SCARIFY 300mm      DRAWN                                  DATE
                                                                                   300 150 300   300                                                     APPLY GYPSUM 1kg/m^2     M. MAHONY                            23/04/2021
  PLUMBING PERMIT NO PL21/0290                                                                                                                                                    DRAWING DETAILS
                                                                                    1350                                     2820                                                 Bed Plan & Section
                                                                                                                                                                                  SCALE
                                                                                                                                                                                  N/A
                                                                                                                  4170                                                            CLIENT REFERENCE #

   Date 30/8/2021                      Officer                                                                                                                                    JOB NUMBER              REVISION      DWG #
                                                                                                                                                                                  TE211533                    A           SL3
     AES BED SECTION VIEW
Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 10

                                                                            SOIL CHARACTERISTICS                            GENERAL NOTES                                                                                                                                                                      100    LOW VENT INSTALL
                                                                                                                                                                                                                                                                                                               WITH A MOSQUITO
                                                                                                                                                                                                                                                                                                               PROOF STAINLESS
                                                     TEXTURE                                        LIGHT CLAY              1.    THE SYSTEM INSTALLER IS RESPONSIBLE TO ESTABLISH THE LOCATION, LEVELS AND DEPTHS OF ALL EXISTING SERVICES                                                                    STEEL MESH. FIXED TO
                                                                                                                                  ON-SITE PRIOR TO COMMENCING ANY WORKS
                                                                                                                                                                                                                                                                TURF ALL FINAL GRADES. NO DEEP
                                                                                                                                                                                                                                                                ROOTED PLANT MATERIALS ON SYSTEMS
                                                                                                                                                                                                                                                                                                               BOLLARD                                                             REVISIONS
                                                STRUCTURE                                               STRONG                                                                                                                                                  OR OVERFILL AREAS
                                                                                                                            2.    LOCATIONS AND SETOUT DIMENSIONS SHOWN ARE APPROXIMATE ONLY AND ARE TO BE CONFIRMED ON SITE.                                                                                     ELBOW LEVEL WITH                                 REV DATE      SUBJECT               AUTHORISED
                                        SOIL CATEGORY                                                      5                3.    ACCESS AND LAY DOWN AREAS ARE TO BE CONFIRMED BY THE SYSTEM INSTALLER                                                                                                           TOP OF OFFSET
                                                                                                                                                                                                                                                                                                                                                                    A 23/04/2021 REVISION A            C. TAYLOR




