Appendix B - New Dwelling Plans

of 21

Plans and drawings: the text below has words only, no drawings.

Log in to see the plans as drawn

Original PDF page 6, section 1. The text section number identifies this passage in the reader.

                                                                                                                                                                                       dp
                                                                                                                                                                                                                                                    dp
                (GUTTER INDICATIVE ONLY)




                                                                                                                                                                                                                     25°
                                                NOTE: ROOF PROFILE SUBJECT TO SLOPE / LENGTH OF SPAN




                                                                                                                                                                                                        25°
                                                                                                                                                                                                                                                             dp                                                       dp




                                                                                                                     100mm (<50SQM)                                         Area                                                                                  Area
                                                                                                                                                                                                                                                                                                                                                            ROOFWATER DRAINAGE GENERAL NOTES:
                                                                                                                                                                          70 m²                                                                                 80 m²                                                                                       ALL ROOFWATER DRAINAGE SYSTEMS MUST BE
                                                                                                                                                                            (2 DP'S)                                                                              (2 DP'S)                                                                                  CONNECTED TO A STORMWATER DRAINAGE
                                                                                                                                                                                                25°                                                                                                                                                         SYSTEM COMPLYING WITH NCC PART 3.1.3,




                                                                                                                                                                                                                                                                                    25°
                                                                                                                                                                                                                                                                                                                                                            DRAINAGE OR AS/NZS3500.
                                                                                                                                                                                                                                                                                                           25°
                                                                                                                                                                                                                                                                                                                                                            THE ROOF DRAINAGE SYSTEM MUST BE PROVIDED
                                                                                                                                                                                                                                                                                                                                                            WITH AN OVERFLOW TO PREVENT THE BACKFLOW
                                                                                                                                                                                                                                                                                                                                                            OF WATER INTO THE BUILDING.

                                                                                                                                                                                                                                                                                                                                                            THE AREA SPECIFIC RAINFALL INTENSITY MUST BE
                                                                                                                                                                                                                                                                                                                                                            SELECTED FROM NCC TABLE 3.5.3.1 OR FROM
                                                                                                                                                                                                                                                                                                                                                            AS/NZS3500.

                                                                                                                                                                                                                                                                                                                                                            GUTTERS AND DOWNPIPES MUST BE SELECTED




                                                                                                                                                                                        25
                                                                                                                                                                                                                                                                                                                                                            FROM NCC TABLE 3.5.3.3 OR FROM AS/NZS3500.




                                                                                                                                                                                            °
                                                                                                                                        Area                                                                                                                                                                                                                EAVES GUTTERS MUST BE INSTALLED AT A FALL NOT
                                                                                                                                                                                                                                                                                                                                                            LESS THAN 1 IN 500 WITH SUPPORT BRACKETS AT




                                                                                                                                                                                                      25
                                                                                                                                        49 m²




                                                                                                                                                                                                        °
                                                                                                                                                                                                                                                                                                                                                            1.2m MAXIMUM CENTRES.
                                                                                                                                                                                                                    Area                                                                                                                                    BOX GUTTERS MUST BE INSTALLED AT A FALL NOT
                                                                                                                                                                                                                                                                                                                                                            LESS THAN 1 IN 100, IN ACCORDANCE WITH
                                                                                                                                                                                                                   65 m²                                                                                                                                    AS/NZS3500.3.
                                                                                                                                                                                                                    (2 DP'S)                                                                                          dp
                                                                                                                                                                                                                                                                                                                                                            THE WIDTH OF VALLEY GUTTERS SHALL BE IN
                                                                                                        Area                                                                                                                                                                                                                                                ACCORDANCE WITH AS/NZS3500.3 AND NCC PART




                                                                                                                                                                                                                                      dp
                                                                                                                                                                                                                                                                                                                                                            3.5.3.4
                                                                                                        49 m²
                                                                                                                                                                                                                                                                                                                                                            REFER TO ROOF SHEETING MANUFACTURERS
                                                                                                                                                                                                                                                                                                                                                            SPECIFICATIONS FOR LIMITATIONS ON SHEET
                                                                                                                                                                                                                                                                                                                                                            OVERHANGS INTO VALLEY GUTTERS.




