Building Approval (Applicant) v1
Attached to the e-mail Change to DA (GIA) - MCU16/0140.02.
Ian Maddigan
Ph: 07 5479 7003
Submission No: S00025157
Our Ref: 17-01628
Your Ref: BA # 20190203/DA # MCU16/0140.01
26 June 2019
Ms Tiffany Logan
Moneta Cassa 2 Pty Ltd atf T & M Investment Unit Trust
PO Box 674
NOOSA HEADS QLD 4567
Dear Sir/Madam
Queensland Fire and Emergency Services (QFES) has assessed the referral for the Building
Development Application for the premises listed below.
This report provides QFES advice to the assessment manager when considering the approval for
the application, regarding the degree to which the proposed building work meets the operational
requirements of QFES referral jurisdictions identified in the Planning Regulation 2017 (PR 2017).
• Where a Deemed to Satisfy (DTS) component is identified as being 'Suitable', it indicates:
within the parameters of QFES referral jurisdiction, the special fire service appears to meet
QFES operational requirements.
• Where a DTS component is identified as being 'Not Suitable' it indicates: within the
parameters of QFES referral jurisdiction, the special fire service does not comply with the
requirements of the applicable Codes or Standards or does not meet QFES operational
requirements for reasons identified.
• Where a Performance Solution (PS) component is identified as being 'Suitable' it indicates:
QFES accept, or has no comment on, the solution provided in the Fire Engineering Report.
• Where a PS component is identified as being 'Not Suitable' it indicates: QFES does not
accept the solution and/or the justification provided in the Fire Engineering Report for
reasons identified.
QFES advice should not be construed as verification that the proposed building work complies with
the requirements of applicable Codes and Standards. The assessment manager is advised that
assessment benchmarks within the PR 2017 must be addressed and documented in the Decision
Notices. QFES appeals may be instigated against these benchmarks insofar as they relate to
QFES referral jurisdictions.
Photoelectric smoke alarms save lives Version 1 Page 1 of 4
North Coast Region - Community Safety Operations
2 Enterprise Street, Kunda Park Queensland 4556 Telephone +61 7 5479 7003
PO Box 6139, Maroochydore Bc Queensland 4558 Facsimile +61 7 5479 7032
Website www.qfes.qld.gov.au ABN 93 035 163 778
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalSearchable page text hides email addresses. Original files are unchanged and may show email addresses.
Full text of the other 3 pages
Page 2
Building B
Storage First
42 Hoffman Drive
NOOSAVILLE QLD 4566
QFES is to be notified to inspect and test all referral agency aspects under the Building Regulation
2006.
QFES request that our response be treated as a 'properly made submission'.
Where applicable, an invoice for fees for this assessment will be forwarded to the person
nominated as the billing customer at the time of application.
The invoice is payable within 14 days from the date of the invoice.
If you have any questions regarding this report please contact the Building Approval Officer
nominated below.
Yours sincerely
Ian Maddigan
Building Approval Officer
Enc.
Photoelectric smoke alarms save lives Version 1 Page 2 of 4
North Coast Region - Community Safety Operations
2 Enterprise Street, Kunda Park Queensland 4556 Telephone +61 7 5479 7003
PO Box 6139, Maroochydore Bc Queensland 4558 Facsimile +61 7 5479 7032
Website www.qfes.qld.gov.au ABN 93 035 163 778
Page 3
Deemed To Satisfy/Reassessment/Building Approval
Job Details
Job Name: New Building
Address: 42 Hoffman Drive, NOOSAVILLE QLD 4566
Building Details
Class: 7b Floor Area: 2322m² Effective Height: 3.7m
Size of Largest Fire Compartment: 1000m² Rise in Storeys: 2
Legislation: 01-05-16 (BCA2016)
Drawings
Dwg11.0416.1GPage1G Dwg11.0416.2GPage2G Job190523-H-001-PR-B
Deemed To Satisfy Components
Type of Special Fire Service Assessment
Fire Mains (including booster and/or pumps) Suitable
• achievement of specified performance
• location and suitability of booster connections and enclosures
• location and suitability of internal and roof hydrants and external
hydrants including fire separation from adjacent buildings
• provisions for hard standing for fire appliances
Comments:
Required flow and pressure is 20 L/s @ 350 kPa (unassisted) and 20 L/s @ 700 kPa (boosted).
● Certification indicating compliance of system performance with AS 2419 will be required upon
completion of the project.
● A flow report indicating the available flow of water from the required number of hydrant outlet
is to be provided prior to the final inspection.
● The QFES requires block plans for hydrant booster cabinet to be:
- Etched, engraved or printed on metal or plastic that is suitable for installation in an outdoor
location (paper enclosed within a plastic or laminated cover is not acceptable)
- A minimum of A3 in size
- Mechanically secured in the requiring location
- Correctly orientated to the building/site, and
- Meet all of the other requirements of Australian Standard 2419.1- 2005 including the features
identified on the plan.
● Hydrant locations appear satisfactory for the open plan design only - distances will be
checked upon final inspection to ensure compliance.
Fire Detection and Alarm Systems (Detection System) Suitable
Page 3 of 4 Version 1 QFES Job No: 17-01628
Page 4
• achievement of specified performance of detection and alarm
systems
• location and operation of main fire indicator panel, sub-indicator
panels, mimic panels, local alarm bells and directional signs
• suitability of nominated types of detection in all areas, and the
location of manual call points
• suitability of weather protection, accessibility and lighting of
equipment
Comments:
● A Fire Detection and Alarm System is required to be installed in accordance with BCA & AS
1670.1.
● Compliance certification including 'As Installed' drawings, Commissioning test report, Installers
Statement and/or Form 16 is to be provided upon inspection.
● From previous experience of Building A it was assumed the doors located within the FRL
walls are to held open with magna latches which are to be operated via a detection system.
Certification is required for each Special Fire Service, this will be required prior to or at the time of
inspection.
Page 4 of 4 Version 1 QFES Job No: 17-01628