                                                                                                                                                                                                                                                                                                                                        150
                                                                                                                                                                                                                                                                                                                  ADAPTER
                                                                                                                            4.    EXISTING BUILDINGS AND EXTERNAL STRUCTURES SHOWN ON THESE DRAWINGS ARE OBTAINED FROM THE AVAILABLE
                   INDICATIVE PERMEABILITY                                                        0.12 - 0.5 m/DAY                INFORMATION AND MAY NOT BE COMPLETE AND ACCURATE
                                                                                                                            5.    ALL DIMENSIONS ARE IN MM U.N.O
                          DESIGN LOADING RATE                                                       12 mm/DAY               6.    NO TREES TO REMAIN WITHIN 2.0m OF AES FOOTPRINT                                                                                                 50mm - 100mm
                                                                                                                                                                                                                                                          GEOTEXTILE
                                                                                                                            7.    PLUMBING AND DRAINAGE TO QLD PLUMBING & WASTEWATER ACT, AS / NZS 3500                                                   FIBER WRAP
                                                                               DESIGN VOLUME                                8.    ALL PIPE WORK TO AS / NZS 4020                                                                                                                                             LEVEL
                                                                                                                            9.    ALL TANKS TO BE INSTALLED AND ANCHORED IN COMPLIANCE WITH THE MANUFACTURERS SPECIFICATIONS                              RANDOMLY
                                       WATER SUPPLY                                       RAIN WATER [120 L/P/DAY]          10.   FLEXIBLE JOINTS ON ALL INSTALLED TANKS (AS / NZS 3500)                                                                  ORIENTED FIBER
                                                                                                                                                                                                                                                                                                                              SLOPE
                                                                                                                                                                                                                                                          MAT
                                                                                                                            11.   THERE SHALL BE NO CROSS CONNECTION BETWEEN ANY WASTEWATER / EFFLUENT PIPEWORK AND ANY POTABLE WATER
                         NUMBER OF BEDROOMS                                                         2 BEDROOMS                    SUPPLY PIPEWORK                                                                                                         ENVIRO - SEPTIC                                                OFFSET
                                                                                                                            12.   MINIMUM DISTANCE BETWEEN TANKS AND BUILDINGS TO BE MAINTAINED (AS/NZS 3500)                                                                                                            ADAPTER
                               NUMBER OF PEOPLE                                                         4 PEOPLE
                                                                                                                            13.   USE ONLY A LICENSED DRAINER THAT HAS BEEN ACCREDITED BY THE AES SYSTEM SUPPLIER. THE SUPPLIER WILL NOT
                                                                                                                                                                                                                                                          PIPE
                                                                                                                                                                                                                                                                                                                                                                        TAYLOR ENVIRONMENTAL
                                                                                                                                                                                                                                                                                                                                  ORIGINAL SOIL
                                                                                                                                  PROVIDE THE AES PIPES UNLESS THE LICENSED DRAINER HAS BEEN TRAINED AND ACCREDITED                                                                    APPROVED SAND
                        TOTAL DESIGN VOLUME                                                         480 L/DAY
                                                                                                                            14.   AES PIPES MUST BE INSTALLED AS PER AES INSTALLATION INSTRUCTIONS.
                                                                               DISPOSAL AREA                                15.   FINAL LOCATION OF AES BEDS AND ASSOCIATED PIPE WORK CAN ONLY BE ALTERED ON SITE TO MEET THE SITE CONDITIONS
                                                                                                                                  AFTER APPROVAL FROM TAYLOR ENVIRONMENTAL (AUSTRALIA) PTY LTD
                       TOTAL DISPOSAL AREA                                                              48.0 m²             16.
                                                                                                                            17.
                                                                                                                                  GRADE ALL BATTERS EVENLY AT 1 IN 5, UNLESS NOTED OTHERWISE
                                                                                                                                  ANY SOILS ENCOUNTERED WHICH SHOW EVIDENCE OF CONTAMINATION ARE TO BE STOCKPILED SEPARATELY. CONTAMINATED                                      LOW VENT
                                  TYPE OF FACILITY                                         ADVANCED ENVIRO SEPTIC                 SOIL SHALL BE HANDLED IN ACCORDANCE WITH ALL WORKPLACE HEALTH & SAFETY AND ENVIRONMENTAL REGULATIONS
                                                                                                                            18.   IT IS THE INSTALLERS RESPONSIBILITY TO PROVIDE ACCURATE 'AS CONSTRUCTED' DRAWINGS TO RELEVANT LOCAL                                                                                  90 DEGREE ELBOW
        TREATMENT PLANT APPROVAL                                                                        15 / 2019
                                                                                                                                  AUTHORITY AND INCUR ASSOCIATED COST
                                 TREATMENT LEVEL                                            ADVANCED SECONDARY              19.   ALL DISTURBED AREAS TO BE RE-GRASSED AND RECTIFIED
                                                                                                                            20.   EXISTING TOPSOIL IS TO BE RETAINED AND SET ASIDE (WINDROWED) TO PREVENT DAMAGE FROM MACHINERY AND                 DO NOT INSERT PVC PIPE MORE THAN                                   100mm PVC PIPE
                                                                          AES CALCULATOR OUTCOMES                                 REDISTRIBUTED ONCE INSTALLATION IS COMPLETE                                                                          100MM INTO OFFSET ADAPTER
                                                                                                                            21.   AT LEAST A 5 TONNE MACHINE WITH POSI-TRACK SYSTEM IS REQUIRED FOR EARTHWORKS TO ELIMINATE POTENTIAL TRACK
                            GRAVITY OR PUMPED                                                           GRAVITY                   INDENTATIONS INTO GROUND LEVEL
                                                                                                                            22.   IT IS THE RESPONSIBILITY OF THE INSTALLER TO ENGAGE THE DESIGNER TO UNDERTAKE INSPECTIONS DURING INSTALLATION.                                                                       OFFSET ADAPTER
              NUMBER OF AES PIPE ROWS                                                                      2                      FAILURE TO DO SO WILL RESULT IN THE FORM 8 / COMMISSIONING CERTIFICATE NOT BEING ABLE TO BE COMPLETED
                                                                                                                                                                                                                                                                                                                         END VIEW
                 LENGTH OF AES PIPE ROW                                                                   9m
                                                                                                                            INSTALLATION                                                                                                                                                                                       ELBOW LEVEL WITH TOP OF
                                                                                                                                                                                                                                                                                                                                   OFFSET ADAPTER
             NUMBER OF AES PIPES/ROW                                                                       3                                                                                                                                                                                GEOTEXTILE FIBER
                                                                                                                                                                                                                                                                                                                                              2
                                                                                                                                                                                                                                                                                                 WRAP
                                                                                                                            -     IT IS THE INSTALLERS RESPONSIBILITY TO ENSURE THAT ALL COMPONENTS COMPLY WITH THESE GUIDES UPON
                                  BUFFER CAPACITY                                                        1272 L                   COMMISSIONING OF THIS SYSTEM                                                                                                                                RANDOMLY
                                                                                                                                                                                                                                                                                            ORIENTED FIBER                                                         QBCC LICENCE NUMBER 150 556 72
                                                                             BILL OF QUANTITIES                             -     ALL BURIED PIPE WORK IS TO BE IDENTIFIED WITH UNDERGROUND MARKING TAPE PLACED ABOVE THE PIPE WORK                                                              MAT                                                               ABN NUMBER 95268308955
                                                                                                                            -     ALONG THE BOUNDARY OF THE LAND APPLICATION AREA THERE SHALL BE AT LEAST 2 WARNING SIGNS CLEARLY                                 TOP VIEW                     ENVIRO-SEPTIC                                              OFFSET
                                                  AES PIPES                                                6                      VISIBLE TO ADVISE THAT RECYCLED WATER IS USED (EACH SIGN SHALL COMPLY WITH AS1319 AND HAVE THE                                                                                                                         ADAPTER   Phone: +61 400 301 364
                                                                                                                                  WORDING RECYCLED WATER - AVOID CONTACT DO NOT DRINK)                                                                                                                                                                             Email: [email protected]
                                   COUPLINGS [AESC]                                                        4                                                                                                                                                                                                                                                       Web: www.taylorenviro.com.au
                   OFFSET ADAPTOR [AESO]                                                                   4                MAINTENANCE                                                                                                                                                                                SIDE VIEW

