Attachment 4 - Building Certifier Advice & Flow Pressure Test Results.pdf
Australian Fire Services Testing # 11647.3
www.firetesting.com.au PH: 1800 347 383
Double head Pillar Hydrant located on Eastern side of site is completely covered by vegetation
WS
Sprinkler System Flow & Pressure Testing
Sprinkler Requirements 905l/m (15.1l/s) @185kPa
DESIGN REQUIREMENTS AS.2118.1 1999
BUILDING OCCUPANCY CAR PARK
HAZARD CLASSIFICATION OH.2
STORAGE HEIGHT n/a
DISCHARGE: DENSITY 5 mm/mim/sq.m
AREA OF OPERATION 144 sq.m.
MAX AREA / SPRINKLER 12 sq.m
SPRINKLER DATA 1Sdia K=8
FLOW & PRESSURE REQD Basement 2
MOST REMOTE 905 I/m © 185 kPa
MOST FAVOURABLE
HEIGHT OF HIGHEST SPRINKLER ABOVE CONTROL VALVES — 4.5 m.
Maximum flow at Sprinkler valve set