Attachment 4 - Building Certifier Advice & Flow Pressure Test Results.pdf

of 5

Page text read automatically using OCR, there may be inaccuracies

BP24/1073




11/02/2026

Cayas + Ward
Suite 2, 19-25 Musk Avenue
Kelvin GroveQLD4059




RE: 37-49 Noosa Drive, Noosa Heads QLD 4566
Lot 0 on SP152217


Dear Sir/Madam,

Bartley Burns building certifiers have provided initial advice for the proposed building work to the Noosa Reef
Hotel located at 37-49 Noosa Drive, Noosa Heads.

As part of the initial advice, it has been determined that the existing tavern and the proposed future works are
required to be protected by a compliant fire hydrant system in accordance with the National Construction
Code 2022 Volume 1 Part E1D2, AS2419.1 and the Queensland Fire Department’s operational requirements.

Following site investigations and testing of the existing fire hydrant system, it was determined the existing system
does not currently achieve compliance with the above-mentioned criteria. It is believed the existing fire hydrant
system will require alterations/rectification works to be undertaken to achieve the required level of compliance.

A suitably qualified hydraulic consultant will be required to confirm how to best achieve compliance.


Yours Sincerely




Toby Spencer A1064976




                                 Bartley Burns Pty Ltd  ABN 98 482 284 007
           Unit 10 / 16 Metroplex Ave, Murarrie Q 4172  1300 051 189  [email protected]


[OCR of page images]
BP24/1073

“es bartley
weoUrNS

building certifiers & town planners

 
 

11/02/2026

Cayas + Ward
Suite 2, 19-25 Musk Avenue
Kelvin GroveQLD4059

RE: 37-49 Noosa Drive, Noosa Heads QLD 4566
Lot 0 on SP152217

Dear Sir/Madam,

Bartley Burns building certifiers have provided initial advice for the proposed building work to the Noosa Reef
Hotel located at 37-49 Noosa Drive, Noosa Heads.

As part of the initial advice, it has been determined that the existing tavern and the proposed future works are
required to be protected by a compliant fire hydrant system in accordance with the National Construction
Code 2022 Volume 1 Part E1D2, AS2419.1 and the Queensland Fire Department’s operational requirements.

Following site investigations and testing of the existing fire hydrant system, it was determined the existing system
does not currently achieve compliance with the above-mentioned criteria. It is believed the existing fire hydrant
system will require alterations/rectification works to be undertaken to achieve the required level of compliance.

A suitably qualified hydraulic consultant will be required to confirm how to best achieve compliance.

Yours Sincerely

Toby Spencer A1064976

Unit 10 / 16 Metroplex Ave, Murarrie Q 4172 * 1300 051 189  [email protected]

Log in to download the original (Attachment 4 - Building Certifier Advice & Flow Pressure Test Results.pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.