5.3.2 Initial and Continuing Losses
Initial and continuing losses were approximated based on calibrating the pre-development flows
within XPSTORM to be comparable with Rational Method results. Refer to Table 5-4 below for the
adopted initial and continuing losses.
Table 5-4 – Adopted Initial and Continuing Losses
Designation Initial Loss Continuing Loss
Impervious Areas 0.0 0.0
Pervious Areas 10.0 2.6
5.3.3 On-site Detention
In order for the post-development stormwater discharge conditions to match the pre-development
conditions, it is proposed to incorporate a series of on-site above ground detention tanks with a
maximum storage volume of 27.5kL. The detention tanks will be located adjacent to each roof
catchment within the site.
The proposed OSD tanks will typically have the following properties:
• Available detention depth above reuse component = 1.420 m;
• Low flow orifice diameter = 0.070 m;
• High flow pipe diameter = 0.150 m;
• High flow pipe elevation above reuse component = 1.135 m;
• Total required detention volume = 23.5 kL; and
• Total provided detention volume = 27.5 kL.
The detention tanks will be designed to contain all flows up to a Q20 storm event from the roof
catchment and will mitigate flows at or less than pre-development for all flows up to a Q100 storm
event.
Refer to Appendix F for the Concept Siteworks and Drainage Plan which details the proposed on-
site detention system.
5.3.4 Comparison of Peak Flows at Lawful Point of Discharge
The pre-development and post-development mitigated peak mean/median flow rates were
compared for the catchment and are shown in Table 5-5 below.
Site Based Stormwater Management Plan
Proposed Townhouse Development at 5 Pearl Street, Cooroy