Information Response - Email 1 of 2 MCU16/0153 & REC16/0041

of 124

Page text shows just the words. Original shows the document exactly as it was published.

Page text read automatically using OCR, there may be inaccuracies

Very large file: it may take a few minutes

The original of this document is very large (22.0 MB). Opening the original or downloading it may take a few minutes. Please be patient and don't click again. The page text is quick to read. If you are on mobile data, it is best to wait until you are on Wi-Fi.

      data and audio recording capabilities so that the source of noticeable dominant events may be
      confirmed and the contribution of extraneous noise sources may be identified. The noise logger is to
      record levels continuously with a sampling period no greater than 1 second and preferably one-eighth
      of a second (FAST response). Of particular interest are the times, durations and frequency spectra of
      trucks accessing the loading dock for deliveries or waste collection prior to 7am daily and vehicle and
      patron noise after 10pm.
      Issue – Noise monitoring of IGA roof plant
      The air-conditioning and refrigeration plant for the IGA are mounted on the roof of the IGA store. The
      noise emissions are stated in the acoustic report to have been previously measured by ASK on the roof
      of the IGA store. Plant noise levels but no acoustic spectral information is provided in the acoustic
      report. The acoustic report does not state whether the propagated noise at the receptor locations is
      likely to be predominantly low frequency, or whether it has low frequency tonal components.
      14. A SoundPLAN noise model of the IGA roof-top mechanical plant shall be prepared based upon
      octave or one-third octave spectral noise data for the roof-top mechanical plant. Noise levels shall be
      predicted which show the predicted noise contours (1m grid) at the motel (first and second storeys),
      the four nearest attached houses (first floor) and the nearest linea unit (first floor), with and without
      the proposed partial enclosure around the mechanical plant. The noise contours shall demonstrate
      that the proposed partial enclosure barrier (1m height above the height of the mechanical plant)
      around the sides of the mechanical plant deck provides sufficient noise mitigation for all affected
      receptors to achieve compliance with the external noise limit.
      15. Noise calculations shall be conducted which predict the internal noise levels in the motel unit (first
      and second levels), houses and linea units (upper levels) to confirm compliance with the internal noise
      criteria in each type of habitable space. Calculations should demonstrate the transmission loss of the
      building envelope of all affected habitable spaces provides sufficient noise attenuation to achieve
      compliance with the internal noise limits for IGA mechanical plant noise emissions, including adverse
      noise character adjustments. The building envelope noise intrusion calculations should be conducted
      in accordance with the method of AS3671 based upon octave spectral levels and the building
      envelope construction details. Building constructions details shall be confirmed for all building
      envelope constructions. Copies of calculations are to be provided for review by Council.
      16. Similarly, maximum noise levels recorded prior to 7am shall be used to demonstrate compliance
      with sleep disturbance criteria in bedrooms for short duration noise events emanating from activities
      on the shopping village site prior to 7am and after 10pm. Building envelope noise intrusion
      calculations for maximum noise levels to demonstrate compliance with the sleep disturbance criteria
      shall be provided for review by Council (as for item 3 above).
      Issue - Noise Monitoring of Peregian Hotel
      The acoustic report has not referenced the hotel license, or the unreasonable noise criteria, or Council
      conditions in its assessment of the noise impact of the hotel approval conditions and operations upon
      the proposed development, in particular, the linea houses along the eastern boundary of the
      development site.
      Information Required
      17. A detailed report of the hotel noise emissions having regard to the License, OLGR unreasonable
      noise criteria and Council conditions. The report is to indicate the noise mitigation plan required for
      the hotel to achieve compliance with all of the relevant criteria and development conditions,
      assuming that the proposed residential development is approved. The detailed report is to be based
      on source noise levels measured at the Peregian Beach hotel site. The noise mitigation plan is to be
      agreed between the hotel and the developer with a formal commitment by each party to implement
      the plan prior to commencement of construction of the proposed development if it is approved by


8816R02V01.docx                                                                                               2
Log in to download the original file

Information Response - Email 1 of 2 MCU16_0153 & REC16_0041.pdf · 22.0 MB (very large file)

Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.