21598 - Glenridge Drive - STAGE 1 -Response to info request

Attached to the e-mail Response to information request - OPW22/0163 - Email 2 of 2 - Glenridge Drive -.

of 2

Page text shows just the words. Original shows the document exactly as it was published.

     3. Issue

The proposed table drain works along the frontage of 60 Glenridge Drive drains towards the north-west.
Council are concerned that the overland flow within the table drain will pool on the south-eastern side of
the existing driveway crossover due to the lack of drainage under the crossover.

Council recognise that as part of the Higher Order Approval, the developer and landowner came to an
agreement that the existing driveway crossover (and internal driveway) would be reconstructed to
accommodate for the proposed works.

Information Required

Provide an additional driveway design plan. The driveway design plan must be prepared by a suitably
qualified person (RPEQ – Registered Professional Engineer of Queensland) and include, but not be
limited to:
a.       a design generally in accordance with Noosa Council’s standard drawing RS-056 and any
         associated addendum;

b.      demonstrate that the overland flow within the proposed free draining table drain will not pool
        along the southern frontage of 60 Glenridge Drive.

Response

There is no table drain on the south eastern side of the existing driveway crossover. The road is
constructed on an embankment in this location and run off generally sheet flows from the road reserve
into lot 8 and ultimately to the gully to the south. There is a minor depression (150mm deep) adjacent to
the existing driveway crossover which we have shown as being filled to eliminate the potential of any
water ponding in this area. Note that there is insufficient depth to install a pipe under the existing
crossover.

I can confirm that there is no agreement between the developer and landowner to reconstruct the existing
driveway crossover and internal driveway. Notwithstanding we agree that the crossover needs to be
upgraded in order to comply with condition 51 of the higher order approval. As such these works have
been added to our drawing C003.

We trust the above is satisfactory. Should you have any queries regarding this matter please contact the
undersigned.

Yours faithfully




Doug Reynolds
Principal Civil Engineer
07 5449 9600 | [email protected]
TOD Consulting Engineers




                                                                                                    Page 2 of 2
                                                                                         Tod Job Number: 21598
Log in to download the original file

21598 - Glenridge Drive - STAGE 1 -Response to info request.pdf · 199 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.