2.2 Runoff Volumes & Flows
I The site has changed size and layout. The total development site area is approximately 2.32 Ha. The
development site and amount of impervious area have significantly reduced in size, thus runoff
I volumes have significantly reduced compared to those calculated by Cardno in the original report.
The new areas are as follows;
Surface Type Original Areas Proposed Areas (TGM
(Cardno Report) Report)
(Ha) (Ha)
Roof 0,7884 0.667
Impervious Ground 1.325 1.20
Surface
Pervious Areas 0.352 0.456
F1
TGM note that the CARDNO report calculated runoff from the site layout prior to this development
using RAFTS and it then compared to the result calculated using the rational method. Results of the
comparison between the RAFTS and rational methodologies indicated that runoff flow rates were
close and therefore it is expected that a pro-rata adjustment of those flows for the new site areas
will also give acceptable results (i.e. existing discharge calculations adjusted by a factor of
2.327Ha/2.7543Ha).
DRAINS uses rainfall hyetographs from Australian Rainfall & Runoff to simulate actual rainfall events.
The hyetographs mimic the variation in rainfall during a rain storm, therefore for any given average
rainfall intensity DRAINS simulates the peaks and troughs during the storm, so that peak runoff flow
rates may be more than when calculated using the average intensity.
2.2.1 Detention Basin
It is anticipated that all paved areas can be collected and discharged via the detention basin and the
legal point of discharge in Gateway Drive. The construction stage sedimentation basin will be
cleaned at the end of the construction phase and converted into a detention basin and bioretention
cell.
t The outlet pipe from the basin shall be 600mm diameter. The invert of the outlet pipe will be set
300mm above the invert of the basin to allow for an extended detention period for the
sedimentation basin. It is assumed that the extended detention depth is full at the commencement
of the design storms for the purpose of sizing the detention basin.
5
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
OPW11/0023 Development Application part 2 of 2 Planning Report and Plans 178 Eumundi Noosa Road NoosavilleRelated documentApplication case desk ↗