       OXYGEN DEMAND VENT [AESODV]                                                                          1               -     SEPTIC TANKS TO BE CHECKED FOR SOLIDS BUILD UP ANNUALLY
       INSPECTION POINT BASE [AESIPB]                                                                      2                -     SEPTIC TANKS TO PUMPED OUT IF 31 FULL OF SOLIDS OR 5 YEARS (WHICHEVER IS SOONER)                                                          RAISED CONNECTION                                                                       WASTE WATER TREATMENT &
                                                                                                                            -     LAND APPLICATION IS IMPORTANT AND IS TO BE REGULARLY MOWED AND ANIMALS AND VEHICLES EXCLUDED
                            CLEAN COURSE SAND                                                            17 m²                                                                                                                                                                                                                                                      EFFLUENT DISPOSAL SYSTEM
                                                                               AES FOOTPRINT
                                                                               LENGTH          WIDTH                AREA                                                                                                                                                                                                                                           AUTHORISED FOR ISSUE                  DATE
             AES SYSTEM                                                         9.6 m          1.35 m             13.0 m²                                                                                                                                                                                                                                                                             23/04/2021
       EXTENSION AREA                                                           9.6 m          2.82 m             27.0 m²
                                                                                                                                                                                                                                                                                                                                                                   STREET ADDRESS
                          TOTAL                                                 9.6 m          4.17 m             40.0 m²                                                                                                                                                                                                                                          53 MARTINS ROAD, COOROY 4563
                                                                                                                                                                                                                                                                                                                                                                   LOT & PLAN 4 RP852013
                                                                                                                                                                                                                                                                                                                                                                   NAME OF CLIENT
                                                                                                                                                                                                                                               INSPECTION OPENING, SWIVEL KNUCKLE,
                                                                                                                                                                                                                                               EXPANSION JOINT ON INLET AND OUTLET OF                                                                              ECO COTTAGES
                                                                                                                                                                                                                                               SEPTIC TANK                                                                                                         COUNCIL
        C:\Users\Chris\Downloads\CEA#15_2019_AES Advanced Secondary.png
                                                                                                                                                                                                                                                                                                                                                                   NOOSA SHIRE
                                                                                                                                                                                                                                                      ∅100 uPVC DWV TO AES BED                                                                                                                            DATE
                                                                                                                                                                                                                                                                                                                                                                   DESIGNER
                                                                                                                                                                                                                                                      [MIN GRADE 1:60]                       AES BED                                                               C. TAYLOR                            23/04/2021
                                                                                                                                                                                                        GROUND                                                                               75mm MIN DIFFERENCE IN LEVEL
                                                                                                                                                                                                                                                                                             BETWEEN BOTTOM OF SEPTIC TANK                                         DRAWN                                  DATE
                                                                                                                                                                                                         LEVEL
                                                                                                                                                                                                                                                                                             OUTLET AND FINAL SURFACE AREA OF                                      M. MAHONY                            23/04/2021
                                                                                                                                                                                                                                                                                             AES BED
                                                                                                                                                                                                                                                                                                                                                                   DRAWING DETAILS
                                                                                                                                                                                                                                                                       75                                              LOW VENT
                                                                                                                                                                                                                            50




