The normal structural arrangement is that the inner leaf of brickwork in Corroded guttering or downpipes can spill water to ground.
the external walls and at least some of the internal walls (depending on the • Downpipes not positively connected to a proper stormwater
roof type) comprise the load-bearing structure on which any upper floors, collection system will direct a concentration of water to soil that
ceilings and the roof are supported. In these cases, it is internally visible is directly adjacent to footings, sometimes causing large-scale
cracking that should be the main focus of attention, however there are a problems such as erosion, saturation and migration of water under
few examples of dwellings whose external leaf of masonry plays some the building.
supporting role, so this should be checked if there is any doubt. In any
case, externally visible cracking is important as a guide to stresses on the
structure generally, and it should also be remembered that the external Seriousness of Cracking
walls must be capable of supporting themselves. In general, most cracking found in masonry walls is a cosmetic nuisance
only and can be kept in repair or even ignored. The table below is a
Effects on framed structures reproduction of Table C1 of AS 2870-2011.
Timber or steel framed buildings are less likely to exhibit cracking due to AS 2870-2011 also publishes figures relating to cracking in concrete
swell/shrink than masonry buildings because of their flexibility. floors, however because wall cracking will usually reach the critical point
Also, the doming/dishing effects tend to be lower because of the lighter significantly earlier than cracking in slabs, this table is not reproduced
weight of walls. The main risks to framed buildings are encountered here.
because of the isolated pier footings used under walls. Where erosion or
saturation causes a footing to fall away, this can double the span which a Prevention/Cure
wall must bridge. This additional stress can create cracking in wall linings,
particularly where there is a weak point in the structure caused by a door Plumbing
or window opening. It is, however, unlikely that framed structures will be Where building movement is caused by water service, roof plumbing,
so stressed as to suffer serious damage without first exhibiting some or all sewer or stormwater failure, the remedy is to repair the problem. It is
of the above symptoms for a considerable period. The same warning prudent, however, to consider also rerouting pipes away from the
period should apply in the case of upheaval. It should be noted, however, building where possible, and relocating taps to positions where any
that where framed buildings are supported by strip footings there is only leakage will not direct water to the building vicinity. Even where gully
one leaf of brickwork and therefore the externally visible walls are the traps are present, there is sometimes sufficient spill to create erosion or
supporting structure for the building. In this case, the subfloor masonry saturation, particularly in modern installations using smaller diameter
walls can be expected to behave as full brickwork walls. PVC fixtures. Indeed, some gully traps are not situated directly under
the taps that are installed to charge them, with the result that water
Effects on brick veneer structures from the tap may enter the backfilled trench that houses the sewer
Because the load-bearing structure of a brick veneer building is the frame piping. If the trench has been poorly backfilled, the water will either
that makes up the interior leaf of the external walls plus perhaps the pond or flow along the bottom of the trench. As these trenches usually
internal walls, depending on the type of roof, the building can be expected run alongside the footings and can be at a similar depth, it is not hard
to behave as a framed structure, except that the external masonry will to see how any water that is thus directed into a trench can easily affect
behave in a similar way to the external leaf of a full masonry structure. the foundation’s ability to support footings or even gain entry to the
subfloor area.
Water Service and Drainage
Where a water service pipe, a sewer or stormwater drainage pipe is in the Ground drainage
vicinity of a building, a water leak can cause erosion, swelling or saturation In all soils there is the capacity for water to travel on the surface and
of susceptible soil. Even a minuscule leak can be enough to saturate a clay below it. Surface water flows can be established by inspection during and
foundation. A leaking tap near a building can have the same effect. In after heavy or prolonged rain. If necessary, a grated drain system
addition, trenches containing pipes can become watercourses even though connected to the stormwater collection system is usually an easy solution.
backfilled, particularly where broken rubble is used as fill. Water that It is, however, sometimes necessary when attempting to prevent water
runs along these trenches can be responsible for serious erosion, migration that testing be carried out to establish watertable height and
interstrata seepage into subfloor areas and saturation. subsoil water flows. This subject is referred to in BTF 19 and may
Pipe leakage and trench water flows also encourage tree and shrub roots properly be regarded as an area for an expert consultant.
to the source of water, complicating and exacerbating the problem. Poor Protection of the building perimeter
roof plumbing can result in large volumes of rainwater being concentrated It is essential to remember that the soil that affects footings extends
in a small area of soil: well beyond the actual building line. Watering of garden plants, shrubs
• Incorrect falls in roof guttering may result in overflows, as may and trees causes some of the most serious water problems.
gutters blocked with leaves etc. For this reason, particularly where problems exist or are likely to occur,
it is recommended that an apron of paving be installed around as much
• of the building perimeter as necessary. This paving should
CLASSIFICATION OF DAMAGE WITH REFERENCE TO WALLS
Approximate crack width Damage
Description of typical damage and required repair limit (see Note 3) category
Hairline cracks <0.1 mm 0
Fine cracks which do not need repair <1 mm 1
Cracks noticeable but easily filled. Doors and windows stick slightly. <5 mm 2
Cracks can be repaired and possibly a small amount of wall will need to be 5–15 mm (or a number of cracks 3
replaced. Doors and windows stick. Service pipes can fracture. Weathertightness 3 mm or more in one group)
often impaired.
Extensive repair work involving breaking-out and replacing sections of walls, 15–25 mm but also depends on 4
especially over doors and windows. Window and door frames distort. Walls lean number of cracks
or bulge noticeably, some loss of bearing in beams. Service pipes disrupted.
8894-193 Sankeys Rd-FEDERAL Page 14 of 15 19/07/2023
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Appendix E - Geotechnical site classification report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 4.6 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.