SPECIAL MEETING MINUTES 5 JUNE 2019
i. the facades of the Visitor accommodation Type 4 motel building facing towards
the IGA building and IGA carparking area;
ii. the facades of the Visitor accommodation Type 4 dwelling units facing towards
the IGA building; and
iii. the facades of the Visitor accommodation Type 4 dwelling units facing towards
the hotel building, drive-through access road and drive-through bottleshop, and
carparking areas.
54. Prior to the commencement of use written certification is required from a suitably
qualified person confirming that upgrades to the building facades and provision of
mechanical ventilation/air conditioning comply with the recommendations of the
Second Joint Report of Experts in Noise (30 May 2018) for Planning and Environment
Court Appeal 4066 of 2017.
55. Prior to the commencement of any use or sealing of Plan of Survey, whichever occurs
first, an acoustic screen must be constructed around the IGA rooftop mechanical plant
to a height of 3.0 metres above the roof level plant deck, as shown on Figure 4 and
described in Section 4.6 of the Second Joint Report of Experts in Noise (30 May 2018)
for Planning and Environment Court Appeal 4066 of 2017.
56. Prior to the commencement of use of the Visitor accommodation Type 4 dwelling units
an acoustic barrier along the common boundary of the development site with the
Peregian Beach Hotel must be constructed. The barrier shall be constructed of
materials to achieve a minimum surface density 12.5 kg/m2 and a height 2.5 metres
above the hotel pavement level along the boundary of the site and adjacent to the hotel
drive-through lane and carparking areas, as shown on Figure 4 and described in
Section 4.8 of the Second Joint Report of Experts in Noise (30 May 2018) for Planning
and Environment Court Appeal 4066 of 2017.
57. Written certification is required from a suitably qualified person confirming that sound
pressure levels from all mechanical plant and equipment within the development site
comply with the following when measured at the façade of any habitable room or formal
outdoor area of the Visitor accommodation Type 4 motel building or the Visitor
accommodation Type 4 dwelling units. Noise levels to be measured as LAeq adj 15min
where adjustments refer to tonality or impulsivity, in accordance with the most recent
edition of the Queensland Noise Measurement Manual:
a. Air-conditioning and Refrigeration
i. 7am to 10pm: Maximum level allowable = background + 5dB(A)
ii. 10pm to 7am: Maximum level allowable = background + 3dB(A)
b. Pumps
i. 7am to 7pm: Maximum level allowable = background + 5dB(A)
ii. 7pm to 10pm: Maximum level allowable = background + 3dB(A)
iii. 10pm to 7am: No audible noise.
The certification must be submitted to Council prior to commencement of the use,
which certifies that operational noise from any fixed plant and equipment complies with
the requirements of this Decision Notice.
58. Written certification is required from a suitably qualified person confirming that sound
pressure levels from all mechanical plant and equipment from the existing IGA
shopping centre comply with the following when measured at the boundary of the newly
created lot. Noise levels to be measured as LAeq adj 15min where adjustments refer
to tonality or impulsivity, in accordance with the most recent edition of the Queensland
Noise Measurement Manual:
Page 14 of 16