The site has been identified on Noosa Shire Councils Potential and Actual Acid Sulphate Soils Overlay Map. As the proposed
development is to undertake filling and excavation below RL20.0m AHD, it is anticipated that Acid Sulphate Soils may be
encountered. Therefore, it is recommended that an Acid Sulphate Soil investigation be completed as part of the detailed
geotechnical investigation conducted for the site. If Acid Sulphate Soils are present, then an Acid Sulphate Soil Management
Plan will be required.
All earthworks will be undertaken in accordance with the Noosa Shire Council guidelines.
3.3 ROADWORKS
The proposed road works are as follows:
− Three new driveway crossovers are proposed from the private access road into Lot 3, to provide vehicle access to
the basement carpark, ground-level carpark, and loading docks. Two new driveway crossovers are proposed from
the private access street into Lot 7, to provide vehicle access to the surface carparking and loading docks;
− Multiple pedestrian entrances into both Lot 3 and Lot 7 are proposed along the private access roadway;
− A pedestrian walkway is proposed along the existing pedestrian access easement along the western side of Lot 3,
which will connect with a new pedestrian bridge that spans across the environmental zone and natural drainage
channel between the Lot 3 development and the existing shopping centre to the west; and
− All proposed road works will be undertaken in accordance with Noosa Shire Council Guidelines.
Refer to the engineering drawings in Appendix B for further information.
3.4 SEWER
3.4.1 Existing Infrastructure
The Unity Water As-Constructed Plans of the surrounding area indicate the following existing sewer reticulation information:
− An existing 225mm dia. sewer main is located below the western verge of the private access roadway at the southern
boundary of both development sites; and
− There are two existing 150mm dia. capped property connections into both Lot 3 and 7 respectively, with the Lot 3
property connection running below the existing private access roadway to the eastern verge.
The Unity Water As-Constructed Plans of the existing sewer infrastructure can be found in Appendix C of this report.
3.4.2 Proposed Infrastructure
The proposed sewer infrastructure for this development is as follows:
− It is proposed to construct two new property connections into the existing maintenance hole to service both Lot 3
and Lot 7 sites, which suit the internal development layout and driveway crossover placement;
− The existing property connection into Lot 7 is to be decommissioned, whilst the existing property connection into
Lot 3 is to remain to allow for future development of the area to the south of the Lot 3 development; and
− As the surrounding roadways and services have been master-planned to service a fully developed catchment, it is
expected the existing sewer infrastructure has sufficient capacity to service the proposed development.
Refer to Appendix B for preliminary drawings of the proposed sewer works.
www.bornhorstward.com.au Page 6
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
Attachment 5 - Servicability Report.pdfRelated documentApplication case desk ↗
About this file
- File size
- 21.0 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.