Reinforcement:
                Reinforcement is to comply with the following :
                a) Concrete cover around the reinforcement must be 40mm to unprotected ground, 40mm to external
                exposure, 30mm to the membrane in contact with the ground, and 20mm to the internal surface. The
                slab fabric shall be placed towards the top of the slab within the zone defined by these limits.   We
                recommend 30mm top cover.
                b) Slab fabric must be lapped by one full panel of fabric so that the two outermost transverse wires of one
-               sheet overlap two outermost transverse wires of the sheet being lapped. Slab fabric is to be supported on
                 bar chairs placed at 800mm ctrs.                       -
                 ¢) Trench mesh must have ail cross wires cut flush with the outer main wires. Trench mesh in slab and
                 edge beams must be overlapped by the width of the fabric at “T” & “L” intersections. Trench mesh must
                 be spliced, where necessary, by a !ap of 500mm.
                 d) Pre-Fabricated footing cages or reinforcing bars at “T” & “L” intersections are to have a Y12 comer
                 lapping bar top and bottom and lapped 500mm with adjacent bars.
                 e) The minimum fap length of reinforcing bar is to be 500mm or 25 bar diameters, whichever greater.
                 7.0    ARTICULATION REQUIREMENTS:
                 The specifications in this report have been specifically formulated for articulated masonry construction.
                 This usually results tower construction costs. All masonry walis must have full height articulation at a
                 maximum spacing of 8 meters. The articulation joint must separate the masonry from footing to eaves
                 fevel at this spacing. Masonry must be supported on each side of the joint in an approved manner to
                 retain its structural integrity. :                                                       ;
                 Where used, internal masonry walis should be articulated in accordance with the masonry manufacturers
                requirements for the width and type of unit used. In no instance should the spacing exceed 4.0m and
                 articulation should always be provided at an abutment with an external wall.
                 If articulation of masonry is found to be unacceptable, the footing system will require re-designing.
                 in addition to joints in masonry, articulation is achieved wherever a 40mm (min) separation in masonry
                 from footings to eaves is achieved. For example, where timber panels are used above and / or below
                 doors and windows.
               _ Where it is necessary to construct construction joints to meet the articulation requirements, they can be
                  placed in places of limited visibility. For example behind downpipes. Internal masonry walls should be
                  articulated where they abut the perimeter walls.
                  The designer of the building must also ensure that articulation is established:           .
                  1,     Adjacent to a change in floor level which exceeds 400 mm.
                 2.      if any proposed extension abuts any existing structure, full height articulation must be established
                         where the new masonry joins the old.
                 3.      Where a masonry wall transgresses from one footing type to another - e.g. from a perimeter
                         footing to a continuous footing.
                  If the building has any masonry arches we must be contacted for further advice.
                  Methods of articulation are well documented in “Technical Note 61” by the Cement & Concrete
                  Association.

                  $CG CONSULTING ENGINEERS                          5                                  SCG Ref: 16078(S)

Used in these records

About this file

File size
702 KB (small file)
File type
PDF

No other editions are linked here.

Original file

Log in to download the original file

0015CE08.001.pdf · 702 KB (small file)

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.