REFERENCED DOCUMENT 100 Year Boundary for the Existing Floodplain Condition - REC13/0095
No. 55 Lake Macdonald Drive Cooroy Stage 2 Short Duration Culvert Calculations for Access for Lots 5, 6, & 7. Lot 7 Culvert: Catchment A (see Plan 1225-25). Catchment Area A = 1.653 ha Q 1 00 rainfall event FCIA = 1/360 x 0.94 x 155 x 1.653 0.67 m3/s Cross Road culvert, 1 X 900x300 RCBC with outlet control. Maximum HW = 103.475(upstream side of dwy) 102.875(RCBC invert) - = 0.6m ke 0.4, A = = 0.908 x 0.305 = 0.277 sqm, L = 4.88m de = 0.467(QIB)2/3 = 0.467 X (0.51/0.9)2/3 = 0.32m TW = xsect DIS of2/A (see attached PCDrain Calculation sheet) = 0.232m (de + 0)/2 = (0.32 + 0.305)/2 = 0.313m So ho is greater of 0.232 and 0.313 = 0.313m HW = H + ho - LSo 0.6 = H + 0.313 - 0.03 H = 0.317 From Figure 9A-5 DTMR Road Drainage Manual, Q = 0.51 m3/s Q 1 00 weir flow = Q 1 00 flow 0.67 m3Is - 0.51 m3Is piped 0.16 m3/s Weir Q100 1.7LH3/2 B = 6m 0.16 1.7 x 6 x H312 H (0.16I (1.7 x 6)i/3 0.063m Adopt weir capacity for a 0100 of 0.67 m3/s with 6m width, 0.063m upstream depth Hand 900x300 RCBC. Note culvert more than adequate tor Q5 without overtopping as Q5 = 0.32 m3/s vs culvert capacity of 0.51 m3Is.