                                                                                                                                                             °
                                                                                                     TOTAL ROOF CATCHMENT




                                                                                                                                                          25
                                                  100mm (<50SQM)
                                                                                                           AREA 565 m²                                                                                                                                                                                                                                      THE MAXIMUM ROOF CATCHMENT AREA FOR




                                                                                                                                                                        °




                                                                                                                                                                                                                                    dp
                                                                                                                                                                     25
                                                                                                 (15 DOWNPIPES REQUIRED @40sqm/DP)                                                          Area                                                                                                                                                            VALLEY GUTTERS IS 20m2.




                                                                                                                                               °
                                                                                                                                            25
                                                                                                       17 DOWNPIPES PROVIDED
                                                                                                                                                                                                                                                                                                                                                            VALLEY GUTTERS ON ROOFS PITCHED LESS THAN
                                                                                                                                                                                         68 m²                                                                                                                                                              12.5° MUST BE DESIGNED AS BOX GUTTERS.
                                                                                                                                                                                            (2 DP'S)




                                                                                                                                                                     25
                                                                                                                                                                                                                                                                                                                                                            DOWNPIPES MUST SERVE NOT MORE THAN 12




                                                                                                                                                                      °
                                                                                                                                                                                                                                                                                                                                                            METRES OF GUTTER LENGTH FOR EACH DOWNPIPE
                                                                                                                                                                                                                                                                                                                                                            WHICH MUST BE LOCATED AS CLOSE AS POSSIBLE




                                                                                                                                                      °
                                                                                                                                                   25
                                                                                                                                                                                                                                                                                                                                                            TO VALLEY GUTTERS.
                                                                     Area
                                                                                                                                                                                                                                                                                                                                                            EAVES GUTTERS MUST BE PROVIDED WITH AN
                                                                    40 m²                                                                                                                                                                                                                                                                                   OVERFLOW SYSTEM WHERE DOWNPIPES ARE
                                                                                                                                                                                                                                                                                                                                                            LOCATED MORE THAN 1.2 METRES FROM A
                                                                                                                                                                                                                                                                                                                                                            VALLEY GUTTER.
                                                                                                   25




                                                                                                                                                                                                          °
                                                                                                                                                                                                       25
                                                                                                    °




                                                                                                                                                                                                                                                                                                                                                            TABLE 3.5.3.1 RAINFALL DURATION INTENSITY
                                                          25°




                                                                                                                                                                                                                                                                                                                                                            5 MINUTE DURATION RAINFALL INTENSITY
                                                                                                                                           Area
                                                                                                               25




                                                                                                                                                                                                                                                                                                                                                            NOOSA HEADS - 20YEARS     258mm/h




                                                                                                                                                                                           °
                                                                                                                                                                                        25
                                                                                                                °




                                                                                                                                                                                                                                                                                                                                                                          - 100YEARS 331mm/h
                                                                                                                                          68 m²                                                                                                                                                                                                             TABLE 3.5.3.2 GUTTER & DOWNPIPE SELECTION




                                                                                                                                                                                                                                                      dp
                                                                                                                                           (2 DP'S)
                                                          25°




                                                                                                                                                                                                                                                                                                                                                            FROM TABLE A & B

                                                                                                                                                                                                                                                                                                                                                            40sqm - A - MEDIUM RECTANGULAR GUTTER or
                                                                                                                                                                                                                                                                                                                                                                    D - 125mm D GUTTER
                                                                   25°         25°




                                                                                                                                                                                                                           25
                                                                                                    Area




                                                                                                                                                                                                                               °
                                                                                                                                                                                                                                                                                                                                                            FROM TABLE C

                                                                                                   44 m²                                                                                                                                                                                                                                                    90mm DIAMETER DOWNPIPE
                                                                                                    (2 DP'S)
                                                        Area                                                                                                                                                                                                                                                                                                TABLE 3.5.3.3 OVERFLOW VOLUME
                                                                                                                                                   dp
                                                                                                                                   dp




