Building Approval (Applicant) v1
Attached to the e-mail Change to DA (GIA) - MCU16/0140.02.
• achievement of specified performance of detection and alarm
systems
• location and operation of main fire indicator panel, sub-indicator
panels, mimic panels, local alarm bells and directional signs
• suitability of nominated types of detection in all areas, and the
location of manual call points
• suitability of weather protection, accessibility and lighting of
equipment
Comments:
● A Fire Detection and Alarm System is required to be installed in accordance with BCA & AS
1670.1.
● Compliance certification including 'As Installed' drawings, Commissioning test report, Installers
Statement and/or Form 16 is to be provided upon inspection.
● From previous experience of Building A it was assumed the doors located within the FRL
walls are to held open with magna latches which are to be operated via a detection system.
Certification is required for each Special Fire Service, this will be required prior to or at the time of
inspection.
Page 4 of 4 Version 1 QFES Job No: 17-01628