3_Minor Change Letter
Proposed Change
The proposed change seeks to alter the approval to remove two (2) parking spaces to
accommodate the relocation of fire pumps within Basement 1.
Medihub is currently operating under a conditional certificate of occupancy for non-
conformance with the fire pumps and electrical switchboard located together in the same
room. This was despite it being approved by the QFES and Building Certifier in this location
during the detailed design of the project but not approved by the QFES at the final inspection.
The Development has until 25 Feb 2025 to rectify the non- conformance to relocate the fire
pumps immediately outside the room into the adjoining carparks. A copy of this conditional
Certificate of Occupancy is attached for information. The resulting impact of these works is
the removal of two parking spaces for carparking as detailed below.
We note that if these works are not done the development will not be able to continue
operating until completed.
Figure 1: Updated plans removing two parking spaces adjoining pump room
The above change is supported by the attached technical note from SLR Traffic Consulting
supporting the removal of the parking spaces. The technical note determines that whilst
moving the fire pumps will result in a net loss of parking spaces, this loss is not expected to
introduce new impacts or increase the severity of known impacts from a transport
perspective. The proposed changes will not result in a substantially different development to
that previously approved from a traffic engineering perspective.
In the interest of completeness, several GIA items agreed during construction of the building
have been included in this application. These items include: