Information Request OPW26 0055 [As Published]
Officer: Daniel Epps
Direct Telephone: 07 53296223
Our Reference: OPW26/0055
Your Reference: 260104
19 May 2026
GJ Powell
C/- URBN Town Planning Pty Ltd
PO Box 81
BUDERIM QLD 4556
[email protected]
Dear Sir/Madam,
Information Request
Planning Act 2016
I refer to your application and advise that Council requires further information to satisfactorily
assess the proposal.
1. APPLICATION DETAILS
Application No. OPW26/0055
Proposal: Stormwater
Street Address: 85 Gympie St Tewantin Qld 4565
Real Property Description: Lot 51 SP 260161
Planning Scheme: Noosa Plan 2020 (20 March 2026)
2. INFORMATION REQUIRED
The information requested is set out below:
Item – Connection of Downpipes
Lindsay’s Operational Works Stormwater Plan (22-0416-F22, Rev. E) dated 10 April 2026
details that the existing downpipes will be connected to the new drainage pipe.
It is unclear to Council if these downpipes will connect directly to the new sealed pit or to the
captive relief line.
Council suggests that the head losses from connecting to the captive relief line wouldn’t allow
flows from the downpipes to discharge to Gympie Street and would discharge via the level
spreader to the downstream property.
Information Required
1. Provide additional clarifying if the existing downpipes will connect directly to the new
sealed pit. The additional detail must be prepared by a suitably qualified person (RPEQ).
ABN 97.969.214.121 PO Box 141
noosa.qld.gov.au Tewantin QLD 4565
[email protected] 07 5329 6500
Page 1 of 2
Document Set ID: 24802629
Version: 2, Version Date: 19/05/2026
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 1 page
Page 2
Item – Hydraulic Calculations
No hydraulic calculations have been provided as referenced in Lindsay’s Operational Works
Stormwater Plan (22-0416-F22, Rev. E) dated 10 April 2026.
Information Required
2. Provide hydraulic calculations demonstrating the charged line is functional for the entire
roof area.
Item – Level Spreader
Provide comment from a suitably qualified person (RPEQ) addressing and certifying how the
level spreader complies with Section 3.9 of QUDM whereby there is no ultimate nuisance
caused to the downstream neighbour.
3. DUE DATE FOR RESPONSE TO INFORMATION REQUEST
The due date for providing the requested information is 18 August 2026. Email your response
to [email protected]. Please advise Council of your response to this information request
in accordance with section 13 of the Development Assessment Rules.
If you do not provide a response before the due date, it will be taken as if you have decided
not to respond to the information request and Council will continue with the assessment of
your application.
4. OTHER DETAILS
You can follow the progress of this application online at www.noosa.qld.gov.au. The “Online
Services” page can be accessed via "Quick Links" on the left hand side of the screen.
Should you have any further queries in relation to the above, please do not hesitate to contact
me on the number above.