                                                                                                                                                                                                                                                                                                                                                                   MATERIALS
                                                                                                                                                                                                                                                                                                                                                                   SCALE
                                                                                                                                                                                                                                                                                                                                                                   N/A
                                                                                                                                                                           ∅100 uPVC DWV TO SEPTIC TANK                                                                                                                                                            CLIENT REFERENCE #
                                                                                                                                                                           [MIN GRADE 1:60]                            SEPTIC TANK
                                                                                                                                  REDUCED LEVELS
                                                                                                                                  AES FSL                       0.00 m
                                                                                                                                  MIN INVERT OF SEPTIC OUTLET + 0.075 m
                                                                                                                                  MIN INVERT OF SEPITC INLET  + 0.05 m                                                                                                                                                                                             JOB NUMBER              REVISION      DWG #
                                                                                                                                  MIN TOP OF SEPTIC TANK      + 0.425 m
                                                                                                                                                                                                                                                                                                                                                                   TE211533                    A           SL4



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 11

                 Appendix B                  Advanced Enviro-Septic Approved Calculator




                 Site and Soil Evaluation                              53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                  Page 11 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 12

                                                                                  Advanced Enviro-septic Design Calculator V8.8 ©

                                                        Leader in Passive Solutions
                      Site
                              53 Martins Road Cooroy QLD 4563                                                                     State     QLD               Post Code                        4563
                    Address
                     Client
                              MAIN BED                                                                                                                    Date of Site Visit
                     Name
                                                                                                                                                           Designer Lic
                    Designers                                                                            Designers Ph
                              Chris Taylor | Director | Taylor Environmental (Aust)                                             Mb,0400 301 364               Number                15055672
                     Name                                                                                  Number
                      Lic                                                                                                                                   (eg.QBCC)
                                                                                                         Plumber Ph                                       Plumb / Drainer
                    Plumber TBA                                                                                                       TBA                                             TBA
                                                                                                           Number                                           Lic Number
                     Name
                    Council                                                                             Designers AES
                              Sunshine Coast                                                                                       QLD00011                     Date                 23/4/21
                      Area                                                                               Cert Number
                             This Calculator is a guide only, receiving soil classification, surface water, water tables and all other site constraints addressed by the qualified designer.

                                       System Designers site and soil calculation data entry                                                    IMPORTANT NOTES
                    Enter AES L/m loading rate, "30" for ADV Secondary or "38" Secondary                     30         >> This design is for an ADVANCED SECONDARY system

                                                         Is this a new installation     Y or N                Y         >>     Minimun single vent size is 80mm or 2 x 50mm house vents

                                                                            Number of person                  4                a septic tank outlet filter is NOT RECOMMENDED

                                             Daily Design Flow Allowance Litre/Person/Day                    120

                                         Number of rows required to suit site constrants                      2         >>The maximum length of a single AES pipe run is 30 meters


                    Infiltration surface Soil Cat as est by site/soil evaluation. CATEGORY                    5         >> Catagory may require design considerations. Ref AS1547

                      Design Loading Rate based on site & soil evaluation DLR (mm/day)                       12         >> Soil conditioning may be necessary. Ref AS1547 & Comments.

                                                         Bore log depth below system Basel area              600        >>Min depth below basel area 600mm check water table/restrictive layer

                    Enter System footprint Slope in % for std AES systems to calc extension                   0

                              Is this design a gravity system with no outlet filter? Y or N                   y         >>     A House Vent & LOW VENT required on this system

                                PLEASE CHECK YOU HAVE FALL FROM TANK TO AES SYSTEM PIPES
                                                                                      40

                    COMMENTS :- " The outcome must be important to everyone. "
                    - Ripping of receiving surface required in clay soil structures in Cat 4,5,6. In addition refer to AS 1547. Always excavate & rip parallel to the site slope/AES pipe.

                    - Specialist soils advice & special design techniques will be required for clay dominated soil having dispersive or shrink/swell behaviour. Refer AS1547




                    - Plumbers are reminded that good construction techniques as per AS1547 are especilly important in these soil types. Refer AS1547 & AES installation Instructions


                                                AES System Calculator Outcomes                                                                                AES dimensions

                                                          Total System load - litres / day (Q).              480        l/d                                AES System          System Extension

                                                Min Length of AES pipe rows to treat loading                 8.0        lm                  Lth m : (L)          9.6                   9.6

                                                    Number of FULL AES Pipe lengths per row                   3         lths              Width m:(W)            1.35                 2.82
                                                                                                                                             Sand
                                                 Total Capacity of AES System pipe in Litres                1272        ltr.                                     0.75                 0.15
                                                                                                                                            Depth :
                                        AES Additional infiltration extension required                      27.0        m2                    Area m2            13.0                 27.0
                               USE CUT LENGTHS OF PIPE IN THIS DESIGN? (ENTER Y)                              y

                                IF YOU WISH TO USE A TRENCH EXTENSION DESIGN OPTION ENTER "Y"                                               Enter Custom Width in metre

                        AES INFILTRATION FOOT PRINT AREA -                   L = Q / ( DLR x W)           Length                 Width            Minimum AES foot print required .

                                                         for this Basic Serial design is                     9.6         x        4.17            =              40.0          m2 total




                      Code                        AES System Bill of Materials.                                                                       Chankar Environmental Use Only

                    AES-PIPE                         AES 3 mtr Lths required                                  6         lths                                                      Digitally signed by
                      AESC                          AESC Couplings required                                   4         ea                                                        Steve Dennis
                                                                                                                                                                                  DN: cn=Steve
                      AESO                            AESO Offset adaptors                                    4         ea
                                                                                                                                                                                  Dennis, o=Chandar
                    AESODV                           AES Oxgen demand vent                                    1         ea                                                        Enviromental,
                    AES-IPB                     AES 100mm Inspection point base                               2         ea
                                                                                                                                                                                  ou=Resign Review,
                                                                                                                                                  “Nature's Wastewater Solutions” email=designrevie

                    AES Equ                         AES Speed Flow Equaliser                                            ea                                                        w@enviro-
                    AES DESO                          Double Offset Adaptors                                            ea                                                        septic.com.au,
                                                                                                                                                                                  c=AU
                                     TOTAL SYSTEM SAND REQUIRED (Guide Only)                                 17         m3
                                                                                                                                                                                  Date: 2021.04.23
                                       PLEASE email your AES CALC and Drawings to                                                                                                 15:39:49 +10'00'
                                       [email protected]                                                                                  [email protected]
                    > The AES Calculator is a design aid to allow checking of the AES components and configuration and is a guide only. Site and soil

                     conditions referencing the AS 1547 standard are calculated and designed by a Quailified Designer.

