Stormwater Technical Memo · MCU23/0096
Figure 2. Extent of Proposed Arts Centre (right) transposed on existing (left). Table 1. Estimated Surface-Split Breakdown. Note: the garden and green corridor attached to the proposed building are included in the area calculations. Surface-Split Existing Proposed Roof Area (m2) 0 1,200 Road/Pathway (m2) 1,200 0 Garden/Open Space (m2) 0 165 Total (m2) 1,200 1,365 4 HYDROLOGIC ANALYSIS In accordance with the Queensland Urban Drainage Manual, peak stormwater flows are calculated based on impervious fractions. As shown in Table 2, the impervious fraction between the existing and proposed areas do not significantly change. This indicates that there will not be any significant changes to peak flows, and as such, detention is not required. Table 2. Impervious Fraction Estimate. Hydrological Assessment Existing Proposed Impervious Area (m2) 1,200 1,200 Impervious Fraction (%) 88 88 Technical Memo | 21-0211TM-SW01-v3 |Good Shepherd Page 3