([D)MWH.                                                    Noosa on Weyba Water Network Performance Assessment




  Table 2-1: EP Summary for Proposed Noosa on Weyba Development




                                                         339 lots                2.3 EP x lot                      779.7
                                                                           (assumed 2 bedroom
                                                                                  unit)

                                                         600 m2                 100 EP per ha                        6


                                                                                                Total            2,415.9



  The water supply demands as flows for the proposed development were supplied by Card no and
  confirmedby MWH. A Peak Hour demand of 31 LIs and a fire flow demand of 51 LIs (30 Us + 2/3
  maximum hour) at the development site were confirmed. Table 2-2 details the demand distribution into
  the H20MAP Water model. The location of proposed development connections are shown in Figure 2-1.

  Table 2-2: Model Demand for Proposed Noosa on Weyba Development


                                                      Option 1                     Option 2                     Option 3
            Model Junction ID /
                                                 Peak          Fire            Peak            Fire        Peak            Fire
                  Description
                                                 Hour          Flow            Hour           Flow         Hour            Flow
                                                 (Lis)         (Lis)           (Lis)          (Lls)^       (Lis)           (Lis)

   NOOSA_ON_WEYBA_CONN1,                      31.32          50.88         31.32          50.88         31.32            50.88
   proposed development
  connection #1


   NOOSA_ON_WEYBA_CONN2,                                                   3              32
   proposed development
  connection #2

   ^
       Both fire flow demands do not occur simultaneously




   3              Standards of Service
  The standards of service for water supply applicable to this investigation are as follows:
              Minimum residual pressure                                            >= 22 m

              Fire flow demand assessed                                            at 2/3 PH demand
              Minimum pressure under fire flow demand at hydrant                   =   12 m
              Maximum velocity                                                     =   2.5 Us

  The above standards have been been adopted from the Unitywater Desired Standards of Service.




  Status: Draft                                                                                                           22/06/2012
   Project number:                                                Page 3                  Our ref: Noosa on Weyba WS Assessment.docx

Used in these records

About this file

File size
29.5 MB (very large file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

Part 7 of 37 Appendix 5 - Water and Sewer Infrastructure Report MCU12_0208.pdf · 29.5 MB (very large file)

The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.