Log in to see the plans as drawnOilSET-1000 Oil Separator Alarm Device D15383Be
Installation and Operating Instructions
7 TECHNICAL DATA
OilSET-1000 control unit SET/DM3D probe
Dimensions 175 mm x 125 mm x 75 mm (L x H x D) Control unit Labkotec Oy’s LevelSET S and SET –
control units
Enclosure IP 65, material polycarbonate
Principle of operation Measurement of conductivity
Ambient temperature -25 ºC…+50 ºC
Enclosure IP68, materials: AISI 316 and PVC,
Supply voltage 230 VAC ± 10 %, 50/60 Hz NBR, PA
Fuse 5 x 20 mm 125 mAT (EN 60127-
2/3) Cable Fixed, oil resistant and shielded
The device is not equipped with a mains instrumentation cable 2 x 0.75 mm2.,
switch standard length 5 m. Can be delivered
with a customized cable, max. length of
Power consumption 2 VA a fixed cable 15 m. The cable can be
extended if necessary. Max. load 75 Ω.
Probes One SET probe (SET/DM3D)
Temperature range
Max. impedance of the 75 Ω.
Ambient 0 ºC…+0 ºC
current loop between the
Safety -30 ºC…+60 ºC
control unit and a probe
Signal Digital and analog 7 mA / 13 mA
Relay outputs Two potential-free relay outputs
250 V, 5 A, 100 VA
Supply voltage 8 V…16 V DC
Operational delay 5 sec or 30 sec.
Relays de-energize at trigger point. Cable Fixed oil resistant PVC cable 3 x 0,5
Operation mode selectable for increasing mm2, standard length 5 m.
or decreasing level.
EMC
Electrical safety Emission EN 61000-6-3
EN 61010-1, Class II , CAT II / III
Immunity EN 61000-6-2
Insulation level 375V (EN 50020)
Ex-classification II 1 G Ex ia IIB T5 Ga
Probe / Mains supply voltage
VTT 09 ATEX 026X
Special conditions (X) - (Ta -30 ºC…+60 ºC)
EMC IECEx VTT 10.0001X
Emission EN 61000-6-3
Electrical parameters Ui = 16 V Ii = 80 mA
Immunity EN 61000-6-2
Pi = 400 mW Ci = 3,5 nF
Ex-classification II (1) G [Ex ia] IIC Li = 85 μH
VTT 04 ATEX 031X
Year of manufacture xxx x xxxxx xx YY x
Special conditions (X) (Ta = -25 °C…+50 °C)
where YY = year of manufacture
IECEx VTT 10.0003X
See serial number from the (e.g. 10 = 2010)
Electrical parameters Uo = 14,7 V Io = 55 mA type plate
Po = 297 mW R = 404 Ω
Characteristic curve of the
output voltage is trapezoidal
See table 2.
Year of manufacture xxx x xxxxx xx YY x
where YY = year of manufacture
See serial number from the (e.g. 10 = 2010)
type plate
Due to non-linear characteristics of the probe voltage, the interaction of
both, capacitance and inductance, must be taken into account. The
table below indicates the connecting values in explosion groups IIC and
IIB. In explosion group IIA the values of the group IIB can be applied.
Max. permissible value Combined Co and Lo
Co Lo Co Lo
568nF 0,15 mH
458 nF 0,5 mH
II C 608nF 10 mH 388 nF 1,0 mH
328 nF 2,0 mH
258 nF 5,0 mH
3,5 µF 0,15 mH
3,1 µF 0,5 mH
II B 3,84μF 30 mH 2,4 µF 1,0 mH
1,9 µF 2,0 mH
1,6 µF 5,0 mH
Lo/Ro = 116,5 µH/Ω (IIC) and 466 µH/Ω (IIB)
Table 2. OilSET-1000 electrical parameters
Figure 9. Dimensional drawing of SET/DM3D probe
Copyright © 2010 10/10 We reserve the right for changes without notice