Attachment 4 - Building Certifier Advice & Flow Pressure Test Results.pdf

of 5

Page text read automatically using OCR, there may be inaccuracies

Australian Fire Services Testing # 11647.3

www.firetesting.com.au PH: 1800 347 383
Part E—Pump appliance booster test | PASS | O | FAIL ja

This part relates to sections 10.4 and 10.5 of AS2419.1 If pressure/flow rates do not meet the fire system design criteria and there are
contact the relevant water service provider to ascertain if there are any problems with the water system network. In the tal

 

 

 

  
   

n-site problems,
low, please
record the pressure readings obtained during the pump appliance booster test.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hrdant locations | ee en | ae | m
System requirements | I/s @ | kPa Static pressure at booster kPa
Pump inlet pressure kPa Booster supply pressure kPa
Boost pressure kPa Calculated frictional loss kPa
Part F—Spripkter hydrostatic test pass | CO | FAIL oO
Sa

Part G—Sprinkler system flow test PASS | O | FAIL x

Sprinkler Requirements 905l/m@185kPa Sprinkler Achieved 810I/m@40kPa

Part H—Compliance

Critical defects Yes | C1 | Give owner/occupier a critical defect notice

identified No 0 | Noaction required in relation to critical defects at this time

Repairs/corrective Yes | O | Attach details (including action and date taken) as part of Licensee's report

actions taken No No action required in relation to repairs/corrective actions at this ime Refer below
System Pass| 0) | Submit Form 72 to Owner / Occupier

Fail | Xl | Submit Form 72 to Owner / Occupier

 

 

 

 

Part I—Signature

 

By signing this Form 72, | confirm that the information contained herein is correct to the best of my knowledge given the information available
and that this Form 72 has been completed in accordance with the relevant standards, codes and regulations.

 

 

 

 

 

 

 

 

 

 

Licensee Bruce Dan Licence no. (BSA/PIC) Licensee SLIIH)
Name M.App.Sc — Fire & Risk Engineering Signature ee
739305
For and on behalf of AFST Pty Ltd
Comments
1. Part D unassisted flow & pressure test fails.
2. Block Plan is defective and needs to be redrawn and replaced — refer page 3
3. One Double head Hydrant is obscured by a tree fern — refer page 4
4. Automatic fire sprinkler system flow and pressure test performed at the alarm valve fails — refer

page 4
5. SeeAFST report 11647.3 Report of street mains testing results

 

 

 

Note: Building owners/occupiers are responsible for ensuring their buildings continuously meet fire safety standards. Where a building owner/occupier becomes aware that their building does not

meet the minimum requirements for water pressure required by any standard applicable under the Queensland Development Code Mandatory Part 6.1 (Maintenance of fire safety installations)

the building owner/occupier should contact the Queensland Fire and Emergency Service.

Definitions “Commissioning test” is a test that is required upon completion of a new system or an extension to an existing system. “Running test” means a two inch waste test installed at the sprinkler
control valve on older systems

Privacy: The information on this form is collected for purposes related to monitoring compliance under the Plumbing and Drainage Act 2002, the Building Act 1975 and the Building Fire

Safety Regulation 2008 (“legislation”). This information may be stored in the department's database and may be used for statistical research, information provision and evaluation of Plumbing Industry
Council and state government services. Your personal information may be disclosed to other government agencies, local government authorities and third parties for purposes related to this
application

Except for these circumstances, personal information will only be disclosed to third parties with your consent or in accordance with the Information Privacy Act 2009.

RTI: The information collected on this form will be retained as required by the Public Records Act 2002 and other relevant Acts and regulations, and is subject to the Right to Information regime
established by the Right to Information Act 2009. If you have any further questions regarding your privacy, please email Building Codes Queensland on [email protected] © The State of
Queensiand.(Deparimentbof,bousing-and: Public: Works) sJilly-2014-Published:bysthe Queensiand-Governmenindtli-201444- George Street» BrisbaneQLD.4000

Log in to download the original (Attachment 4 - Building Certifier Advice & Flow Pressure Test Results.pdf)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.

The supporting record

Open full page ↗

Source document

Analyse documents ↗Open full page ↗

My Comparisons

Choose two to four records of the same kind. Drag using a handle or use the “Compare” buttons.

Your selected records are saved in this browser for your account. Results use the filters on the page where you choose “Compare selected”.