                                                                                       Water Supply and Sewerage Analysis



Table 6-5      Noosa on Weyba Proposed Pump Station Details

 Pump           Local        Service       Total
                                                           Pump Station Size (kW)      Rising main Diameter (mm)
 Station ID     Population (EP)            Service EP



 SPSNWA                   679.                 679                    1.56                           100



 SPSNWB                    132                 811                    1.50                           80


 SPSNWC                    409                1,220                   6.87                           100




A small portion of development in Precinct 1 is considerably lower than the surrounding development.
Servicing of this site may not be possible via gravity, as identified in Figure 2.(Appendix A) A small grinder
pump servicing this site may be required, discharging to the nearest gravity main.
Figure 2 illustrates the proposed alignment of gravity mains in the development.

6.3.2          Low Pressure Sewer Pump Stations
Due to the topography of the site, a low pressure sewer network may be proposed for these areas. Typically
confined to the south east of the site, properties in this catchment will each have a small pump station
conveying flow to the northern gravity catchment within the site.

6.4            Conventional Sewerage Pump Station
To discharge to the existing pump station NVL011, the Noosa on Weyba pump station (SPSNW1) would
need to discharge, via 400 metres of 150 mm diameter rising main, along Walter Hay Drive. As detailed in
Section 6.2.1, discharging the flow to NVL011 would require an upgrade of this pump station.
Details of the pump station capacities and discharge rising main is detailed in Table 6-6.

Table 6-6      Noosa on Weyba Proposed Pump Station Detail
                                              Total Pump
              Local                                                     Pump        Rising
 Pump                                         Station        Pump                              Maximum
              Service            Total                                  Station     main
 Station                                      Capacity       Head                              Velocity
              Population         Service EP                             Size        Diameter
 ID                                           (PWWF –        (m)                                 (m/s)
              (EP)                                                      (kW)        (mm)
                                              L/s)


 SPSNW1           896.7            2,117          22          20.05          6.67     150         1.25




Figure 2 (Appendix A) illustrates the proposed sewerage servicing strategy. Due to the mains proposed to
service the development, the ownership and operation of the proposed infrastructure would be granted to
Unitywater




Northbrook Corporation Pty. Ltd.                        Version 4                                        17 September 2013
5101-19                                           Commercial in Confidence                                        Page 13

Used in these records

About this file

File size
11.7 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Attachment 15- Amended Water Supply and Sewerage Analysis MCU12_0208.pdf · 11.7 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.