Log in to see the plans as drawnOilSET-1000 Oil Separator Alarm Device D15383Be
Installation and Operating Instructions
3 OPERATION AND SETTINGS
The OilSET-1000 alarm device is initialized at the factory.
The operation of the alarm device should be checked always after the
installation.
Functionality test 1. Immerse the probe into water. The device should be in normal mode.
2. Lift the probe up in air or oil. An Oil alarm should be generated (see
chapter 3.1 for more detailed description).
3. Immerse the probe back into water. The alarm should go off after a
delay of 5 sec. Clean up the probe if necessary before placing it back
into the oil separator.
A more detailed description of the operation is provided in chapter 3.1.
If the operation is not as described here, check the factory settings
(chapter 3.2.) or contact a representative of the manufacturer.
3.1 Operation
The operation of a factory-initialized OilSET-1000 is described in this
chapter.
Normal mode – no alarms SET/DM3D probe is totally immersed in water.
Mains LED indicator is on.
Other LED indicators are off.
Relays 1 and 2 are energized.
Oil alarm SET/DM3D probe is immersed in oil. (The probe gives an alarm earliest
when the upper electrode is in oil and latest when the probe is totally
immersed in a non-conductive liquid, in other words it is totally away from
the water.)
Mains LED indicator is on.
Oil Alarm LED indicator is on.
Buzzer on after 5 sec delay.
Relays de-energize after 5 sec delay.
(Note. The same alarm takes place when SET/DM3D probe is in the air.)
After removal of an alarm, the Oil Alarm LED indicator and buzzer will be
off, and relays will be energized after a fixed delay of 5 sec.
Fault alarm Probe cable break, short circuit or a broken probe, i.e. too low or too high
probe signal current.
Mains LED indicator is on.
Probe circuit Fault LED indicator is on after 5 sec delay.
Buzzer is on after 5 sec delay.
The relays de-energize after 5 sec delay.
Reset of an alarm When pressing the Reset push button.
Buzzer will go off.
Relay 1 energizes.
Relay 2 will stay de-energized until the actual alarm or fault is off.
TEST FUNCTION
Test function provides an artificial alarm, which can be used to test the
function of the OilSET-1000 alarm device and the function of other
equipment, which are connected to OilSET-1000 via its relays.
Attention! Before pressing the Test button, make sure that the change
of relay status does not cause hazards elsewhere!
Copyright © 2010 6/10 We reserve the right for changes without notice