Figure 2: Aerial image showing existing deck (Nearmap, accessed June 2022)
Item 4
Submit amended plans that remove decks that are above ground level situated on the
boundary (and achieve a 6m rear setback). Any structure above ground level must meet the
setback requirements. The position of the decks does not comply with AO9.3 of the Low
Density zone code or PO9 a), b), c), d) or e).
Response: The deck to the south of the pool has been setback 0.5m from the southern side boundary.
Landscaping is proposed to provide privacy screening to adjoining residents. We note that the
Information Response previously submitted included a letter of support from the southern adjoining
neighbour, who acknowledged and provided support for the proposed encroachments.
Item 5
Provide amended plans that remove stairs outside of the property boundary.
Response: The Proposal Plans prepared by Aboda Design Group have been revised to remove the stairs
outside of the property boundary.
Item 6
Provide a site specific geotechnical report and site stability assessment for the site and
development. The report must include, but not be limited to:
a. recommendations for the construction and operational phases of the development to
ensure the stability of the subject site and the adjoining properties for the longer
term; and
b. details of the proposed structural solution to protect the structural integrity of the
existing sewer infrastructure running along the site’s eastern boundary.