RESPONSE TO DEVELOPMENT APPLICATION

ENERGEX Limited acting as an advice agency under the Integrated Planning Act
1997, response to the proposed development is:

 

This application be refused for the following reasons: or

 

 

 

x

 

This application be approved in principle subject to the following conditions:

 

When considering any future works either on ENERGEX easements or in the vicinity of
ENERGEX assets, please be aware of the following general conditions:

Any further proposal for works or development on the easement including those
involving changes in ground level and retaining wall designs around towers and
poles must have prior approval from ENERGEX. Please submit the relevant civil
design to the Principal Mains Design Engineer for approval.

Satisfactory clearance from any proposed structure to the existing (and/or future)
electricity wires must be maintained in accordance with the Electrical Safety
Regulations 2002.

No civil works are to occur within 5 metres of any part of a tower base, pole or stay.
Trenches in excess of 5metres in depth must have a minimum horizontal
séparation, from the trench to any tower base or pole, at least equal to the trench
depth. Natural ground levels on the easement should not be disturbed without
ENERGEX approval.

ENERGEX trenching requirements for the installation of pipe include full depth
shoring of trench sides for 5 metres either side of a structure. The trench is not to
be left open overnight and backfill is to be compacted in 150mm layers in the
immediate vicinity of the structure.

Final ground levels should slope gently to the edge of the easement, surrounding
area or kerb such that pooling of water on the easement is avoided and conductor
ground clearances are not decreased.

10 metres clear access must be provided around all towers and pole structures.
Stockpiling of spoil on the easement is prohibited.

Lighting structures are not permitted in the easement without prior written consent
of ENERGEX.

Underground services should be kept to the outer edge of the easement and any
crossing of the easement should be clearly marked. Please submit the relevant
design drawings to the Principal Mains Design Engineer for review. The
identification, assessment and mitigation of any possible hazards in the service due
to electromagnetically induced voltages, is the responsibility of the developer.

Any cut in the vicinity of a structure or between a structure and the road kerb will
need to be stabilised by a retaining wall. The retaining wall design and location is
to be submitted to ENERGEX for approval.

Reference: HBD313709 - (710/23/11 P23-02) — L1167
Log in to download the original file

EGX_PROD_n6829410_191_Hollett_Road,_Noosaville_L53_SP163571.pdf · 3.0 MB (large file)

Large file: the download may take up to a minute.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.