Information Response - Email 1 of 2 MCU16/0153 & REC16/0041
Very large file: it may take a few minutes
The original of this document is very large (22.0 MB). Opening the original or downloading it may take a few minutes. Please be patient and don't click again. The page text is quick to read. If you are on mobile data, it is best to wait until you are on Wi-Fi.
3. Response to Items 14 to 16 – IGA Mechanical Plant Noise
Emissions
Noise calculations were initially undertaken within a spreadsheet format and incorporated distance
attenuation and Fresnel barrier effect algorithms. The noise modelling of the IGA rooftop plant has been
undertaken within Soundplan (Version 7.4). The source noise level data has been reviewed and a tonality
penalty of +2dB has been applied for a potential tonal component in the 200Hz one-third octave band.
The noise levels have been predicted at the nearby sensitive locations with and without the proposed noise
screen. The calculations undertaken with Soundplan indicate that with a 1.0m high screen above the top of
the A/C plant located around the root-top platform the 37dBA Leq,adj,1hour external noise goal is still
exceeded. However, the internal noise goal 30dBA Leq,adj,1hour can be achieved with the windows closed, the
internal noise level calculations are presented in Attachment B. As the windows can be closed to mitigate
the potential noise intrusion, ventilation requirements may need to be considered.
Table 3.1 Predicted Mechanical Plant Noise Levels
Day Level/Floor Predicted Noise Predicted Noise Levels with an Acoustic Screen
Levels without 1.0m Higher than the top of the A/C Plant
Acoustic Screen
LAeq,1hour dBA LAeq,1hour dBA Tonality LAeq,adj,1hour dBA
Penalty dB
House 1 Upper 44 33 2 35
House 2 Upper 46 35 2 37
House 3 Upper 48 36 2 38
House 4 Upper 48 37 2 39
Linea House 25 Upper 47 37 2 39
Linea House 26 Upper 48 38 2 40
Unit 06 1st floor 46 36 2 38
Unit 07 1st floor 46 36 2 38
Unit 08 1st floor 47 36 2 38
Unit 09 1st floor 47 36 2 38
Unit 10 1st floor 48 36 2 38
Unit 14 1st floor 45 32 2 34
Unit 15 1st floor 46 37 2 39
Unit 16 1st floor 46 37 2 39
Unit 22 2nd floor 46 36 2 38
Unit 23 2nd floor 46 37 2 39
Unit 24 2nd floor 47 37 2 39
Unit 25 2nd floor 48 37 2 39
Unit 26 2nd floor 49 37 2 39
Unit 30 2nd floor 51 39 2 41
Unit 31 2nd floor 50 38 2 40
Unit 32 2nd floor 50 38 2 40
The recommended noise barrier is required to have a minimum surface density of 12.5kg/m2 and an
absorptive lining on the plant side of the barrier.
Referring to Item 16 of the Information Request, the existing IGA shopping centre building provides a
significant barrier for emissions from the loading dock area to the nearest proposed houses (Houses 1-4)
8816R02V01.docx 7
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalLog in to download the original file
Very large file: the download may take a few minutes. If you are on mobile data, it is best to wait until you are on Wi-Fi.
Searchable page text hides email addresses. Original files are unchanged and may show email addresses.