Water Supply and Sewerage Analysis
3.2 Sewerage
The adopted DSS for sewer is detailed in Table 3-2.
Table 3-2 Adopted Sewerage Network Planning DSS
Item Detail
Average Dry Weather Flow (ADWF) 180 L/EP/d
Peak Wet Weather Flow (PWWF) 900 L/EP/d
Minimum velocity @ PDWF 0.7 m/s
Gravity Main Design Criteria Maximum velocity @ PWWF 3 m/s
Depth of flow @ PWWF 0.75d of pipe diameter
Minimum [email protected] m/s
Rising Main Design Criteria Preferred Velocity 1.0-1.5 m/s
Maximum velocity @ PWWF 2.5 m/s
For SPS with 2 pumps, EACH pump delivers minimum 5 x
ADWF
Pump Station Design Criteria Overflows should not occur at flow < 5 x ADWF or C1 x
ADWF (whichever is the larger).
6hrs at ADWF of “in catchment storage