Unit Building. Sunshine Beach
Geotechnical Investigations

The design of piled foundations should include assessment of both strength and serviceability limit
states. A geotechnical strength reduction factor of ©, = 0.65 should be applied to the ultimate strength
values when considering the ultimate strength limit state. Where driven piles are adopted, should a
suitable proportion be dynamically tested, a higher geotechnical strength reduction factor of ®, = 0.7
may be adopted.

The geotechnical design parameters for pile design are a function of pile type, size, load and depth.
The type and size of piles in turn depends on the relative cost of altemate piling systems and sizes.

The most cost effective piling system can be designed by your piling contractor based on the Coffey
borehole logs.

Excavations

Soils on the site to a depth of 3 metres may be excavated with conventional earthmoving equipment.
Temporary open excavations in the medium dense to very sands should be battered back at a slope not
steeper than 1.5 horizontal to 1 vertical where the excavation is above the water table and 3 horizontal
to 1 vertical for excavations below the water table. Alternatively, engineered support systems must be
adopted.

Basement Retaining Wall Design

Geotechnical parameters for retaining wall design are as follows:-

Soil internal Angle of Friction 30 degrees
Base Soil Angle of Friction 33 degrees
Soil Unit weight 20 KN per cubic metre

Minimum Depth of Toe Footing 0.5 metres

Minimum Width of Toe Footing 0.6 metres

Allowable Bearing Capacity Founding not recommended in loose sands. See above
100 kPa in medium sands to a depth of 2.4 metres
160 kPa in dense sands at depths greater than 2.4 metres

Propped basement walls retaining drained sand or gravel may be designed assuming a rectangular
pressure distribution with a maximum earth pressure of GH kPa acting over the wall where H is the total
depth of excavation in metres. Where the sand or gravel backfill is undrained, the triangular hydrostatic
pressure distribution must be added to the earth pressures. This does not take into account any
additional lateral earth pressures produced by surcharges such as landscaping, adjacent structures or
vehicles or heavy equipment. Lateral pressures due to shrink swell can be ignored.

Coffey Geotechnics 4
GEOTKPAR13340A/A
22 January 2008

ao hae wb +

Used in these records

About this file

File size
20.7 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

09_1382 - Operational Works - Landscaping & Civil Works [As Published].pdf · 20.7 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.