Response to Information Request - OPW12/0222
RABRlNK PTY LTD trading as
SCRC CORRESPONDENCE
John..Norden
1111111111111111111111111
80555988
& As$ociates
Structural I Civil Design Engineers
ABN 47 312 012 117
John Norden
August 27, 2012
CPEng, MIE A st, RPEQ
our ref: 12/52
Sunshine Coast Regional Council
Locked Bag 72 ’::- ..(
Sunshine Coast Mail Centre
Nambour
Q4560
--( r2:~~~;12
fj"-
Attention: Monkeith Kadhum
Dear Sir,
L
Re:SCRC REFERENCE - MK001 :MXM:OPW12/0222 INFORMATION REQUEST
-
Please find attached prints of our amended drawings 12/52-1A & 12/52-2A which
include the following amendments. All other drawings remain unchanged.
1. The new outlet pipe and associated baffle has been lowered to reduce the
baffle’s effect on through-flow and the upstream hydraulic gradient. Note that in this
section of the network, calculations indicate that pipes do not run at capacity due to
their 20% grade. The major effect on the hydraulic gradient is in the next pit
downstream, where the existing outlet pipe’s grade is dramatically reduced.
2. A grated hinged manhole lid has been incorporated in the lid of the pit. This will
allow easy access for cleaning and maintenance. The condition of the pit will be
easy to observe through the grate. Calculations indicate that this pit will not
surcharge due to it’s depth and the grade of the outlet pipe. However, should such
an event ever occur (e.g. major blockage of the 650mm diameter pipe) then the
surcharge would be relieved through the grated manhole and continue down the
existing nominated overland flow path.
3. A 25mm diameter pipe has been included to drain the standing water in the
225mm diameter pipe after a storm event. A first-flush diverter has also been added
to the stormwater collection system.
With regard to other concerns in the Information Request dated August 6,2012,the
Body Corporate will formulate an updated maintenance schedule of the pipe network
and appurtenances which will be submitted to Council as part of this operatonal
works application. Of/H):! 02.-U
E"::’ .J.6.J..lo..R: .......1.(2...... $-(:)
/ unueMal
Suite 16, Tewantin Plaza
ZWZ 9nV 61 113 Poinciana Avenue Tewantin
PO Box 205 Tewantin Q. 4565
J9lUnoC) lU~Wdo,a^aa tel 07 5449 7137
fax 07 5449 7172
[email protected]
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalFull text of the other 3 pages
Page 2
This schedule will include a weekly inspection of the modified pit and the first-flush diverter and cleaning out and general maintenance when necessary. An additional maintenance inspection will be carried out after each storm event. This will be in addition to the current maintenance schedule of the network generally which includes the gross pollutant traps installed in the distribution pit and the individual soakage pits. Please contact me if you require any further information.
Page 3
~. ..~ ~
~
30
~.
.
PIP SIZES
~/ THE NOMINATED DN225 PIPE
t
CAN BE REPLACED WITH
TWO DN150 or FIVE DNi00
10,000 L POLY TANKS
N APPROVED BASE.
PUll’ ON 225 (MIN)INTERCONNECTING
LOWARAGS". BALANCE PIPES
MODIFY EXISTING PIT SUBMERSABLE 6GS3O
-SEEDETAlL SINGLE PHASE 3kw
LID RL 100.00 (TBM)I
IL 98.00
__l /’ --
( \
r -",
\ )
I ........_/
\
\,.
I
._ ,/
..
/
/~~-,~!-
-.
l",~
-~
.
NOTE
THE APPROPRIATELY SiZeD RISING MAIN,
SHALL CONNECT THE STORAGE SYSTEM \
SYSTEM
,;II TO THE EXISTING IRRIGATION
DOWNSTREAM OF THE EXISTING RPZD
i.e. THE STORAGE SYSTEM SHALL BE
ISOLATED FROM THE MAIN WATER
RETICULATION SYSTEM UNDER ALL
OPERATING MODES.
