Building Approval (Applicant) v1

Attached to the e-mail Change to DA (GIA) - MCU16/0140.02.

of 4

Page text shows just the words. Original shows the document exactly as it was published.

                                Deemed To Satisfy/Reassessment/Building Approval

        Job Details
        Job Name:                      New Building
        Address:                       42 Hoffman Drive, NOOSAVILLE QLD 4566

        Building Details
        Class:        7b                            Floor Area:    2322m²     Effective Height:       3.7m
        Size of Largest Fire Compartment:           1000m²                    Rise in Storeys:        2
        Legislation: 01-05-16 (BCA2016)

        Drawings
        Dwg11.0416.1GPage1G                  Dwg11.0416.2GPage2G               Job190523-H-001-PR-B




        Deemed To Satisfy Components

        Type of Special Fire Service                                                       Assessment
        Fire Mains (including booster and/or pumps)                                          Suitable
         • achievement of specified performance
         • location and suitability of booster connections and enclosures
         • location and suitability of internal and roof hydrants and external
           hydrants including fire separation from adjacent buildings
         • provisions for hard standing for fire appliances

        Comments:
        Required flow and pressure is 20 L/s @ 350 kPa (unassisted) and 20 L/s @ 700 kPa (boosted).

              ● Certification indicating compliance of system performance with AS 2419 will be required upon
                completion of the project.
              ● A flow report indicating the available flow of water from the required number of hydrant outlet


                is to be provided prior to the final inspection.
              ● The QFES requires block plans for hydrant booster cabinet to be:


                - Etched, engraved or printed on metal or plastic that is suitable for installation in an outdoor
                location (paper enclosed within a plastic or laminated cover is not acceptable)
                - A minimum of A3 in size
                - Mechanically secured in the requiring location
                - Correctly orientated to the building/site, and
                - Meet all of the other requirements of Australian Standard 2419.1- 2005 including the features
                identified on the plan.
              ● Hydrant locations appear satisfactory for the open plan design only - distances will be


                checked upon final inspection to ensure compliance.




        Fire Detection and Alarm Systems (Detection System)                                   Suitable




Page 3 of 4                                            Version 1                                  QFES Job No: 17-01628
Log in to download the original file

Building Approval (Applicant) v1.pdf · 105 KB (small file)

Searchable page text hides email addresses. Original files are unchanged and may show email addresses.