Log in to see the plans as drawn 3.4 Mitigated Scenario
When comparing the peak flows in the existing and developed scenario, increases in
the peak discharge occur at Outlets 2 and 3. As a result a detention system will be
required to be implemented in order to demonstrate non-worsening from the site.
All modeling parameters remain consistent between the developed and mitigated
scenarios, with the addition of a detention system within sub-catchments C and D.
Due to site constraints the detention system has been modeled as a
square/rectangular underground detention system. The storage details included
within the model are provided in Table 18.
Table 18: Storage and Outlet Details of Detention System
Sub-Catchment Storage Storage Height Outlet Pipe
Peak 100yr WSL (m)
Location Volume (m3) (m) Diameter (mm)
SUBC 100 1.0 375 0.87
SUBD 100 1.0 250 0.99
A comparison of the peak flows between the existing, developed and mitigated
scenarios are presented below in Table 19. It can be seen that non-worsening of
peak flows are achieved at each outlet to the site.
Table 19: Comparison of Existing, Developed and Mitigated WBNM Outlet Peak Flows
Existing Peak Developed Peak Mitigated Peak
Reduction
Flow (m3/s) Flow (m3/s) Flow (m3/s)
Outlet 1
2 0.73 0.69 0.69 -0.04
10 1.02 0.95 0.95 -0.07
100 1.40 1.31 1.31 -0.09
Outlet 2
2 0.14 0.19 0.14 0.00
10 0.19 0.26 0.19 0.00
100 0.26 0.35 0.25 -0.02
Outlet 3
2 0.07 0.13 0.07 0.00
10 0.10 0.18 0.10 -0.01
100 0.14 0.25 0.13 -0.01