ORDINARY MEETING MINUTES                                                            17 MAY 2018


    Spill Containment
    Fuel Dispensing Area (Higher Risk Area)
    50   Spill capture capacity must be sufficient capacity to hold a volume equivalent to at least
         the largest tanker compartment likely to be delivering fuel to the site (>8kL)
    51   In the event of failure of any part of the system, power failure or where the spill
         compartment or hydrocarbon chamber exceeds capacity, no petroleum product shall
         be released beyond the property boundary.
    Stormwater quality discharge criteria.
    52   Stormwater quality discharge must be to the following minimum standards:
         i.       <5ppm (mg/L) Total Petroleum Hydrocarbons (TPH)
         ii.      ≥80% reduction in Total Suspended Solids (TSS) heavy oils & metals
         iii.     ≥90% reduction in gross pollutants
    53   There must be no high-flow bypass. 100% of captured liquids to be treated.
    Uncovered Forecourt Area (Medium Risk Area)
    54   In the event of failure of any part of the system, power failure or where the spill
         compartment or hydrocarbon chamber exceeds capacity, no petroleum product shall
         be released beyond the property.
    55   Stormwater quality discharge must be to the following standards:
         i.       <5ppm (mg/L) Total Petroleum Hydrocarbons (TPH)
         ii.      ≥80% reduction in Total Suspended Solids (TSS)
         iii.      ≥90% reduction in gross pollutants
    56   High-flow bypass / first-flush capture design capacity must be designed to meet the
         defined discharge criteria during a storm up to the 3 month ARI-6 minute design rainfall
         event without surcharging or backing up the drainage system.
    Submit Certification
    57   Prior to the commencement of the use certification shall be provided to Council
         demonstrating that the system has been installed in accordance with the above.
    Noise
    58   Mechanical plant and equipment, a/c units, motors, refrigeration equipment,
         compressors, pumps etc. on site must be located within the building or suitably
         provided with noise reduction measures and located to prevent a noise nuisance
         beyond the boundary of the site and to not exceed the levels specified in Table 1.
                                                Table 1
                                 NOISE LIMITS AT A SENSITIVE RECEPTOR
              PERIOD          Noise level at noise sensitive place measured as the adjusted
                              maximum sound pressure level (Lamax, adj,T)
              7am – 6pm       Background noise level (LAbg,T) plus 5 dB(A)
              6pm – 10pm      Background noise level plus 5 dB(A)
              10pm – 7am      Inaudible
                                  NOISE LEVELS AT COMMERCIAL PLACE
              PERIOD          Noise level at a commercial place measured as the adjusted
                              maximum sound pressure level (Lamax, adj,T)
              7am – 6pm       Background noise level (LAbg,T) plus 10 dB(A)
              6pm – 10pm      Background noise level plus10 dB(A)
              10pm – 7am      Background noise level plus 8 dB(A)
    59   When requested by Council, a Noise Impact Assessment Report (NIAR) showing
         monitoring and recording of noise levels must be undertaken to investigate any
         complaint (other than a frivolous or vexatious complaint) caused by noise emissions
         from operations at the premises.


                                                                                   Page 27 of 30
Log in to download the original file

2018-05-17 Ordinary Meeting Minutes(PDF, 653KB).pdf · 669 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.