Introduction
The purpose of this report is to evaluate and design a suitable on-site treatment system
and disposal area in accordance with AS 1547 – 2012, the Queensland Plumbing and
Wastewater Code, The Environmental Protection Act, The Plumbing and Drainage Act and
Local Council requirements. The report relates exclusively to the above site and the
proposed and or existing buildings shown on the plan only. All measurements and levels
shown are as accurate as possible with the information provided these are to be used for
locating the onsite effluent disposal system only.
Site Description
Weather Conditions Showers
Slope 0-12%
Slope Stability N/a
Vegetation Grassed, scattered mature trees
Flooding Present
Watercourses Dams
Site exposure Sun & wind
Salinity Nil
Surface condition Nil cracks, seepage, or compaction
Boulders & Rock outcrops Nil
Will water from uphill traverse the area Yes
Water table Not encountered
Soil Category (AS1547-2012 Table M1)
Boreholes 0-200mm 200-600mm
BH 1, BH2 Cat 4 Cat 6
FILL Silty Sand, Grey FILL Silty Clay, Grey/Brown
Perc Result: 0.07 Clay Loams Medium-heavy clays
Weakly Structured Moderately structured
0.12-0.5m/d <0.06
2 of 6