                                                       32 m²                                                                                                                                                                                                                                                                                                FROM TABLE A

                                                                                                                                                                                                                                                                                                                                                            350mm/h         12.0m GUTTER [email protected] (L/s/m) = 14.4L/s
                                                                         25°




                                                                                                                                                                                                                                                                                                                                                            FROM TABLE B

                                                                                                                                                                                                                                                                                                                                                            350mm/h - 40sqm = 3.9(L/s)
                                                                                                                                                                                                              dp




                                           dp                                                                       dp                                                                                                                                                                                                                                      USE CONTROLLED BACK GAP (SEE DETAIL)
                                                                                                                                                                                                                                                                                                                                                                     = 1.5 L/s/m x 12.0m = 18.0L/s
                                                                                                                                                                                                                                                                                                                                                            (NOT REQUIRED FOR RAKED SOFFITS)




                                                                                     © COPYRIGHT. THIS DRAWING REMAINS THE PROPERTY OF G.J GARDNER HOMES & IS PROVIDED FOR THE USE AS DESCRIBED & MAY NOT BE USED OR REPRODUCED IN WHOLE OR IN PART WITHOUT WRITTEN PERMISSION. ANY LANDSCAPING (WHEN SHOWN) ARE FOR ILLUSTRATIVE PURPOSES ONLY AND DO NOT FORM PART OF ANY CONTRACT.
                                                                                                                                                                                                                                                                                                                PAGE: SHEET SIZE: REV DRN CHK DETAILS                        DATE: I/WE HAVE CHECKED THE PLANS AND AGREE THAT
                                                                                                                                             MONTVILLE 462                              ASPECT HOUSE
                                                                                                                                                                                                                      CLIENT:                                          PROJECT: PROPOSED RESIDENCE                    6       A2      *   RW   RW   CONCEPT FLOOR PLAN                28/06/22   THEY ACCURATELY DEPICT THE HOUSE FOR
                                                                                                                                                                                                                                                                                                                                                                                                 CONSTRUCTION.
                                                                                                                                                                                                                      SANDRA & RICHARD MATHISON                                                                    JOB NUMBER:        B             AMENDED CONCEPTS                  03/08/22
                                                                                                                                              (MODIFIED)                                   PLANS                                                                       LOT 2 ON RP196994          GJGG430718                          C
                                                                                                                                                                                                                                                                                                                                          RW
                                                                                                                                                                                                                                                                                                                                          RW
                                                                                                                                                                                                                                                                                                                                               RW
                                                                                                                                                                                                                                                                                                                                               RW   AMENDMENTS - PRELIMS              29/09/22   JOB SPECIFICATION BY BUILDER TAKES
ROOF CATCHMENT PLAN                                                                          WOJTEK STAINWALD                                         RESORT FACADE                                                   DRAWING TITLE:
                                                                                                                                                                                                                                                                       1073 POMONA - KIN KIN ROAD SALESPERSON:                        D   RW   RW   AMENDMENTS - PRELIMS              01/11/22
                                                                                                                                                                                                                                                                                                                                                                                                 PRECEDENCE OVER THESE PLANS.


1 : 100                                                                                            QLD                                                                                         QLD                                                                     KIN KIN, QLD               CHRIS McNEIL                        E   RW   RW   AMENDMENTS - PRELIMS              21/12/22   OWNER SIGNED: ............................... DATE: ..........
                                                                                                                                               © COPYRIGHT EXCLUSIVE                                                                                                                                               DATE:              F   RW   RW   CONSTRUCTION DRAWINGS             04/05/23   OWNER SIGNED: ............................... DATE: ..........
                                                                                               QBCC 1285235                                    TO G.J.GARDNER HOMES                         QBCC 1257937             ROOF CATCHMENT PLAN                                                                            13/07/2023        G   RW   RW   GARAGE BIGGER                     13/07/23   BUILDER SIGNED: .............................   DATE: ..........
Log in to download the original file

Appendix B - New Dwelling Plans.pdf · 2.3 MB (large file)

The download may take up to a minute.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.