1.0 Summary
The proposed residence at 71 Seaview Terrace, Sunshine Beach comprises the
following:
• Generally two living levels
• Access driveway at road level/roof level, ramping down to garage level
• External terraced areas, pool and access corridors
• Elevated timber and steel walkway and observation deck
The Structural design of the project will consider the steep sandy nature of the site
and will be carried out in accordance with the relevant Australian Standard Codes
of Practice including but not limited to the following:
• AS/NZS 1170 Part I Loading Code : Dead and Live
• ASINZS 1 170 Part 2 Loading Code : Wind
• AS/NZS 1 170 Part 4 Loading Code : Earthquakes
• AS2159 Piling Code
• AS 3600 Concrete Structures
• AS 3700 Masonry Code
• AS 4100 Steel Structures
• AS2783 Swimming Pool Code
• Building Code of Australia
The maximum loading deflection criteria to be adopted for the development is as
follows:
a) Horizontal (Lateral) movement (wind and seismic)
Total not greater than Height/500 (at maximum permissible stress loads)
Inter-storey not greater than Floor to Floor Height/500 (at maximum
permissible stress loads)
b) Horizontal (lateral) movement of retaining walls due to horizontal loads
from retained soil and surcharge - not to exceed height/500.
c) Vertical movement (dead plus live load)
Slab and beams are to be designed to achieve the following maximum
deflection criteria
Incremental Deflection
General Span/500 or l5mm (whichever is less)
Long Term Deflection
Slabs Span/500 or 15mm (whichever is less)
Beams Span/500 or 15mm (whichever is less)
Spandrel Beams Span/500 or 15mm (whichever is less)
Total allowable 20mm max to end spans
(Slab + Beam) 20mm to internal spans
Cantilever Span/250 or 10mm (whichever is less)
The structural framing system is to comprise a reinforced concrete frame utilising
permanent reinforced concrete slabs, beams and columns. External decks and the
garage floors are to be 40 MPa reinforced concrete slabs and beams. All piled
3
See the original
The page text is free to read. Viewing or downloading an original file needs an account.
Log in to see the originalUsed in these records
2008/0169 Response to information request - 71 Seaview Tce Sunshine BeachRelated documentApplication case desk ↗
About this file
- File size
- 31.0 MB (very large file)
- File type
No other editions are linked here.
Original file
Log in to download the original file
The download may take a few minutes. On mobile data, it is best to wait for Wi-Fi.