Information Request MCU24 0085
Issue – Retaining Wall
The sections of retaining structures shown in the below extract require further justification.
Figure 3 – Sections of retaining wall in question extracted from Barlow Shelley’s Bulk Earthworks Plan
(C101, Rev. A)
Figure 3 shows the rear portion is hatched for ‘cut’ which Council believes to be an error, as
Section A of Barlow Shelley’s Earthworks Sections (C102, Rev. A) does not indicate a cut and
annotations suggest the existing levels are to be retained.
Information Required
6. Clarify the intent of the sections of retaining wall highlighted in Figure 3 and comment
on the overall intent of the rear portion of the site with respects to earthworks (cut). Any
commentary must be prepared by a suitably qualified person (RPEQ) and include
amended plans where necessary.