B - Code Compliance
Waterways Works Code
i. the gangway for a single berth pontoon has a
minimum width of 900 millimetres;
ii. the gangway for a multiple berth pontoon has a
minimum width of 1.2 metres if fitted with one
handrail and 900 millimetres if fitted with a
handrail on each side;
iii. the primary walkway to multiple berth pontoons
has a maximum width of 1.5 metres; and
iv. the maximum width of a gangway is 1.5 metres.
AO13.7
In Noosa Sound, where quaylines are set, a jetty or
pontoon does not extend into the watercourse beyond the
quayline;
OR
AO13.8
Where no quaylines are set, the maximum distance a jetty
or pontoon extends into the watercourse is 10m, unless it
can be demonstrated that a distance in excess of 10m is
essential to safely access a vessel from the jetty.
Editor’s Note— The quayline is measured from real property boundary
except where a relevant State Government Authority permits the
measurement from High Water Mean Springtide.
AO13.9
All attachments to jetties, including but not limited to boat
lifts, jetski cradles, floating berths and floating pontoons
are located within the quay line.
AO13.10
Pontoons are structurally capable of sitting on the sand
bed. Rollers and bracing should account for this situation.
AO13.11
Jetties and pontoons are free standing and do not rely on
connecting to any revetment wall or other structure.
Design, Construction and Safety for Boat Ramps - prescribed tidal works outside Noosa Waters Estate