                 Figure 2-1: Flood inundation extents for minor to extreme events (Source: Noosa Shire Council Interactive Mapping)




                 Figure 2-2: Inundation extents for minor to moderate flood events (Source: Noosa Shire Council Interactive
                 Mapping)



                 2.1.1.      Minimum design levels
                 Noosa Shire Council specifies minimum flood levels and flood immunity requirements in table 8.2.6.4 of the
                 Flood Hazard Overlay code (Noosa Plan 2020). These minimum design levels seek to manage risk to people
                 and property (performance objective PO1) and are summarized in Error! Reference source not found.
                 below. The proposed development’s floor level is set at 109.230 which is at the existing floor level according
                 to LIDAR data. According to levels obtained from the Six Mile Creek flood study, the maximum 1% AEP
                 (2100) DFE level within the building area is 108.9m AHD. Therefore, the proposed floor level meets the
                 minimum design level described in Table 2-1, and meets acceptable outcome A01 for the performance
                 objective (P01).

                 Table 2-1: Flood Levels and Flood Immunity Requirements (Table 8.2.6.4 Noosa Plan 2020)
                  Type of development               Flood Level (Defined              Minimum design level –            Minimum finished floor
                                                    Flood Event) for a 2100           surface level                     level
                                                    planning period

                  Infrastructure other               1% AEP                            DFE/DSFE or Historical            DFE + 0.3m or Historical
                  than specified                                                      flood level                       flood level + 1m




                 23-0102-SMP01-V1A | Preliminary Stormwater Management Plan | Cooroy Sportsground Preliminary SMP Page 4

Document Set ID: 22785418
Version: 1, Version Date: 29/01/2024
Log in to download the original file

Reference Documents - MCU23 0058 (As Published).pdf · 16.2 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.