Figure 6.1 – Drains Model Layout
Peak flow rates determined for each 3 cases are outlined in Table 6.6.
Table 6.6 – Comparison of Peak Flows
AEP Q1 Q2 Q5 Q10 Q20 Q50 Q100
Storm (1EY) (0.5EY) (0.2EY) (10%AEP) (5%AEP) (2%AEP) (1%AEP)
Existing 24 33 45 56 69 83 95
(L/s)
Developed 40 50 62 69 83 102 118
(L/s)
Mitigated 24 (0) 31 (-2) 45 (0) 56 (0) 69 (0) 79 (-4) 91 (-4)
(L/s)
As shown in Table 6.6 the proposed detention tank has demonstrated the proposed mitigated peak
discharge flow rates will not exceed the total pre-development flows for all design storms, up to and
including the 1% AEP Design Storm. Refer Appendix D for the drains results.
The proposed stormwater detention system is therefore considered to be adequate for the development.
SCG Consulting Engineers Page 14 SCG Ref: 33114(SWMP)