                                                                            Preliminary Acid Sulphate Soil Management Plan
                                                                                                            Noosa on Weyba


Table 7-3       Summary of Monitoring, Testing and Reporting

 Monitoring Type        Details

 Site Monitoring        The Contractor shall conduct regular site inspections for evidence of environmental harm
                        caused by acidic materials with particular reference to the following:
                              Scalding degradation of vegetation;
                              Presence of corroded shell;
                              Death or disease of aquatic organisms;
                              Formation of jarosite and other acidic materials;
                              Standing waters very clear or blue green indicating aluminium;
                              Invasion by acid dominated or acid tolerant species;
                              Rust coloured deposits on plants or the banks of drains;
                              Corrosion of concrete and/or steel structures in contact with soil or water;
                              Black to very dark water indicating de-oxygenation;
                              Sulphidic odours (rotten egg smell).

                        Weekly Site Inspection reports shall be prepared by the Contractor detailing the results of all
                        monitoring undertaken on site and provided to the Consultant Engineer.
 Soil Testing          The Contractor shall undertake the testing of excavated materials where potential or existing
                       ASS may have been disturbed, in accordance with the QASSIT Guidelines.
 Discharge Testing     Prior to discharge or reuse on site, the Contractor shall test stored waters to ensure compliance
                       with the discharge criteria outlined in Table 7-2. This requirement is for all temporary
                       waterbodies, including sediment basins and wick drains. All results must be included in the
                       weekly Contractor report.
 Validation Testing    The Contractor shall undertake testing of lime treated and placed fill material at a frequency of
                       at least one test per 500m3. Tests shall monitor fill for acid generating potential by SPOCAS or
                       approved equivalent such as the Chromium Reducible Sulphur Method. Laboratory
                       determination of Total Potential Acidity shall be conducted on at least 10% of the samples.
 Groundwater           The Contractor shall undertake groundwater quality monitoring around the perimeter of the fill
 Monitoring            pad area on a weekly basis during construction. Testing for the following parameters
                              pH;
                              Groundwater Depth;
                              Iron;
                              Aluminium; and
                              Cl/SO4 ratio.
 Surface Water         The Contractor shall undertake monitoring of any temporary surface waters on a weekly basis
 Monitoring            during construction. Testing for the following parameters:
                               pH;
                               Iron;
                               Aluminium;
                               Cl/SO4 ratio; and
                               Total Suspended Solids.




10 October 2013                                         Cardno                                                         20

Used in these records

About this file

File size
61.0 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment 8- Amended Engineering Report MCU12_0208.pdf · 61.0 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.