                    > Chankar Environmental has no responsibility for the soil evaluation, loading calculations or DLR entered by the designer for this calculator.

                    > AES pipes can be cut to length on site. They are supplied in 3 meter lths only.

                                                                    AES-Design-V8.8-Calculator © Copy Right - Chankar Environmental pty ltd 14/3/2016

Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 13

                 Appendix C                  Treatment Plant Approval




                 Site and Soil Evaluation                               53 Martins Road, Cooroy QLD 4563
                 Taylor Environmental (Australia) Pty Ltd                                   Page 13 of 16



Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 14

                                        TREATMENT PLANT APPROVAL 15/2019
                                            Plumbing and Drainage Act 2018
                                                  Amendment No.1
                 Approval

                   1. The Advanced Enviro-septic (AES) (“the System”) described in the Specifications and
                      Drawings in the attached Schedule and manufactured by Presby Environmental Inc.
                      Whitefield, New Hampshire (“the manufacturer”) and supplied by Chankar
                      Environmental Pty Ltd (ACN 148 175 455) (“the supplier”) has been assessed in
                      accordance with the Queensland Plumbing and Wastewater Code (QPW Code) dated
                      15th January 2013.

                 2.     The supplier applied to the Chief Executive on 12 February 2020 for an amendment to
                        the system as specified below.

                 3.     Approval is granted for previous Condition 10, to be amended to state: ‘A septic tank
                        conforming to AS/NZS1546.1 and sized in accordance with AS/NZS1547 for the
                        influent hydraulic load from the dwelling is a component of the system’.

                 4.     Approval is granted for an advanced secondary quality wastewater treatment system,
                        subject to compliance by the manufacturer/supplier with the requirements of the
                        Plumbing and Drainage Act 2018 and the conditions of approval detailed below.

                 5.     This approval, the conditions of approval and the Schedule comprise the entire
                        Treatment Plant Approval document.

                 6.     Any modification by the manufacturer/supplier to the design, drawings or
                        specifications scheduled to this approval must be approved by the Chief Executive.

                 Conditions of approval
                 7.     The manufacture, installation, operation, service and maintenance of the systems
                        must be inconformity with the conditions of this Treatment Plant Approval.

                 8.     The advanced secondary quality wastewater treatment system, which is an example
                        of the approved systems, may only be used on premises that generate per day:

                            a) a maximum hydraulic loading of 90L / 3 metre length of AES piping system
                            b) a maximum organic loading of 240mg/L BOD5
                            c) a maximum total suspended solids of 300mg/L.

                   9. The system must continue to meet the requirements of advanced secondary quality
                      wastewater treatment system, producing the following effluent quality —

                            a) 90% of the samples taken must have a BOD5 less than or equal to 10 g/m³
                               with no sample greater than 20 g/m³.
                            b) 90% of the samples taken must have total suspended solids less than or equal
                               to 10g/m³ with no sample greater than 20g/m³.
                   10. Each system must be serviced in accordance with the details supplied in the owner’s
                       operation and maintenance manual.
                                                                                    Treatment Plant Approval
                                                                                Approved by: Lindsay Walker
                                                                                Delegated Authority
                                                                                Department of Housing & Public Works
Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 15

                   11. The system design is based upon secondary quality effluent design loading rate as
                       defined in AS/NZ1547 using the AES Design Calculator prepared by a qualified
                       designer. System designs must be verified and signed by the supplier before being
                       submitted to the Local Government.

                   12. A septic tank conforming to AS/NZ 1546.1 and sized in accordance with AS/NZ 1547
                       for the influent hydraulic load from the dwelling is a component of the system. Waste
                       from the septic tank is to be diverted to the AES piping system prior to the system
                       sand and basal area. The septic tank that feeds into the system must be regularly
                       monitored and maintained (including de-sludging) in accordance with AS/NZ 1547 to
                       ensure optimum operation of the system.

