Log in to see the plans as drawnPerformance outcomes Acceptable outcomes
PO1 AO1.1
Development maintains the safety of people and property from the Development which will materially increase the number of
adverse impacts of bushfire. people living or congregating on premises, including
reconfiguring a lot, is not located within a medium or high
bushfire hazard area.
AO1.2
Development maximises setbacks from hazardous vegetation to
achieve an acceptable risk.
Editor’s Note — PSP8 Natural Hazards provides guidance for
assessing bushfire hazard risk and preparing a bushfire hazard
management plan.
Impacts on Ecologically Important Areas
PO2
Bushfire mitigation measures do not adversely impact on: No acceptable outcome provided
(a) biodiversity values, connectivity and ecosystem functioning;
and
(b) the long term physical integrity of waterways, wetland and
areas of native vegetation.
Water Supply for Fire Fighting Purposes
PO3 AO3.1
Development provides an adequate water supply for fire fighting Premises are connected to the reticulated water supply.
purpose which is reliable, safely located and freely accessible.
Editor's note—For reconfiguring a lot, water supply needs to
provide for a minimum flow and pressure of 10 litres a second
at 200kPa at all times for fire fighting purposes.
OR
AO3.2
Where there is no available reticulated water supply, the premises
has:
(a) an accessible dam, swimming pool or water tank available
for fire fighting purposes with an onsite water volume of not
less than 5,000 litres; and
(b) a water supply outlet pipe 50 milimetres in diameter fitted
with a standard fire brigade fitting connected to the water
supply (other than where the water supply is in a swimming
pool or dam).
Editor’s Note—Water supply capacity for fire fighting purposes is
in addition to water supply capacity for other uses and activities on
the premises.
Essential Community Infrastructure
**FINAL DRAFT Post Consultation 2019**