~
RAMJljK PTY LTD T/A DRAWN DATE
NOOSA DUNES CTS 26506 John Norden
SASHTON JUNE 2012
PROPOSED .~ & Associates
ACN010163P7 SCALE
TORMWATER STORAGE
. Structural I CIvIl DesIgn engineers
Suite 18’Tewantln Plaza"
DAVID LOW WAY Poinciana Avenue I PO Box 205 DRGN.
MARCUS BEACH A Tewantln Q 4565
Ph:0754497137 Fax: 0754497172
jn_aOlntemode.on.net
Page 4
..
.... -,
~
2’
/
76 x 75 x 6 EAANGLE
~
T PL G 300 NOM CRg"
FIX TO WALL
I /
WITH ONE SIS M12
m’
150
MIN
~
z
/
STAINLESS STEEL MESH
~
"-
,
,.;’ "
.
.... ’.
’.; ......’..
".:.’, .."
;:i.{~’ ’
\.
"-
’----
~~
....:::1
900
/
.
~LAN
120
_...
~~
....:::1
~
MASS CONCRETE
(20MPa MIN)
75x 75 x.8 EAANGLE
CLEAT PL @300 NOM CRS
FIX TO WALL
WITH ONE SIS M12
TYPICAL SECTION
1:20
75x75x6EA
.t_
FULL STRENGTH
WELD
:’:;’,:1;H_RU’ST- ’S,LOCK DETAIL
’..’,.. ;.+, t,,,,,, \
1:20
. ....... ,.’, ; ," ..
....
I’ ’_
.
.
..
.
.. ’to. ",.’ .
NEW PIPE. SEAL PIT .
.,. . .....
6mmPLATE
WALL AROUND PIPE ~.. :.,’ ’:...
~
.
(CHEQUERPLATE
OR EQUIVALENT)
WITH APPROVED GROUT ,"t’ i’ : "
"
.
,
AFTER APPLYING A CONTINUOUS:’ ’." ’:’:’ :’.~’. .
.
("’.:
HYDROPHILIC SEAL TO PIPE : :. ’" ,;.
’.
.
..;; )".
PIT.’DETAIL 1:20 ":;; ~,.;:?:’<’
"
.",’.,’
,
~;::.!~r.,’,’/", .: .’ ’,’
.
NOTES’,
.
,-’ t-’.. ... ,"
’to’ f -: r .
’. .
";;
<:, ’:.::,’_ ;;..
.
1. UNLESS NOTED OTHERWISE,ALL STEELWORK SHALL BE HOT DIP GALVANIZE .
.. .
Ji,", ~,,’ ,,_,’ "J.. ,...
OR,COATED WITH A SUITABLE EPOXY SYSTEM. STAINLESS STEEL WHERE NOPyiINATEDT::"’,’:..’ .
:
’.
SHALL I:lE GRADE 316.’ .".~’ :r" :.
~ ..
’’’. .
’~"I’,..."_.:.. ",’
~’_\:"\.’ I:.. .,::-"
; .". .
_.
2..A MAINTENANCE SCHEDULE SHALL BE CREATED FOR REGULAR CHECKING ~,..::; ~’:’~.~J-’;’...: ’.: ,: .
.
!o t l~ "" "
.
.
.
AND C~eANING OF THE STORMWATER DISPOAL INCLUDING THE NEW STORAGE’SYSTEM. ,
?~ :~
~.,
i:- ....r
~ ~_ IWIRIHK PrY LTD TJA
1 f:. NOOSA DUNES CTS 26506 John Norden /t
__
I~
V’ .I,
PROPOSED V
.
& Associates
~010263’77
.~ I
."!. ,
/
1"~ 7
i~ _:;- TORMWATERSTORAGE
.]0" ’iF
..:11 .;;
DAVID LOW WAY
. Struc:tlIrell CMI DesIgn engineers
Suite 16’Tewantln Plaza-
lF
li. " A PoInciana Avenue I PO Box 205
-
l;i
)1, ~
~
MARCUS BEACH ...TewantIn Q 4685 Ph:07 54497137 Fax: 0754497172
~ c~
~ ~". In_a@Intemode,on.net
Used in these records
Response to Information Request - OPW12/0222Related documentApplication case desk ↗
About this file
- File size
- 3.6 MB (large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take up to a minute.