                   13. When granting a compliance permit, the local government must satisfy itself that the
                       designer’s choice of the system configuration is optimal for the proposed use and site
                       conditions and that the effluent can be retained within the land application area.

                   14. Each application for a compliance permit to install a system must also be accompanied
                       by a copy of a completed Advanced Enviro-Septic Design Calculator Report endorsed
                       by the supplier, showing the footprint/basal area of the proposed system and number
                       of pipe modules for the site.

                   15. An inspection/sampling point must be installed permanently in the sand immediately
                       below the half-way point of the AES piping system. Where a system is installed in a
                       sloping basal area an additional inspection/sampling point must be installed at the
                       lowest point of the system extension.

                   16. Routine maintenance of the system at set intervals, other than septic tank sludge
                       levels, is not stipulated by the manufacturer/supplier. However, routine monitoring may
                       be required by the Local Government. In the event of failure of the system’s land
                       application area an AES authorised person may need to follow the rejuvenation
                       procedures set out in the manufacturer/supplier’s Design and Installation Manual.

                   17. Where a system installed at a site, has been found not to operate satisfactorily during
                       its service life, and as a result requires modification to achieve the required
                       performance requirements, in particular, water quality limits, the installed system is to
                       be modified accordingly. Any modifications including any of the supplier’s rejuvenation
                       procedure outcomes must be recorded on the service report.

                   18. Permitted use of the effluent is for sub-surface absorption only.

                   19. Each system must be supplied with —

                        (a)    a copy of this Treatment Plant Approval document;
                        (b)    details of the system;
                        (c)    instructions for authorised persons for its installation;
                        (d)    a copy of the owner’s manual to be given to the owner at the time of installation;
                               and
                        (e)    detailed instructions for authorised service personal for its operation and
                               maintenance.




                                                                                           Treatment Plant Approval
                                                                                    Approved by: Lindsay Walker
                                                                                    Delegated Authority
                                                                                    Department of Housing & Public Works

Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021

Page 16

                   20. At each anniversary of the Treatment Plant Approval date, the supplier must submit to
                       the Chief Executive a list of all systems installed in Queensland during the previous 12
                       months. Where the Chief Executive is notified of any system failures the Chief
                       Executive may randomly select a number of installed systems for audit. The Chief
                       Executive will notify the supplier’s nominated NATA accredited laboratory which
                       systems are to be audited for BOD5 and TSS. The sampling and testing of the
                       selected systems, if required, is to be done at the supplier’s expense. The following
                       results must be reported to the Chief Executive;

                        a) Address of premises;
                        b) Date inspected and sampled;
                        c) Sample identification number;
                        d) BOD5 for influent and effluent; and
                        e) TSS for influent and effluent.
                   21. The Chief Executive may, by written notice, cancel this approval if the
                       manufacturer/supplier fails —
                        a) to comply with one or more of the conditions of approval; or
                        b) within 30 days, to remedy a breach, for which a written notice been given by the
                           Chief Executive.
                   22. This approval may only be assigned with the prior written consent of the Chief
                       Executive.

                   23. This approval expires on 1 January 2024 unless cancelled earlier in accordance with
                       paragraph 21 above.




                Lindsay Walker
                Director                                                                                                      Level 7,
                                                                                                            63 George Street Brisbane
                Plumbing, Drainage and Special Projects
                Building Legislation and Policy                                                      GPO Box 2457, Brisbane Qld 4001

                 Date approved:        03 March 2020                                                     Telephone +61 7 3008 2557
                                                                                                           Facsimile +61 7 3237 1248
                                                                                                         Website www.hpw.qld.gov.au

                                                                                                                 ABN 61 331 950 314




                                                                                          Treatment Plant Approval
                                                                                     Approved by: Lindsay Walker
                                                                                     Delegated Authority
                                                                                     Department of Housing & Public Works

Document Set ID: 21598877
Version: 1, Version Date: 30/08/2021